Installing the ROV Sidescan
SeaKing Sidecan Sonars
0374-SOM-00013, Issue: 01
18
© Tritech International Ltd.
If using a rectified transformer PSU the output must have a filter capacitor of at least
470μF for each head that is being powered. The use of unregulated power supplies
is not recommended.
If powering the head down a long lead or umbilical, the maximum recommended
loop resistance of the power line must not exceed 10Ω for a single device. If other
SeaKing devices are connected via the
AUX
port in a network then the loop resistance
should be 5Ω for two devices and 3Ω for three devices.
If the supply voltage is less than the minimum specified in Chapter 2,
SeaKing ROV
Sidescan
the Sidescan is unlikely to work correctly.
Ground Fault Monitoring Equipment
The power supply within all SeaKing devices includes an electrically
isolated DC to DC converter front end with a small capacitive connection
made to the sonar chassis. This should not noticeably affect any impressed
current Ground Fault Interrupter (GFI) or Residual Current Devices
(RCD).
Содержание ROV Sidescan
Страница 1: ...SeaKing Sidecan Sonars Towfish SK150 and ROV Sidescan 0374 SOM 00013 Issue 01 ...
Страница 8: ...SeaKing Sidecan Sonars 0374 SOM 00013 Issue 01 8 Tritech International Ltd Part I Specification ...
Страница 15: ...SeaKing Sidecan Sonars 0374 SOM 00013 Issue 01 15 Tritech International Ltd Part II Installation ...
Страница 23: ...SeaKing Sidecan Sonars 0374 SOM 00013 Issue 01 23 Tritech International Ltd Part III Seanet Pro Software Suite ...
Страница 39: ...SeaKing Sidecan Sonars 0374 SOM 00013 Issue 01 39 Tritech International Ltd Part IV Image Tiler Software ...
Страница 68: ...SeaKing Sidecan Sonars 0374 SOM 00013 Issue 01 68 Tritech International Ltd Part V Service and Maintenance ...