Error codes

The following error codes can be indicated on the display (17):

Error code Display

Fault

Cause

Remedy

F1

COOLING mode 
indication (16) 
lights up briefly 
in a 3-second 
cycle

Temperature sensor for the 
ambient temperature

• The terminals at the temperature sensor for the 

ambient temperature and at the mainboard are 
loose or have no contact

Contact Trotec

• Short circuit at the mainboard
• Temperature sensor for the ambient temperature 

defective

• Mainboard defective

F2

COOLING mode 
indication (16) 
lights up briefly 
twice in a 
3-second cycle

Temperature sensor for the 
evaporator

• The terminals at the temperature sensor for the 

evaporator and at the mainboard are loose or 
have no contact

Contact Trotec

• Short circuit at the mainboard
• Temperature sensor for the evaporator defective
• Mainboard defective

F4

COOLING mode 
indication (16) 
lights up briefly 
four times in a 
3-second cycle

Temperature sensor for the 
condenser

• The terminals at the temperature sensor for the 

condenser and at the mainboard are loose or 
have no contact

Contact Trotec

• Short circuit at the mainboard
• Temperature sensor for the condenser defective
• Mainboard defective

E5

ON/OFF 
button (32) lights 
up briefly five 
times in a 
3-second cycle

Overvoltage protection

• The power supply is unstable and deviates from 

the values on the nameplate by more than 10 %

Connect the device to a power supply 
conforming to the data on the nameplate.

• Power supply is too low or load is too high

Disconnect unnecessary loads in the same 
grid from the power supply.

• Voltage at the mainboard is higher than the 

overvoltage protection value

Contact Trotec

• The inside of the device is heavily contaminated  Contact Trotec

• Air inlet or air outlet is blocked

Remove any foreign objects and dirt from the 
air inlet and outlet.
Observe the minimum distances specified in 
the technical data

• The fan does not run or runs too slowly

Contact Trotec

• Compressor malfunction: Temperature at the 

housing is very high, compressor makes unusual 
noises or refrigerant leaks

Disconnect the device from the power supply 
and contact Trotec.

• The system is blocked on the inside

Contact Trotec

H8

Acoustic signal 
8x in quick 
succession

Condensate overflow 
protection

• Too much condensate has accumulated in the 

device

Discharge condensate, see chapter 
Maintenance

FO

n. a.

Refrigerant leakage protection

• The inside of the device is heavily contaminated Contact Trotec

• Air inlet or air outlet is blocked

Remove any foreign objects and dirt from the 
air inlet and outlet.
Observe the minimum distances specified in 
the technical data

• Compressor malfunction: Temperature at the 

housing is very high, compressor makes unusual 
noises

Contact Trotec

• The system is blocked on the inside

Contact Trotec

• Refrigerant leaks

Contact Trotec

Содержание 1210002004

Страница 1: ...PAC 2000 E OPERATING MANUAL LOCAL AIR CONDITIONER EN TRT BA PAC2000E TC 004 EN...

Страница 2: ...gulations and was tested at the factory for perfect functionality multiple times However if faults in the functionality occur and cannot be remedied with the measures in the Errors and faults chapter...

Страница 3: ...g the device from the mains before starting with maintenance service or repair work Intended use Only use the air conditioner PAC 2000 E for cooling ventilating and dehumidifying room air indoors whil...

Страница 4: ...1 The device was designed for universal and flexible application Due to its compact dimensions it can be easily transported and used in all interior spaces The air conditioner cools the room air by wi...

Страница 5: ...ositioning the device observe the minimum distances from walls and other objects stated on the product data sheet Set the device up in a level upright and stable position Do not create tripping hazard...

Страница 6: ...ose see fig B 3 Attach the sealed condensation hose to the condensate outlet see fig C 4 Affix the condensation hose by means of the hose clip and snap it into the retaining clip see fig C Discharging...

Страница 7: ...utton 23 until the DEHUMDIFICATION mode indication 18 lights up VENTILATION mode FAN The device circulates the room air but there is no cooling A target temperature cannot be set the plus 21 and minus...

Страница 8: ...various values and settings of the device 25 MODE button Setting the operating mode COOLING COOL DEHUMIDIFICATION DRY VENTILATION FAN 26 Plus button Increases the target temperature value in COOLING...

Страница 9: ...k the proper fit of the exhaust air hose In case of kinks bends or blockage in the hose exhaust air cannot be discharged Clear the way for the exhaust air Check the air filter for dirt If required cle...

Страница 10: ...supply is unstable and deviates from the values on the nameplate by more than 10 Connect the device to a power supply conforming to the data on the nameplate Power supply is too low or load is too hig...

Страница 11: ...tec Pump does not operate or condensate cannot be discharged Contact Trotec The rubber stopper at the condensate outlet is not properly attached Check the rubber stopper for tight fit Refrigerant leak...

Страница 12: ...oling and air conditioning or by Trotec Condensate discharge In COOLING and DEHUMIDIFICATION mode condensate is formed which is mostly discharged via the exhaust air Remaining condensate accumulates a...

Страница 13: ...by a reduced cooling capacity see chapter Errors and faults Caution Ensure that the air filter is not worn or damaged The corners and edges of the air filter must not be deformed or rounded Before re...

Страница 14: ...ng manual Local air conditioner PAC 2000 E EN Exploded assembly drawing Note The position numbers of the spare parts differ from those describing the positions of other parts mentioned in this operati...

Страница 15: ...urther information is provided on the nameplate Dispose of the refrigerant appropriately and according to the national regulations Pos no Spare part Pos no Spare part Pos no Spare part 1 Front Panel A...

Страница 16: ...uch pro Stunde Electricity Consumption QSD kWh 60 min 0 8 Nennleistung im K hlbetrieb Nom Power Prated kW 2 1 Nenn Leistungsaufnahme im K hlbetrieb Nom Power Consumption PEER kW 0 95 Leistungsaufnahme...

Страница 17: ......

Страница 18: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Отзывы: