Connection

attach the PDU to the Power Module and Battery Pack.

Align and connect the PDU's power module terminal block with the input/output terminal 
block 

a

 

on the back of the power module. Secure the PDU to the power module with four 

screws. Before proceeding, ensure that the bypass switch is set to NORMAL. Remove the 
utility input terminal block cover

 

B

Hardwire the PDU to a Utility Power source.

Pass user-supplied cabling through the knockouts on the top of the PDU

 

C

 and connect 

it to the PDU's input terminals

 

D

. Replace the terminal block cover. Connect the other 

end of the cabling to a dedicated utility power circuit of sufficient amperage.

Connect the Battery Pack to the Power Module.

Consult  the  owner’s  manual  that  came  with  the  battery  pack.  Remove  the  retention 
brackets

 

e

 from the power module's battery connector

 

F

 and one of the battery pack's 

rear panel connectors

 

g

. Attach one end of the detachable battery power cable

 

H

 to each 

connector.  (Small  sparks  may  occur;  this  is  normal.)  Reattach  the  retention  brackets  
immediately to the right of each connector, using the additional screw holes

 

i

 provided to 

the right of the original bracket position. The brackets will secure the battery power cable 
connection. 

Warning:  Always  use  the  connector  retention  brackets  to  secure  the 

battery  pack  connection.  Do  not  attempt  to  operate  the  UPS  system  without  the 
connector  retention  brackets  in  place. 

NOTE:  the  power  module  does  not  contain 

internal batteries and will not start until a battery pack is connected. Allow the battery to 
charge for at least 12 hours to ensure full battery backup for connected equipment. If you 
require  increased  battery  backup  runtime,  an  unlimited  number  of  additional  external 
battery packs may be daisy-chained to the primary battery pack. Adding additional external 
battery  packs  will  increase  runtime  battery  backup  runtime,  but  it  will  also  increase 
recharge time.

turn the UPs On.

Press the “ON” Button

 

J

 until you hear a beep to begin inverter operation. The UPS will 

now provide output power through its AC outlets to connected equipment. The UPS will 
perform a brief self-test and show the results on the LCD Display

 

K

. See “Startup Self-

Test” in the “Operation” section for the display sequence.

Cold  Start:  To  use  the  UPS  as  a  stand-alone  power  source  when AC  input  power  is  unavailable  (i.e.  during  a 
blackout), you can cold start the UPS and power connected equipment from the battery. The battery must be at least 
partially charged for this operation to succeed. Press and hold the “ON” Button until you hear a beep to cold start 
the  UPS.  The  LCD  Display  will  show  “ON  BATTERY  MODE”.  Battery  power  will  begin  discharging.  Some 
electronic equipment may draw more amps during startup; when cold starting, consider reducing the initial load on 
the UPS.

1

2

J

K

4

note: the output voltage is set at 208/120V~ when the UPs is shipped from the factory. if you need to change  

the output voltage of the UPs, refer to “Output Voltage selection” in the “Operation” section. you should select  

the correct output voltage before connecting equipment to the UPs.

1

2

Hardwiring Cautions 

•   Wiring must be installed by a qualified electrician.
•  When making wiring connections, observe the regulations appropriate to your region [National Electrical Code (NEC) in the U.S.] at all 

times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS AC input during fires 
and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a 
torque of not less than 24-28 inch-pounds (2.7-3.2 newton-meters). Make sure that your equipment is properly grounded.

•   Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to 

make wiring connections. Ground conductors must be the same size and type as the power conductors used.

•  Refer to National Electrical Code (NEC) guidelines for proper wire gauge and output protection circuit requirements.

a

3

Contacts on Power Module and PDU

Warning! High Voltage! risk of electrical shock!

Do not let these contacts touch any surface!

see "Manual Bypass Procedure" section for more information.

4

3

B

C

D

F

e

g

H

i

input and Output ratings

 

Input 

Maximum Rated  Maximum Rated   Typical 

Model 

Voltage 

Input Current  Output Current  Wire Size

SU16000RT4U 

100-140V (L1-N: L2-N) 

68A 

70A 

4 AWG

SU16000RT4UHW  100-140V (L1-N: L2-N) 

68A 

70A 

4 AWG

To Turn the UPS System OFF: 

Press the UPS's “OFF” Button until you hear a beep. The LCD Display will show “BYPASS MODE.” 

The UPS will continue to charge its batteries as long as AC input power is present. To completely deactivate the UPS, disconnect the UPS 
from AC input power when the UPS system is in bypass mode.

Содержание SmartOnline SU16000RT4U

Страница 1: ...and SU16000RT4UHW Important Safety Warnings 2 Features 3 Mounting 7 Connection 8 Optional Connection 9 Manual Bypass Procedure 15 Operation 10 Storage Service 17 Warranty Warranty Registration 17 111...

Страница 2: ...ergy source battery The output terminals may be live even when the UPS is not connected to an AC power source Do not connect surge suppressors or extension cords to the output of the UPS This might ov...

Страница 3: ...and hold it until you hear a beep The UPS will display the following message Switch to Bypass N ON Y OFF if it is safe to do so Pressing OFF again will put the UPS in Bypass still providing power to...

Страница 4: ...stem s battery charge rate The switch is set to the left the position labeled NORMAL by default If you connect more than one external battery pack to the UPS system set the Battery Charge Level Switch...

Страница 5: ...ss the terminals unscrew and remove the terminal block cover Diagram shows cover removed The UPS must be connected to a dedicated circuit of sufficient amperage split phase rated in accordance with th...

Страница 6: ...t connect or disconnect battery packs while the UPS is running on battery power the BATTERY LED will be lit on the control panel Warning Always use the connector retention brackets to secure the batte...

Страница 7: ...rack and rack enclosure types and may not be appropriate for all applications WARNING The UPS system is extremely heavy Use caution when lifting and mounting User must properly stabilize the UPS when...

Страница 8: ...lone power source when AC input power is unavailable i e during a blackout you can cold start the UPS and power connected equipment from the battery The battery must be at least partially charged for...

Страница 9: ...rd to the second and so on Note When daisy chaining multiple battery packs they should be identical models of similar age and level of wear Make sure that cables are inserted fully into connectors Sma...

Страница 10: ...AC Input DIAGNOSTIC MODE INPUT AC OK DIAGNOSTIC MODE INPUT AC BAD DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE AC DC OK DIAGNOSTIC MODE AC DC OK DI...

Страница 11: ...wn if AC power is interrupted If solid the UPS is in Economy Mode ECO See page 12 for details The second line of the LCD Display shows basic power conditions Push the SCROLL buttons to browse through...

Страница 12: ...h the SET UP screen 1 and press the SCROLL DOWN button again to exit the SET UP procedure The LCD should be back to ON BATTERY MODE Press the OFF key until you hear a beep and the UPS will save the se...

Страница 13: ...on on its LCD and stops supplying output power to its load Bypass Voltage Conditions L1 15 Higher Than Nominal Voltage L2 15 Higher Than Nominal Voltage L1 20 Lower Than Nominal Voltage L2 20 Lower Th...

Страница 14: ...VERLOAD XXX OP S HORTCIRCUIT LOAD1 XX X X XKW OP1 SHORTCIRCUIT LOAD1 XX X X XKW OP2 SHORTCIRCUIT LOAD1 XX X X XKW REMOTE C OMMAND LOAD1 XX X X XKW EMERGENCY STO P LOAD1 XX X X XKW SITE WIR ING F AULT...

Страница 15: ...re and disconnect all communication cable s from the communication port s A on the UPS power module STEP 3 Press the UPS s OFF Button B if the UPS is powered until you hear a beep and see a Switch to...

Страница 16: ...ts are live Do not let these contacts touch any surface A Contacts on Detachable PDU WARNING High voltage Risk of electrical shock If AC is present and Bypass Switch is set to Bypass these contacts ar...

Страница 17: ...pproved by the party responsible for compliance could void the user s authority to operate the equipment Made in China Regulatory Compliance Identification Numbers For the purpose of regulatory compli...

Отзывы: