background image

EK-JZ

R

C1

/

DE

/

1200 × 2030

/

EGS

/

A0

/

B24A

|

|

|

|

|

|

|

|

1

2

3

4

5

6

7

8

1 Type

EK-JZ Smoke control damper

2 Actuator encasing as seen from the operating side

R = On the right (as standard)

L = Left

3 coating

No entry = none

C1 = Promat SR impregnation

4 Country of destination

DE Germany

Other destination countries upon request

5 Nominal size [mm]

B × H

6 Accessories 1

EG = fibre paper bottom (standard)

EGS = bottom and side

MA = fixing tab

EGSMA = possible

(E = Ètanchêité)

(S = site)

(G = ground)

7 Attachments 1

No entry: none

F0, 0F, FF Connecting subframe, galvanised steel Cover grilles

A0, 0A, AA Crimped wire mesh, 20 × 20, galvanised steel

B0, 0B, BB Square perforated metal plate, 10 × 10, galvanised steel

C0, 0C, CC Grille with slanted blades made of aluminium

D0, 0D, DD Grille with slanted blades, aluminium, additionally with crimped wire mesh, 20 × 20, galvanised steel

E0, 0E, EE Grille with slanted blades, aluminium, additionally with welded wire mesh, 6 × 6 mm, galvanised steelSign 1 defines operator side,Sign 2 defines

installation side,Example: FA: Connecting subframe on the operating side, crimped wire mesh on the installation sideAny combination is possible

8 Attachments 2

Belimo actuators

B24 BE 24-12; BLE 24-12, 24 V AC/DC

B230 BE 230-12; BLE 230-12, 230 V AC

Combinations of actuator and control module

B24A BE 24-12 / BLE 24-12, with AS-EM/EK, 30 V DC (AS-i)

B24AS BE24-12 / BLE 24-12, with AS-EM/SIL2, 30 V DC (AS-i)

B24BKNE BE 24-12 / BLE 24-12, with BKNE230-24

B24C BE 24-12 / BLE24-12, with BC24

B24D BE 24-12 / BLE 24-12, with BRM-10-F-ST

B230D BE 230-12 / BLE 230-12, with BRM-10-F

B24AM BE24-12 / BLE24-12, with AS-EM/M, 30V DC (AS-i), for function C

Order example: EK-JZ-R-C1/DE/800×1030/ES/A0/B24A

Actuator encasing

Operating side, on the right

Coating

Impregnation

Country of destination Germany
Nominal size

800 × 1030

Accessories 1

Fibre paper, fixing tab

Attachment 1

Cover grille on the operating side

Attachment 2

24 V AC/DC with TROXNETCOM control module AS-EM/EK

mod

Homepage

>

Products

>

Fire and Smoke Protection

>

Smoke Control Damper

>

Type EK-JZ

Home Contact Imprint Delivery and payment terms Privacy Disclaimer

20.12.2020 © TROX

Austria GmbH

Содержание EK-JZ

Страница 1: ...l sizes 200 430 1200 2030 mm for smoke gas flow rates up to 87700 m h or 24360 l s at 10 m s Quick and easy installation in or on building structures for smoke and heat exhaust remote control with an...

Страница 2: ...combined systems and thus pneumatic volume flow rate balancing via the selection of intermediate positions Complies with the requirements of EN 12101 8 Tested to EN 1366 2 and 1366 10 for fire resist...

Страница 3: ...control TROX X smoke exhaust fans from the X FANS subassembly Smoke exhaust fan for roof installation BVDAX BVD Smoke exhaust fan for wall installation BVW BVWAXN Smoke exhaust centrifugal fan BVREH B...

Страница 4: ...eliability of the smoke control damper must be tested at least every six months this has to be arranged by the owner of the smoke extract system functional tests must be carried out in compliance with...

Страница 5: ...n automatically or manually triggered control signal According to the specified time temperature curve an EK JZ can still fully open or close after 25 minutes MA manual release Similarly position chan...

Страница 6: ...30 1050 430 2 0 32 0 45 30 1100 430 2 0 34 0 47 30 1150 430 2 0 35 0 49 30 1200 430 2 0 37 0 52 30 200 630 3 0 09 0 13 36 250 630 3 0 12 0 16 35 300 630 3 0 14 0 19 34 350 630 3 0 16 0 22 33 400 630 3...

Страница 7: ...27 200 1030 5 0 16 0 21 34 250 1030 5 0 2 0 26 33 300 1030 5 0 24 0 31 32 350 1030 5 0 28 0 36 31 400 1030 5 0 32 0 41 31 450 1030 5 0 35 0 46 30 500 1030 5 0 39 0 52 30 550 1030 5 0 43 0 57 29 600 10...

Страница 8: ...6 1 14 1 48 25 200 1430 7 0 22 0 29 32 250 1430 7 0 28 0 36 31 300 1430 7 0 33 0 43 30 350 1430 7 0 39 0 50 30 400 1430 7 0 44 0 57 29 450 1430 7 0 50 0 64 29 500 1430 7 0 55 0 72 28 550 1430 7 0 61 0...

Страница 9: ...30 8 1 52 1 96 24 200 1830 9 0 29 0 37 31 250 1830 9 0 36 0 46 30 300 1830 9 0 43 0 55 29 350 1830 9 0 50 0 64 29 400 1830 9 0 57 0 73 28 450 1830 9 0 64 0 82 28 500 1830 9 0 71 0 92 27 550 1830 9 0 7...

Страница 10: ...1 83 2 33 23 1200 2030 10 1 91 2 44 23 B H n Number of blades n Cross section A m Cross section A m Sound reduction index R dB Free 2 geo 2 w Quick sizing tables provide a good overview of the volume...

Страница 11: ...and casing airleakage to EN 1751 class C Low sound power level and differential pressure Any airflow direction Manual release is also possible using TROXNETCOM Integration into the central BMS with st...

Страница 12: ...tor side Sign 2 defines installation side Example FA Connecting subframe on the operating side crimped wire mesh on the installation sideAny combination is possible 8 Attachments 2 Belimo actuators B2...

Страница 13: ...issioning Installation on in concrete or masonry shaft walls Installation in lightweight partition walls Installation in shaft walls that are covered on one side Installation in or on tested fire resi...