9
3. Installation
3.2-3
Input Power Cord Connection
(PDUMNH20HV Only):
Insert the
IEC 60320 C19 connector
A
of
the input power cord into the IEC
60320 C20 inlet
B
of the PDU.
Connect the other end of the input
power cord
C
to a compatible
source of AC power, such as a UPS
system, PDU or utility outlet. The
PDU should be provided with
over-current protection.
PDUMNH20HV should be provided
with a maximum 20A branch-rated
over-current protection device.
Note: The AC power source should
not share a circuit with a heavy
electrical load (such as an air
conditioner or refrigerator).
3.2-4
Connect Equipment to PDU:
Do
not exceed the load rating of the
PDU. The total electrical current
used by the PDU will be displayed
on the digital meter in amperes.
Refer to: 2. Features, Digital Load
Meter (Ammeter) for details.
3.2-4
PDUMNH20HV
3.2-4
PDUMNH30HV
PDUMNH20HV
3.2-3
88
C
A
B
3.3 Networking the PDU
For network configuration instructions, please refer to the WEBCARDLX owner’s manual
(PN 93358E) included with this product.