Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite
Customer Service at +1 773 869 1234 before returning your unit for service.

Troubleshooting

SYMPTOM

PROBLEMS

CORRECTIONS

No AC Output

Unit is not properly connected 

Connect unit to utility power.

(All Indicator Lights Are Off)

to utility power.

Circuit breaker is tripped.

Reset circuit breaker.

Battery Not Recharging

Connected batteries are dead.

Check and replace old batteries.

(AC Input Present)

Battery fuse* is blown.

Check and replace fuse.*

Battery cabling* is loose.

Check and tighten or replace cabling.*

Unit has shut down due to battery Disconnect any auxiliary chargers.
overcharge (preventing battery 

Reset by moving Operating Mode

damage). The problem may be 

Switch to “DC OFF.” Wait 1 minute 

with connected auxiliary chargers, and switch to “AUTO” or “CHARGE 
if any, or with the unit’s charger.

ONLY.” If unit remains in shutdown 
mode after several attempts to reset,
contact Tripp Lite Customer Service 
for assistance.

All Three Battery Indicator 

Battery is overcharged. Unit will 

Disconnect any auxiliary chargers.

Lights Are Flashing

shut down to prevent battery 

Reset by moving Operating Mode 

(¼ Second Flashes)

damage. The problem may be 

Switch to “DC OFF.” Wait 1 minute 

with connected auxiliary chargers, and switch to “AUTO” or “CHARGE 
if any, or with the unit’s charger.

ONLY.” If unit remains in shutdown 
mode after several attempts to reset, 
contact Tripp Lite Customer Service 
for assistance.

Red “LOW” Battery

Battery voltage is low. Unit will 

Make sure that AC power is present 

Indicator Light is Flashing

automatically shut down after 10  in order to recharge batteries.
seconds to protect battery from 

Operating Mode Switch must be set  

damage.

to “AUTO” or “CHARGE ONLY.”

False reading due to undersized   Use sufficient size DC cable 
or insufficiently connected

sufficiently connected to the

DC cabling.

Inverter/Charger.

Red “LOAD” Operation

Inverter is overloaded. Unit will  

Reduce load. Operating Mode 

Indicator Light Flashing

automatically shut down after 

Switch must be set to "AUTO" 

5 seconds.

or "CHARGE ONLY."

* User-supplied.

“BATTERY” Indicator Lights

Operating Mode Switch

“OPERATION” Indicator Lights

200705102 93-2678 APSX700HF OM.qxd  8/30/2007  12:34 PM  Page 9

Содержание PowerVerter DC-to-AC Inverter/Charger APSX700HF

Страница 1: ...ing your connected battery bank Built in surge suppression provides connected equipment with additional protection The APSX700HF is the clean quiet emergency backup power alternative to gas generators...

Страница 2: ...e would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC inpu...

Страница 3: ...AC Connection section for instructions AC Output IEC 60320 C13 permits connection of equipment that would normally be plugged into a utility outlet Note The unit will always pass AC power to connected...

Страница 4: ...r a 20 hour discharge rate Actual amp hour capacities are less when batteries are discharged at faster rates For example batteries discharged in 55 minutes provide only 50 of their listed amp hour rat...

Страница 5: ...at the front and rear of the unit The user must supply mounting hardware and is responsible for determining if the hardware and mounting surface are adequate to support the weight of the unit Read the...

Страница 6: ...ect Fuse NEC National Electrical Code article 551 requires that you connect all of your Inverter Charger s positive DC connectors directly to a UL listed fuse s and fuse block s within 18 inches 45 72...

Страница 7: ...tching between operating modes as appropriate to your situation AUTO Switch to this mode when you need constant uninterrupted AC power for connected equipment The Inverter Charger will supply AC power...

Страница 8: ...d alert you to fault conditions Battery Charge Level Indicator Illuminated Battery Capacity Charging Discharging Green 91 Full Green Yellow 81 90 Yellow 61 80 Yellow Red 41 60 Red 21 40 All three ligh...

Страница 9: ...Service for assistance All Three Battery Indicator Battery is overcharged Unit will Disconnect any auxiliary chargers Lights Are Flashing shut down to prevent battery Reset by moving Operating Mode Se...

Страница 10: ...Capacity DC 6 A Line VAC Operation Total Input AC Current Continuous Charger at Maximum 4 5 A Maximum Output Current Continuous 3 A Note on Labeling Two symbols are used on the APS labels V AC Voltag...

Страница 11: ...ty does not apply to equipment which has been damaged by accident negligence or misapplication or has been altered or modified in any way including opening of the unit s casing for any reason This war...

Страница 12: ...12 1111 W 35th Street Chicago IL 60609 USA 1 773 869 1234 www tripplite com 200705102 93 2678...

Отзывы: