background image

VOLTAGE REGULATION

Voltage regulation
description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151 to 290V

Overvoltage correction

Voltage reduction of 12% applies when input is 232-266 (220V), 244-278 (230V), 254-290 (240V)

Undervoltage correction

Voltage boost of 15% applies when input is 175-198 (220V), 182-206 (230V), 190-216 (240V)

Severe undervoltage
correction

Voltage boost of 30% applies when input is 151-174 (220V), 158-181 (230V), 166-190 (240V)

LEDS ALARMS & SWITCHES

LED Indicators

9 LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter
for load and battery charge level

Alarms

Audible alarm indicates power failure and overload conditions

Alarm cancel operation

Power-fail alarm can be silenced using alarm-cancel switch

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches
support nominal voltage selection

SURGE / NOISE SUPPRESSION

UPS AC suppression
joule rating

504

UPS AC suppression
response time

Instantaneous

UPS Dataline suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form factors
supported with included
accessories

Tower

Primary form factor

Tower

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)

10.25 x 6.75 x 13.25

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)

26 x 17.1 x 33.7

UPS / Power Module
weight (lbs)

34.1

UPS / Power Module
weight (kg)

15.5

UPS Shipping dimensions
(height x width x depth /
inches)

14 x 9.75 x 18.5

UPS Shipping dimensions
(height x width x depth /
cm)

35.6 x 24.8 x 47

Shipping weight (lbs)

38.6

Shipping weight (kg)

17.5

Содержание SmartPro SLT SMX750SLT

Страница 1: ...dible alarm and 9 LEDs offer status notification for line power battery power battery charge level load level plus AVR boost and trim operational status information Network grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges Attractive all black tower housing Package Includes SMX750SLT UPS System PowerAlert Software CD ROM USB and seri...

Страница 2: ...t AC waveform battery mode Pure Sine wave INPUT Rated input current at maximum load 3 6A 220V 3 5A 230V 3 4A 240V Nominal Input Voltage s Supported 220V AC 230V AC 240V AC UPS input connection type C14 inlet UPS input connection description IEC320 C14 input connection accepts a variety of detachable cordsets to match country or site specific wall receptacles BATTERY Full load runtime minutes 5 min...

Страница 3: ... alarm can be silenced using alarm cancel switch Switches 2 Switches control off on power status and alarm cancel self test operation rear panel protected switches support nominal voltage selection SURGE NOISE SUPPRESSION UPS AC suppression joule rating 504 UPS AC suppression response time Instantaneous UPS Dataline suppression 1 line TEL DSL 1 in 1 out 10 100Base T Ethernet EMI RFI AC noise suppr...

Страница 4: ...g compatibility Supports Watchdog application OS and hard reboot restart options for remote applications LINE BATTERY TRANSFER Transfer time 4 8 milliseconds Low voltage transfer to battery power setpoint 151 220V 158 230V 166 240V High voltage transfer to battery power setpoint 266V 220V 278V 230V or 290V 240V SPECIAL FEATURES Cold Start startup in battery mode during a power failure Cold start o...

Страница 5: ...nd control via SNMP Web or Telnet 1 U022 010 10 ft USB2 0 A B Gold Device Cable A Male to B Male 1 WATCHDOGSW WatchDog Service Monitoring Reboot Software 1 MODBUSCARD For remote monitoring and control via MODBUS protocol 1 More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModelID 302...

Отзывы: