Air XD User Manual
www.trolex.com
P5628.1600 Rev A 56
Holding Register
(Function code 3
read
– Function code 6
write
)
This is a read/write register containing the instrument settings and parameters, including instrument
date, time, PM assignment and MODBUS settings. Writing to this register will result in the setting
being changed permanently.
Note:
Writing to the MODBUS settings will result in communication errors until the user has changed
their local instrument MODBUS parameters to match the new setting selected on the Air XD.
Register Description
Data Type Units
0
Time (seconds)
Uint16_t
1
Time (minutes)
Uint16_t
2
Time (hours)
Uint16_t
3
Date (date)
Uint16_t
4
Date (month)
Uint16_t
5
Date (year)
Uint16_t
6
UTC offset (minutes)
Int16_t
7
UTC offset (hours)
Int16_t
8
PM A assignment
Uint16_t
x100
9
PM B assignment
Uint16_t
x100
10
PM C assignment
Uint16_t
x100
11
PM D assignment
Uint16_t
x100
12
Alarm 1 assignment
Uint16_t
0
– PM A Live
1
– PM B Live
2
– PM C Live
3
– PM D Live
4
– TSP Live
5
– PM A Av 1
6
– PM B Av 1
7
– PM C Av 1
8
– PM D Av 1
9
– TSP Av 1
10
– PM A Av 2
11
– PM B Av 2
12
– PM C Av 2
13
– PM D Av 2
14
– TSP Av 2
13
Alarm 2 assignment
Uint16_t
0
– PM A Live
1
– PM B Live
2
– PM C Live
3
– PM D Live
4
– TSP Live
5
– PM A Av 1
6
– PM B Av 1
7
– PM C Av 1
8
– PM D Av 1
9
– TSP Av 1
10
– PM A Av 2
11
– PM B Av 2
12
– PM C Av 2
Содержание TX8005 Air XD General Purpose
Страница 2: ......
Страница 5: ...Air XD User Manual www trolex com P5628 1600 Rev A 4...