background image

Output voltage
regulation (Economy
line mode)

+/- 10%

Output voltage
regulation (Battery
mode)

+/- 2%

Built-in UPS output
receptacles

4 L6-20R outlet(s); 2 L6-30R outlet(s)

Output circuit
breaker

20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlets each

Output AC waveform
(AC mode)

Pure Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current
(at maximum load)

44.2A (208V), 38.3A (240V)

Nominal Input
Voltage(s) Supported

208V AC; 240V AC

UPS input
connection type

Hubbell CS8265; Hardwire

UPS input
connection
description

3 wire single phase input (L1, L2, G)

UPS Input cord
length (ft.)

10

UPS Input cord
length (m)

3

Recommended
Electrical Service

208/240V 50A

BATTERY

Full load runtime
(minutes)

5.5 min. (7200w)

Half load runtime
(minutes)

13.5 min. (3600w)

Expandable battery
runtime

Supports extended runtime with optional external battery packs

External battery
pack compatibility

BP240V10RT3U

BP240V557C-1PH

BP240V787C-1PH

BP240V1037C-1PH

BP240V1407C-1PH

DC system voltage
(VDC)

240

Battery recharge
rate (included
batteries)

Less than 6 hours from 10% to 90%

Battery replacement
description

Hot-swappable, user replaceable external battery packs

VOLTAGE REGULATION

Voltage regulation
description

2% output voltage regulation in standard online, double-conversion mode

Содержание SmartOnline SU8000RT3UN50

Страница 1: ...Package Includes SU8000RT3UPM 3U UPS power module BP240V10RT3U external battery pack SUPDMB710 Detachable PDU with manual bypass switch Four post compatible rack rail kit 2 sets Tower stands for upri...

Страница 2: ...luded rail kit supports 6U 19 inch rackmount installation in 4 post racks Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks Optional 2 9USTAND supports upright tower placement Front...

Страница 3: ...ection description 3 wire single phase input L1 L2 G UPS Input cord length ft 10 UPS Input cord length m 3 Recommended Electrical Service 208 240V 50A BATTERY Full load runtime minutes 5 5 min 7200w H...

Страница 4: ...s support set and execute scrolling LCD functions bundled PDU includes bypass switch to enable hot swap UPS power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time Instantane...

Страница 5: ...width x depth inches 39 8 x 31 5 x 23 UPS Shipping dimensions height x width x depth cm 101 x 80 x 58 4 Shipping weight lbs 331 Shipping weight kg 150 3 UPS housing material Steel Cooling method Fan...

Страница 6: ...FEATURES Cold Start startup in battery mode during a power failure Cold start operation supported Economy mode operation Optional economy mode enables high efficiency bypass operation with a maximum...

Страница 7: ...Metered 0U Vertical Rack PDU Metered Power Distribution Unit for Network Applications 1 Power Distribution PDUMV20HVNET Switched Metered PDU with Remote Monitoring 0U Vertical Rackmount Power Distribu...

Отзывы: