VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151 to 290V
Overvoltage correction
Voltage reduction of 12% applies when input is 232-266 (220V), 244-278 (230V), 254-290 (240V)
Undervoltage correction
Voltage boost of 15% applies when input is 175-198 (220V), 182-206 (230V), 190-216 (240V)
Severe undervoltage
correction
Voltage boost of 30% applies when input is 151-174 (220V), 158-181 (230V), 166-190 (240V)
LEDS ALARMS & SWITCHES
LED Indicators
9 LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter
for load and battery charge level
Alarms
Audible alarm indicates power failure and overload conditions
Alarm cancel operation
Power-fail alarm can be silenced using alarm-cancel switch
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches
support nominal voltage selection
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
504
UPS AC suppression
response time
Instantaneous
UPS Dataline suppression
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Installation form factors
supported with included
accessories
Tower
Primary form factor
Tower
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)
10.25 x 6.75 x 13.25
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)
26 x 17.1 x 33.7
UPS / Power Module
weight (lbs)
34.1
UPS / Power Module
weight (kg)
15.5
UPS Shipping dimensions
(height x width x depth /
inches)
14 x 9.75 x 18.5
UPS Shipping dimensions
(height x width x depth /
cm)
35.6 x 24.8 x 47
Shipping weight (lbs)
38.6
Shipping weight (kg)
17.5