Operating manual – IDS 100

EN

B-7

Problem

Reset button

Cause

Error correction

Operation indicator Self-diagnostic 

indicator

Fan does not start running 
and flame is not ignited

switched off

-

Control  device  is  incor-
rectly set

-  Check  if  the  control  equipment  is  correctly  set

(e.g. the temperature set at the thermostat must
be higher than the room temperature).

Control device defective

-  Have the control device replaced by the customer

service.

Fan  does  not  start  run-
ning or switches off dur-
ing start-up or operation

flashing  orange 
light

-

no power supply

-  Check the characteristics of the electrical system

(230 V -1~ - 50 Hz).

-  Check  the  function  and  position  of  the  selector

switch.

-  Check if the fuse is intact.

Voltage < 175 V

-  Check  the  supply  voltage. The  device  will  auto-

matically restart if the voltage exceeds 190 V.

Voltage > 265 V

-  Check  the  supply  voltage. The  device  will  auto-

matically restart if the voltage falls below 250 V.

Fan  switches  off  during 
start-up or operation

continuous  red 
light

flashing  orange 
light

Flame  is  present  prior  to 
the  ignition  of  the  trans-
former

-  Contact the customer service and have the device

cleaned  and  heating  oil  residues  removed  from
the combustion chamber.

Photoelectric cell defective -  Have the photoelectric cell replaced by the cus-

tomer service.

flashing red light 
or  flashing  red/
green light

Motor winding interrupted 
or blown

-  Have the motor replaced by the customer service.

Motor bearing blocked

-   Have the motor bearing replaced by the customer

service. 

Motor capacitor blown

-  Have  the  motor  capacitor  replaced  by  the  cus-

tomer service.

no ignition

-  Check the connections of the ignition cables to the

electrodes and the transformer.

-  Check the position and the distance of the elec-

trodes.

-  Check if the electrodes are clean.
-    Have  the  transformer  replaced  by  the  customer

service.

Flame  control  system  de-
fective

-   Have the flame control equipment replaced by the

customer service.

Photoelectric cell defective -  Have the photoelectric cell cleaned or replaced by

the customer service.

Burner  is  not  or  only  in-
sufficiently  supplied  with 
heating oil

Contact the customer service in order to:
-  have  the  integrity  of  the  coupling  between  the

pump and motor checked.

-  have  the  heating  oil  circuit  checked  for  air  that

may have entered the circuit and to have the tight-
ness of the lines and filter seal checked.

-  have the nozzle cleaned or replaced.

Содержание IDS 100

Страница 1: ...IDS 100 EN OPERATION MANUAL OIL HEATER TRT BA IDS 100 HS 003 INT ...

Страница 2: ...eating unit for the first time Please store this operating manual and keep it within reach in order to consult it if necessary Please observe all safety instructions and information on use and main tenance contained in this manual This manual should be attached to the device if the latter is made avail able to other persons for use Legend WARNING SYMBOL This symbol is followed by a hazard warning ...

Страница 3: ...Do not apply any liquids to the interior of the device If this does happen nevertheless pull out the power cord and have the de vice checked by a specialist workshop Risk of injury Do not insert any objects into the intake and exhaust opening of the device Do not reach into the existing openings Do not leave children or animals unattended near the operating device Do not operate the device in room...

Страница 4: ... for people and property The following points are to be observed during installation The device may be operated indoors and in roofed outdoor areas The device must be installed in a stable position and placed on a fireproof surface The device must be installed near a chimney or external wall The device must be connected to a properly secured mains socket The installation room of the device must be...

Страница 5: ...e to a properly secured mains socket 230 V 50 Hz 10 A On construction sites a residual current circuit breaker must be connected upstream of the mains socket according to VDE 0100 0105 The oil heating unit is now ready for operation Use the device according to the functions described in chapter 12 Functions and operation 11 Exhaust system Before planning the installation of the exhaust system the ...

Страница 6: ...noz zle may be insufficient This will cause the flame control system to be activated and the device will be blocked Wait for approx 1 minute Press and hold the reset button for at least 5 seconds Switch on the device If the device is still not starting up Make sure that there is enough heating oil in the tank Press the reset button In order to determine the cause of the fault see the chapters Safe...

Страница 7: ... a wet cloth The painted and plastic surfaces may not be scoured Do not use any solvent based cleaning agents 15 Disposal The heating oil must be drained from the tank of the oil heating unit and collected Oil heating unit Electronic equipment may not be disposed of in the domestic waste but must be correctly disposed of in accordance with the EUROPEAN PARLIA MENT directive 2002 96 EC of 27th Janu...

Страница 8: ...ustomer service and have the device cleaned and heating oil residues removed from the combustion chamber Photoelectric cell defective Have the photoelectric cell replaced by the cus tomer service flashing red light or flashing red green light Motor winding interrupted or blown Have the motor replaced by the customer service Motor bearing blocked Have the motor bearing replaced by the customer serv...

Страница 9: ...s Have the position of the air setting ring checked by the customer service Have the support disc of the burner cleaned by the customer service Supply of combustion air too high Have the position of the air setting ring checked by the customer service used heating oil contami nated and or containing water Replace used heating oil with clean heating oil Clean the heating oil filter air has entered ...

Страница 10: ...ty thermostat FUA Fuse LI 2 Overheating protection thermostat L1 RV Selector switch EV 1 Solenoid valve I stage FA Air regulator EV 2 Solenoid valve II stage IT Ignition transformer LF RFI filter RF Heated filter optional DV Change over switch power stage high low TF Plug for heated filter TD Transformer Setting of the air setting ring A Type IDS 100 Parameter Value Setting of air setting ring A 1...

Страница 11: ......

Страница 12: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com ...

Отзывы: