ELECTRICAL REQUIREMENTS

3

SECTION

SECTION

Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6mm²

38A

10mm²

52A

16mm²

69A

Installed in an 

insulated wall

6mm²

32A

10mm²

43A

16mm²

57A

Clipped direct

or buried in a 
non-insulated 

wall

6mm²

46A

10mm²

63A

16mm²

85A

6mm2

10mm2

16mm2

*The method below may be used by

installers to determine the approximate 

size of the incoming cable.

1.

Measure the width of an individual strand,
and half that measurment to find 

(r)

,

e.g: 

1.34mm ÷ 2 = (r) 0.67mm

2.

Multiply 

(r) x (r)

 x 

3.14,

e.g: 

(r)

 

0.67 x (r)

 

0.67 

3.14 = 1.41mm2

3.

Multiply this by the number of wire strands
(usually 7), e.g: 

1.41mm2 x 7 = 9.87mm2.

4.

The number obtained would suggest

10mm2

 wiring.

*PLEASE NOTE:

 If unsure, consult a qualified Electrician.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

 The switch must be accessible and clearly 

able, but out of reach of a person 

u

xed bath or shower, except for the 

cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily accessible 
to switch off after using the shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the disconnection 

time and thermal constraints which means 
that for any given combination of current 
demand, voltage drop and cable size, there is 
a maximum permissible circuit length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed 
in areas where the ambient temperature 
is above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

  In the majority of installations 

(see 

Table B)

, the cable will unavoidably be 

placed in one or more of the above 
conditions. This being so, it is strongly 
recommended to use a minimum of 10mm 
cabling throughout the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Содержание AMORE

Страница 1: ...user IMPORTANT SAFETY ADVICE The shower unit MUST BE switched off at the isolating switch when not in use This is a safety procedure recommended for all electrical appliances The showerhead and hose s...

Страница 2: ...ing other than those specified This appliance is intended to be permanently connected to the water mains and not connected by a hose set A suitable double pole isolation switch for supply disconnectio...

Страница 3: ...th Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806 2 2 The supply pipe must be...

Страница 4: ...r water first check that the sprayplate in the showerhead has not become blocked DO NOT place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the c...

Страница 5: ...8 ONLY Commission the shower in the way described 9 Familiarise yourself with the user operating instructions 10 1 2 3 4 5 6 7 8 9 10 Tick off as you complete PLEASE USE THE FOLLOWING CHECK LIST TO AI...

Страница 6: ...TRICAL INSTALLATION 14 FIT TO THE WALL CONNECT SHOWER SUPPLIES 14 16 FITTING THE COVER 17 COMMISSIONING PROCEDURE 18 CONNECTING THE PCB CABLE 19 USER OPERATING INSTRUCTIONS FUNCTIONS 20 22 CLEANING TH...

Страница 7: ...kPa 10 bar Maximum inlet temperature 28 C Minimum inlet temperature 5 C Inlet connection 15mm diameter Outlet connection BSP male thread MATERIALS ABS Backplate cover controls showerhead Acetal Sprayp...

Страница 8: ...Fig 1 200mm 94mm 300mm ENTRY POINTS DIMENSIONS WATER Left Top Bottom Back Right Bottom Back CABLE Left Top Bottom back Right None Back Back Others Others PLEASE NOTE Deviation from the approved entry...

Страница 9: ...ubt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main s...

Страница 10: ...ile standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets i...

Страница 11: ...to achieve your preferred shower temperature Fig 5 shows a typical system layout Refer to fig 6 for the correct siting of the shower Position the unit where it will NOT be in direct contact with water...

Страница 12: ...ocked showerhead This may cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose Failure to follow this procedure may cause the PRD to operate Make sure the...

Страница 13: ...make the nut accessible for future adjustments NOTE An additional stop valve complying with Water Regulations must be fitted in the mains water supply to the shower as an independent means of isolati...

Страница 14: ...entry has not been chosen the trim can be fitted complete Should either top cable or top pipe entry have been chosen individually the trim has been designed to be separated and the appropriate trim s...

Страница 15: ...to terminal marked L Once the cables have been installed the two trimplates will need to be fitted IMPORTANT When connecting the cable fully tighten the terminal block screws and make sure that no ca...

Страница 16: ...lectricity supply until the shower cover has been fitted 7 SECTION SECTION NOTE The elements on UK models are to 240V specification and will give a lower kW rating if the voltage supply is below 240V...

Страница 17: ...orrectly minor adjustment may be necessary to align the control and spindle Should any difficulty arise recheck the points above While applying slight pressure to the front cover secure in position wi...

Страница 18: ...this could make the PRD operate Turn on the water supply to the shower at the isolating stop valve Switch on the electricity supply to the shower at the isolating switch Wait until water starts to flo...

Страница 19: ...d edge which is uppermost when correctly fitted to the socket There is also a key way for ensuring correct location into the socket Guide the cover into position so that the knob spindle locates corre...

Страница 20: ...ouched to change the power setting After a new power selection is made the appropriate icon is illuminated and the screen will display Cold Eco or Max to confirm the selection before reverting to disp...

Страница 21: ...to compensate for seasonal changes in ambient water temperature NOTE The preferred knob position on ECO will give a different temperature to the same position on MAX To decrease the shower temperature...

Страница 22: ...When the Start Stop button is pressed to end showering all heating elements are switched off but water will continue to flow for a few seconds flushing out any remaining hot water The screen will flas...

Страница 23: ...plate Unscrew the filter cap from the bottom of the inlet pipe Inspect the O ring for damage when the filter cap is removed When cleaning the filter DO NOT use a sharp object as it will cause damage I...

Страница 24: ...ly 2 2 1 Check if stop valves are fully open Check if a blockage in the inlet filter 2 3 Increase in ambient water temperature 2 3 1 Readjust flow rate to give increased flow 2 3 2 Select economy powe...

Страница 25: ...1 Thermal safety cut out device has operated Have the unit checked by a suitably qualified engineer or contact Customer Service 4 Pressure relief device has operated water ejected from PRD tube 4 1 B...

Страница 26: ...r electric products are labelled accordingly with the crossed out wheeled bin symbol This indicates for disposal purposes at end of life that these products must be taken to recognised collection poin...

Страница 27: ...o START the shower Press the start stop switch Press Start Stop automatically defaullts to Max Power selection Press Max Power the shower will switch to the Max Power setting Press Economy Power the s...

Страница 28: ...credit debit card excluding American Express or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given dur...

Отзывы: