Accessories 1
Installation kit – for installation remote from solid walls
06/2015 – DE/en
FK-EU
1
/
WE
/
Order code detail
Application
– Dry mortarless installation remote from solid
walls or ceiling slabs requires an installation kit
– The installation kit contains all special parts
– Cut-to-size calcium silicate boards
are to be provided by others
– Fire damper and installation kit
are supplied partly assembled
– Assembly and installation
are to be performed by others
– The fire damper and the installation kit
must be installed and secured according
to the fire damper operating and installation
manual and the WE installation manual
– Fire dampers with installation kit
only with casing length L = 500 mm
Materials and surfaces
– Installation kit made from special insulation
material and mineral wool strips
– Fixing elements made of galvanised steel
– Existing ducts made of galvanised steel
Description
K 4 – 1.1 – 21
Installation kit for dry mortarless installation remote from solid walls
L [mm]
Order code
500
WE
To be provided by others
Name
Property/size
Mineral wool
Gross density
≥
80 kg/m³, melting point > 1000 °C
Mineral wool, 80 mm thick (slab)
Gross density
≥
80 kg/m³, melting point > 1000 °C
Fixing tab
HUS-H 6 × 100
Washer
8.4, EN ISO 7093-1
Hexagon head screw
M8 × 16, EN ISO4017
Hexagonal nut
M8, EN 24032
Dry wall screw
∅
5 × 50,
∅
5 × 70,
∅
5 × 80
Threaded rod
M12
Hilti mounting rail
MQ 41-3 or equivalent
Hilti perforated plate
MQZ L13 or equivalent
Steel wire clip
63/11, 2/1, 53
Adhesive
Promat K84
PROMASEALMastic fire protection mastic
Paste
Promatect-LS and Promatect-H
–
Other details according to the WE installation manual.