FLAMMABLE GAS SENSOR/TRANSMITTER
A T E X
M1
GROUP I & II
INTRINSICALLY
SAFE
3 DIMENSIONS
ALL DIMENSIONS IN MM
4 TECHNICAL DETAILS
4.1
Specification
Operating Temp. Limits:
–10 to +40°C
Storage Temperature:
–20 to +60°C
Ambient Pressure Limits:
1013 mbar ± 100 mbar absolute
Humidity:
95% RH non-condensing
Protection Classification:
Dust and waterproof to IP66. Gas inlet port to IP54
Housing Material:
Reinforced polymer - proof against electrostatic discharge
Nett Weight:
450 g
Cable Entries:
M20 x 1.5
Electrical Connections:
4 mm Barrier/clamp terminals
Information Display:
Graphic LCD
Impact Limits:
20 joules (Housing)
3.1 TX6383 Flammable Gas Sensor/Transmitter
3.2 TX6383.84 Flammable Gas Sensor/Transmitter
with Remote Gas Sensing Module
110
97
63
26
1
0
0
1
4
8
6
4
3
8
Ø
1
0
Ø
6
.5
Gas Entry Port
3 Cable Entries to
Suit M20 Glands or
Multi Pole Connector
2 Holes for
M6 Socket
Cap Head
Fixing Screws
External Earth Terminal
110
97
2000 (standard)
1
4
8
External Earth Terminal
2 Holes for
M6 Socket
Cap Head
Fixing Screws
2 Fixing Holes for
M6 Socket Cap
Head Screws
1
2
4
.0
1
5
.0
26.0
GAS SENSING MODULE
Plug-in gas sensing module with signal conditioning. Precalibrated and standardised output signal.
Measuring Range:
0 to 5% v/v CH
4
. Calibrated for Methane
Alternative sensing ranges available to specification
Linearity:
±1% 0 to 60% FULL SCALE
±5% from 60% up to 100% FULL SCALE
Maximum Drift @ 25°C:
±0.25% v/v per month
Response Time (T90):
<20 secs
Sensing Element Life:
>5 years in clean atmosphere
Warm Up Time:
<5 mins in air or 1% v/v CH
4
. (To 95% of stated accuracy)
Calibration:
Digitally controlled ZERO and SPAN. Pushbutton setting
Signal Fix:
The transmitted output signal of the sensor is FIXED at 00.0 during calibration
to prevent false alarms from being initiated
Overrange:
If the measured gas concentration exceeds the calibration range of the sensor:
The STATUS indicator will flash
The display value will be CLAMPED
The transmitted output signal will be CLAMPED
Pellistor Protection:
The supply to the gas sensing element will be switched off to prevent
oxidisation damage occurring if the gas concentration exceeds safe limits.
The sensor will attempt to switch back on at 5 minute intervals until the
gas concentration has reduced to a safe level