background image

Automatic overload and thermal (overheating) shutoff

Front panel remote control connector enables remote off/on switching (APSRM4 sold separately)

Load sensing control dial enables adjustable load threshold required to automatically turn the inverter on and off in DC mode as load

conditions change

Automatic Generator Starter jack enables user configuration of automatic generator start-up as inverter batteries drop to 23.0 VDC and

generator shutoff as inverter batteries are recharged to 28.2 VDC.

Remote battery temperature sensing connection function prolongs battery life by adjusting the charge float voltage level based on battery

temperature

DB9 communication port for SNMPWEBSOLOHV management.

Specifications

OVERVIEW

Intended
Application

Emergency Power, Remote Power, Alternative Power

OUTPUT

Frequency
compatibility

50 / 60 Hz

Output watts

6000

Continuous output
capacity (watts)

6000

Peak output
capacity (watts)

12000

Output nominal
voltage

208/230V

Output voltage
regulation

LINE POWER (AC): Maintains 208/230V nominal sine wave output from line power source. INVERTER POWER (AC):
Maintains sine wave output voltage of 208/230 VAC (+/-5%).

Output frequency
regulation

50/60 Hz (+/- 0.3 Hz)

Outlet quantity /
type

Hardwire

INPUT

Nominal Input
Voltage(s)
Supported

208V AC; 230V AC

Recommended
Electrical Service

DC INPUT: Requires 48VDC input source capable of delivering 138A for the required duration (when used at full
continuous capacity - DC requirements increase during OverPower and DoubleBoost operation). For automotive
applications, professional hardwire installation with 250A minimum battery system fusing is recommended.

Maximum input
amps / watts

DC INPUT: Full continuous load - 145A at 48VDC. AC INPUT: 30 amps at 208/230VAC with full inverter and charger
load

Input connection
type

DC INPUT: Set of DC bolt-down terminals. AC INPUT: Hardwire via built in terminal strip with cover plate

Voltage
compatibility (VAC)

208; 230

Voltage
compatibility (VDC)

48

BATTERY

Expandable
battery runtime

Runtime is expandable with any number of user supplied wet or gel type batteries