background image

Installed whole
system total rack
space height (rack
spaces)

6U

Secondary form
factor

Tower

UPS / Power Module
weight (lbs)

43

UPS / Power Module
weight (kg)

19.5

Included battery
pack dimensions
(height x width x
depth / inches)

5.25 x 17.5 x 25

Included battery
pack dimensions
(height x width x
depth / cm)

13.3 x 44.4 x 63.5

Included battery
pack weight (lbs)

158.7

Included battery
pack weight (kg)

72

UPS Shipping
dimensions (height
x width x depth /
inches)

39.8 x 31.5 x 23

UPS Shipping
dimensions (height
x width x depth / cm)

101 x 80 x 58.4

Shipping weight (lbs)

331

Shipping weight (kg)

150.3

UPS housing
material

Steel

Cooling method

Fan

ENVIRONMENTAL

Operating
Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage
Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr.
(full load)

2732

AC economy mode
BTU / hr. (full load)

1020

AC economy mode
efficiency rating
(100% load)

96%

Operating Elevation
(ft)

0-3000m (0 to 10,000 ft.)

Audible Noise

60 dBA at front side 1 meter

Содержание SmartOnline SU8000RT3UN50

Страница 1: ...Package Includes SU8000RT3UPM 3U UPS power module BP240V10RT3U external battery pack SUPDMB710 Detachable PDU with manual bypass switch Four post compatible rack rail kit 2 sets Tower stands for upri...

Страница 2: ...luded rail kit supports 6U 19 inch rackmount installation in 4 post racks Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks Optional 2 9USTAND supports upright tower placement Front...

Страница 3: ...ection description 3 wire single phase input L1 L2 G UPS Input cord length ft 10 UPS Input cord length m 3 Recommended Electrical Service 208 240V 50A BATTERY Full load runtime minutes 5 5 min 7200w H...

Страница 4: ...s support set and execute scrolling LCD functions bundled PDU includes bypass switch to enable hot swap UPS power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time Instantane...

Страница 5: ...width x depth inches 39 8 x 31 5 x 23 UPS Shipping dimensions height x width x depth cm 101 x 80 x 58 4 Shipping weight lbs 331 Shipping weight kg 150 3 UPS housing material Steel Cooling method Fan...

Страница 6: ...FEATURES Cold Start startup in battery mode during a power failure Cold start operation supported Economy mode operation Optional economy mode enables high efficiency bypass operation with a maximum...

Страница 7: ...Metered 0U Vertical Rack PDU Metered Power Distribution Unit for Network Applications 1 Power Distribution PDUMV20HVNET Switched Metered PDU with Remote Monitoring 0U Vertical Rackmount Power Distribu...

Отзывы: