 Installation

2 - Dynamic IP Address Assignment

2-1

  Connect Accessory to Power: 

(Refer to Figure 1, Figure 2a or Figure 2b on 

page 5 and 6.) There are two ways to connect the Accessory to power:
•  Connect the AC Adapter

 

A

 to the Accessory via the port labeled “DC Power” 

 

B

 and plug the other end into an AC power source supported by a UPS 

(Figure 1) or Inverter/Charger (Figure 2a). 

•  Connect one end of the 12V DC Cable

 

A

 to the Accessory via the port 

labeled “DC Power”

 

B

 and connect the other end

 

I

 directly to the Inverter/

Charger

 

J

. This feature is available on select models only.

Note: The Accessory must be plugged into a power source protected by a UPS or 

Inverter/Charger in order to maintain communications during a power outage.

2-2

  Connect Accessory to Device: 

(Refer to Figure 1, Figure 2a or Figure 2b on 

page 5 and 6.) Using the standard serial cable provided, connect one end to the 
Accessory port labeled “UPS/APS”

 

C

 and the other end to the DB9 serial port 

on your UPS or Inverter/Charger

 

D

2-3

  Connect Accessory to Network: 

Connect a standard Ethernet patch cable to 

the RJ45 Ethernet port on the Accessory. 

Note: This port does not support PoE 

(Power over Ethernet) applications. 

The Accessory will attempt to obtain an IP 

address via DHCP. This may take as long as several minutes, depending on your 

network environment.

2-4

  Discover IP Address: 

Contact your network administrator to determine which IP 

address has been assigned to the Accessory by the DHCP server. The card can 
be identified on the DHCP server by referring to its MAC address (see Step

 

1-3

). 

You may wish to request a long-term lease period for the IP address, depending 

on your application. After you have discovered the IP address, proceed to  

4 - Test and Configure

Note: The DHCP address is also displayed during boot-

up when connected to a computer through the configuration cable and a 
terminal emulation program.

201110124-93-3108.indb   3

11/3/2011   11:59:50 AM

Содержание SNMPWEBSOLO

Страница 1: ...is included on the CD ROM bundled with the accessory Refer to the User s Guide for additional information about configuration and operation Installation 2 Features 11 Tech Support 12 Warranty 13 Русский 15 W A R R A N T Y R E G I S T R A T I O N R e g i s t e r o n l i n e t o d a y f o r a c h a n c e t o w i n a F R E E T r i p p L i t e p r o d u c t w w w t r i p p l i t e c o m w a r r a n t ...

Страница 2: ... F CEE 7 7 plug adapter 12V DC cable Comes with SNMPWEBSOLO only Comes with SNMPWEBSOLOHV only 1 2 Install UPS or Inverter Charger Install your UPS or Inverter Charger and turn it on before installing the Accessory 1 3 Locate MAC Address The 12 digit MAC address 000667xxxxxx is attached to the underside of the Accessory 1 4 Determine Network Installation Method If your network s DHCP server will a...

Страница 3: ...nect one end to the Accessory port labeled UPS APS C and the other end to the DB9 serial port on your UPS or Inverter Charger D 2 3 Connect Accessory to Network Connect a standard Ethernet patch cable to the RJ45 Ethernet port on the Accessory Note This port does not support PoE Power over Ethernet applications The Accessory will attempt to obtain an IP address via DHCP This may take as long as se...

Страница 4: ... such as the HyperTerminal program bundled with Microsoft Windows on a computer with an available DB9 serial port A notebook computer may be the most convenient choice Set the terminal emulation program to use the COM port A that corresponds to the DB9 serial port Specify the parameters B required to communicate with the Accessory terminal interface If the terminal emulation program supports multi...

Страница 5: ...one end of the cable attaches to the 8 pin mini DIN serial port labeled CONFIG F on the Accessory Align the connector carefully to avoid damaging the pins The DB9 connector G at the other end of the cable connects to the computer s serial port H INVERTER CHARGER INVERTER CHARGER AC POWER SOURCE D A A C E G H H F F Figure 1 Figure 2A B C D B E G 201110124 93 3108 indb 5 11 3 2011 11 59 51 AM ...

Страница 6: ...igure 2a Connect one end of the 12V DC Cable A to the Accessory via the port labeled DC Power B and connect the other end I directly to the Inverter Charger J This feature is available on select models only Note The Accessory must be plugged into a power source protected by a UPS or Inverter Charger in order to maintain communications during a power outage 3 6 Connect Accessory to Device Refer to ...

Страница 7: ... to the Accessory The default terminal mode password is TrippLite Sample IP settings are shown supply your own IP information when you configure your Accessory This card s hostname This card s domain Obtain IP settings automatically using DHCP for Ethernet interface Y IP address 10 2 0 98 Subnet mask 255 0 0 0 Gateway address 10 0 0 1 DNS server 1 10 0 0 5 DNS server 2 10 2 0 10 This cards host na...

Страница 8: ...frica 2 Atlantic Ocean 3 Moscow Mid East E Africa 3 Greenland Time 4 NW Caspian Sea 4 Atlantic Time 5 Ural Mountains Russia 5 Eastern Standard Time 6 Almaty Alma ATA Russia 6 Central Standard Time 7 W Mongolia 7 Mountain Standard Time 8 China 8 Pacific Standard Time 9 Japan 9 Alaska Time 10 Eastern Russia Sydney Australia 10 Hawaii 11 Kamchatskiy E Russia 11 Pacific Ocean 12 International Date Lin...

Страница 9: ...new static IP settings 3 8 Remove Configuration Cable Remove the configuration cable that connects the Accessory to the computer 4 Test and Configure 4 1 Test Network Connection After an IP address has been assigned to the Accessory try to access it with a Web browser that supports frames forms and Java Open a Web browser on a computer connected to the LAN and enter the Accessory s IP address You ...

Страница 10: ... appears at the left side of the screen 2 From the Event Settings page confirm that the Low Battery Shutdown C box is checked and then click the Details Tab D or double click the checked box to access the Setting Details page 3 From the Details page E choose your preferred settings from the Settings drop down menu F and click the Save Changes button G Note for Network Management System Users Only ...

Страница 11: ...he Accessory to the network with a standard Ethernet patch cable The Link LED C1 and Status LED C2 indicate several operating conditions as shown in the table below Does not support PoE Power Over Ethernet applications Accessory Operating Conditions C1 Link LED Color Off No Network Connection Flashing Amber 100 Mbps Network Connection Flashing Green 10 Mbps Network Connection C2 Status LED Color O...

Страница 12: ...y and the UPS or Inverter Charger AC Power Adapter 120V AC Adapter or 230V AC Adapter Used to provide power to the SNMP WEB Management Accessory Note Plug into an AC power source supported by a UPS or Inverter Charger in order to maintain communications during a power outage Plug Adapter SNMPWEBSOLOHV Model Only For use with the 230V AC Adapter in network environments that are not compatible with ...

Страница 13: ...bject to great variation the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application Not compatible with PoE Power over Ethernet applications WARRANTY REGISTRATION Visit www tripplite com warranty today to register the warranty for your new Tripp Lite product You ll be automatically entered into a drawing for a chance to win a...

Страница 14: ...14 201110124 933108 EN 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 201110124 93 3108 indb 14 11 3 2011 11 59 53 AM ...

Страница 15: ...новки внимательно прочтите данное руководство На компак тдиске поставляемом в комплекте с картой принадлежностей имеется отдельное руководство пользователя в формате PDF В этом руководстве приведена допол нительная информация о конфигурировании карты и работе с ней Установка 16 Разъемы 25 Техническая поддержка 26 Гарантийные обязательства 27 English 1 201110124 93 3108 indb 15 11 3 2011 11 59 53 A...

Страница 16: ...пряжением 120 В или 230 В Вилка переходник с Euro Universal на Hybrid E F CEE 7 7 Кабель питания 12 В Поставляется только с моделью SNMPWEBSOLO Поставляется только с моделью SNMPWEBSOLOHV 1 2 Установка ИБП или инвертора зарядного устройства перед установкой дополнительной платы установите ИБП или инвертор зарядное устройство и включите его 1 3 Определить MAC адрес Наклейка с 12 разрядным MAC адрес...

Страница 17: ...плект стандартного последовательного кабеля к Сетевой карте через вход с маркировкой UPS APS C а другой его конец к последовательному порту DB9 своего ИБП или Преобразователя Зарядного устройства D 2 3 Подключите Сетевую карту к сети Подключите стандартный соединительный кабель Ethernet к Сетевой карте через гнездо RJ45 Ethernet Примечание Питание по кабелю витой пары PoE через данное гнездо не пр...

Страница 18: ...му эмуляции терминала совместимую с VT100 например HyperTerminal которая поставляется с Microsoft Windows Более подходящим может оказаться ноутбук В программе эмуляции терминала задать использование COM порта A который соответствует последователь ному порту с разъемом DB9 Указать параметры A необходимые для связи с терминальным интерфейсом карты Карта управления Если программа эмуляции терминала п...

Страница 19: ...NFIG F карты управления Нужно проследить за правильной ориентацией разъема во избежание повреждения контактов Разъем DB9 G на другом конце кабеля подключается к последовательному порту компьютера H ИБП ВЫПРЯМИТЕЛЬ ВСПОМОГАТЕЛЬНАЯ ПЛАТА КОМПЬЮТЕР С ПОСЛЕДОВАТЕЛЬНЫМ ПОРТОМ DB9 ВЫПРЯМИТЕЛЬ ИНВЕРТОР ЗАРЯДНОЕ УСТРОЙСТВО ИНВЕРТОР ЗАРЯДНОЕ УСТРОЙСТВО ИСТОЧНИК ПИТАНИЯ ПЕРЕМЕННОГО ТОКА ВСПОМОГАТЕЛЬНАЯ ПЛАТ...

Страница 20: ... к Сетевой карте через вход с маркировкой DC Power B а другой его конец I напрямую к Преобразователю Зарядному устройству J Такая возможность предусмотрена только для определенных моделей Примечание Для поддержания связи в случае прекращения подачи электроэнергии Сетевая карта должна подключаться к источнику питания защищенному ИБП или Преобразователем Зарядным устройством 3 6 Подключите Сетевую к...

Страница 21: ...в терминальном режиме используется пароль TrippLite Ниже показан пример настроек IP адреса при конфигурировании своей карты пользователь должен предоставить собственную информацию об IP This card s hostname This card s domain Obtain IP settings automatically using DHCP for Ethernet interface Y IP address 10 2 0 98 Subnet mask 255 0 0 0 Gateway address 10 0 0 1 DNS server 1 10 0 0 5 DNS server 2 10...

Страница 22: ...вропа Африка 1 Юго восток Гренландии 2 Восточная Европа восточная часть Центральной Африки 2 Атлантический океан 3 Москва Ближний Восток Восточная Африка 3 Гренландия 4 Северо западная часть Каспийского моря 4 Атлантическое побережье США 5 Уральские горы Россия 5 Восточное поясное время 6 Алматы Алма Ата Россия 6 Центральное поясное время 7 Западная Монголия 7 Западная часть США горное время 8 Кит...

Страница 23: ...грузится на странице инициализации будут отображаться новые настройки статического IP адреса 3 8 Отключение конфигурационного кабеля Отключите конфигурационный кабель соединяющий Дополнительную плату с компьютером 4 Проверка и конфигурирование 4 1 Проверка сетевого подключения После назначения карте IP адреса попытайтесь получить доступ к ней с помощью веб браузера который поддерживает фреймы форм...

Страница 24: ...рана 2 На экране Event Settings настройки событий установить флажки C Low Battery низкий уровень заряда батареи и Shutdown отключение затем перейти на вкладку D Details подробные сведения или дважды щелкнуть на флажке для перехода на страницу Setting Details подробные сведения о настройках 3 На странице E Details подробные сведения выбрать предпочтительные настрой ки из выпадающего меню F и нажать...

Страница 25: ... поставляется в комплекте с Дополнительной платой Если нужно заказать кабель для замены обратитесь в службу по работе с клиентами компании Tripp Lite Порт Ethernet Этот разъем RJ45 используется для подключения карты аксессуар к сети с помощью стандартного соединительного кабеля Ethernet Светодиоды Link C1 и Status C2 указывают на различные режимы работы описанные в приведенной ниже таблице Не подд...

Страница 26: ...тву с использованием входящего в комплект последовательного кабеля для обеспечения связи между дополнительной платой и ИБП или инвертором зарядным устройством Блок питания переменного тока Блок питания от сети переменного тока напряжением 120 В или 230 В Используется для подачи электропитания на Устройство обеспечения связи через SNMP WEB протокол Примечание Для поддержания связи в случае прекраще...

Страница 27: ...торые штаты не разрешают исключение или ограничение случайных или побочных повреждений поэтому указанные выше ограничения могут не применяться к вашему случаю Эта Гарантия дает вам конкретные законные права и вы можете иметь другие права которые меняются в зависимости от юрисдикции ПРЕДУПРЕЖДЕНИЕ Каждый пользователь должен позаботиться о том чтобы до начала использования определить пригодность дос...

Страница 28: ...28 201110124 933108 RU 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 201110124 93 3108 indb 28 11 3 2011 11 59 55 AM ...

Отзывы: