Battery Connection

• Connect DC Wiring: 

Though your Inverter/Charger is a high-efficiency

converter of electricity, its rated output capacity is limited by the length and gauge
of the cabling running from the battery to the unit. Use the shortest length and
largest diameter cabling (maximum 2 AWG (6.544 mm)) to fit your
Inverter/Charger’s DC connectors. Shorter and heavier gauge cabling reduces
DC voltage drop and allows for maximum transfer of current. Your
Inverter/Charger is capable of delivering peak wattage above its rated
continuous wattage output for brief periods of time. See the 

Specifications

section for details. Heavier gauge cabling should be used when continuously operating heavy draw
equipment under these conditions. Tighten your Inverter/Charger and battery terminals to approximately
3.5 Newton-meters of torque to create an efficient connection and to prevent excessive heating at this
connection. Insufficient tightening of the terminals could void your warranty. 

See the 

Specifications

section for battery wiring recommendations.

• Connect Ground: 

Use an 8 AWG (3.264 mm) wire or larger to connect the Main Ground Lug to earth

ground. See the 

Features

section to locate the Main Ground Lug on your Inverter/Charger. All

installations must comply with national and local codes and ordinances.

• Connect Fuse: 

NEC (National Electrical Code) article 551 requires that you connect all of your

Inverter/Charger’s positive DC connectors directly to a UL-listed fuse(s) and fuse block(s) within 18
inches (45.72 cm) of the battery. The minimum rating of the DC fuse is listed in the 

Specifications

section. See the following battery configuration diagrams for proper fuse placement.

Connect your Inverter/Charger to your batteries using the following procedures

DC Connectors

Battery Configuration

You may connect one or more batteries to your Inverter/Charger in either of the following
configurations.

Parallel Connection: The voltage of each connected battery must match the Inverter/Charger's 
Nominal DC Input Voltage (12 V).

Series Connection: The total voltage of all connected batteries must match the Inverter/Charger's 
Nominal DC Input Voltage (12 V). Example: 6 V + 6 V = 12 V.

Contact Tripp Lite technical support for assistance with battery connection configurations.

2

1

12 Volts

12 Volts

APSX700HF

Parallel Connection

WARNING! 
• Failure to properly ground your Inverter/Charger may result in a lethal 

electrical shock hazard.

• Never attempt to operate your Inverter/Charger by connecting it directly 

to output from an alternator rather than a battery or battery bank.

• Observe proper polarity with all DC connections.

Battery
UL-Listed Fuse & Fuse Block mounted within 18 inches (45.72 cm) of battery
Large-Diameter Cabling, Maximum 2 AWG (6.544 mm), to Fit Terminals

1

6 Volts

6 Volts

APSX700HF

2

Series Connection

A
B
C

A

A

B

B

C

C

200705102 93-2678 APSX700HF OM.qxd  8/30/2007  12:34 PM  Page 6

Содержание PowerVerter DC-to-AC Inverter/Charger APSX700HF

Страница 1: ...ing your connected battery bank Built in surge suppression provides connected equipment with additional protection The APSX700HF is the clean quiet emergency backup power alternative to gas generators...

Страница 2: ...e would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC inpu...

Страница 3: ...AC Connection section for instructions AC Output IEC 60320 C13 permits connection of equipment that would normally be plugged into a utility outlet Note The unit will always pass AC power to connected...

Страница 4: ...r a 20 hour discharge rate Actual amp hour capacities are less when batteries are discharged at faster rates For example batteries discharged in 55 minutes provide only 50 of their listed amp hour rat...

Страница 5: ...at the front and rear of the unit The user must supply mounting hardware and is responsible for determining if the hardware and mounting surface are adequate to support the weight of the unit Read the...

Страница 6: ...ect Fuse NEC National Electrical Code article 551 requires that you connect all of your Inverter Charger s positive DC connectors directly to a UL listed fuse s and fuse block s within 18 inches 45 72...

Страница 7: ...tching between operating modes as appropriate to your situation AUTO Switch to this mode when you need constant uninterrupted AC power for connected equipment The Inverter Charger will supply AC power...

Страница 8: ...d alert you to fault conditions Battery Charge Level Indicator Illuminated Battery Capacity Charging Discharging Green 91 Full Green Yellow 81 90 Yellow 61 80 Yellow Red 41 60 Red 21 40 All three ligh...

Страница 9: ...Service for assistance All Three Battery Indicator Battery is overcharged Unit will Disconnect any auxiliary chargers Lights Are Flashing shut down to prevent battery Reset by moving Operating Mode Se...

Страница 10: ...Capacity DC 6 A Line VAC Operation Total Input AC Current Continuous Charger at Maximum 4 5 A Maximum Output Current Continuous 3 A Note on Labeling Two symbols are used on the APS labels V AC Voltag...

Страница 11: ...ty does not apply to equipment which has been damaged by accident negligence or misapplication or has been altered or modified in any way including opening of the unit s casing for any reason This war...

Страница 12: ...12 1111 W 35th Street Chicago IL 60609 USA 1 773 869 1234 www tripplite com 200705102 93 2678...

Отзывы: