background image

4

Basic Operation

Power ON/OFF

•  ON: When the UPS system is OFF, press the ON/OFF/TEST/MUTE button 

A

 for 1 second (the 

UPS will beep when 1 second has elapsed) to turn the UPS system ON. The green “ON/OFF” light  

B

 will illuminate when the UPS system is ON.

•  OFF: When the UPS system is ON, press the ON/OFF/TEST/MUTE button 

A

 for 1 second (the 

UPS will beep when 1 second has elapsed) to turn the UPS system OFF. The green “ON/OFF” light 

B

 will cease to illuminate when the UPS system is OFF. The UPS system’s outlets and connected 

equipment will cease to receive AC power and the battery will cease to charge.

Automatic Voltage Regulation (AVR)

•  When the UPS detects that input voltage is below the acceptable range, it will automatically adjust 

the voltage to a safe level. This is an automatic function of the UPS system and does not require user 
intervention.

•  Faint clicking sounds may be emitted by the UPS system during automatic voltage regulation. This is 

normal.

•  If the input voltage is extremely far above or below the acceptable range, the UPS system will switch 

to On Battery mode (see “On Battery / Low Battery / Overload” section below) in order to adjust the 
voltage to a safe level.

On Battery / Low Battery / Overload

•  During a utility power failure (or extreme voltage fluctuation), the UPS system will switch to On 

Battery mode. When the UPS switches to On Battery mode, stored battery power supports the 
uninterrupted operation of connected equipment until utility power is restored or battery reserves are 
depleted.

•  After the UPS system switches to On Battery mode, the alarm will emit 4 beeps every 7 seconds. 

The alarm may be muted by pressing the ON/OFF/TEST/MUTE button 

A

 for 2 seconds.

•  If the UPS detects a Low Battery condition after switching to On Battery mode, the frequency of the 

audible alarm will increase to 4 beeps every 2 seconds and the red “Overload / Check Battery” light  

C

 will blink.

•  If the UPS detects an Overload condition after switching to On Battery mode, the audible alarm will 

sound continuously and the red “Overload / Check Battery” light 

C

 will illuminate continuously. In 

order to correct an overload, turn the UPS OFF and remove some of the attached equipment. 

 

Note: If the overload exceeds 150% of the UPS system’s capacity, the UPS system will automatically shut down.

A

B

C

Содержание OMNIPOWER PRO550

Страница 1: ...Tripp Lite All rights reserved Important Safety Instructions 2 Installation 3 Basic Operation 4 Storage and Service 6 W a r r a n t y R e g i s t r a t i o n r e g i s t e r o n l i n e t o d a y f o...

Страница 2: ...ailure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxyg...

Страница 3: ...adequately during a power failure until the internal battery has charged for 4 6 hours It will take up to 8 hours for the battery to charge completely 2 Output Connections Plug your equipment into th...

Страница 4: ...em will switch to On Battery mode see On Battery Low Battery Overload section below in order to adjust the voltage to a safe level On Battery Low Battery Overload During a utility power failure or ext...

Страница 5: ...is unavailable i e during a blackout press the ON OFF TEST MUTE button A for 1 second the UPS will beep when 1 second has elapsed to turn the UPS system ON The UPS will then provide power to its outp...

Страница 6: ...ange to send you proper packaging Securely pack the UPS to avoid damage during shipping Do not use Styrofoam beads for packaging Any damages direct indirect special incidental or consequential to the...

Страница 7: ...1234 www tripplite com Derechos de Autor 2008 Tripp Lite Todos los derechos reservados Instrucciones de Seguridad Importantes 8 Instalaci n 9 Operaci n B sica 10 Almacenaje y Servicio 11 English 1 Si...

Страница 8: ...a del equipo de soporte de vida o significativamente afectar su seguridad o efectividad no es recomendado No use este equipo en presencia de una mezcla anest sica inflamable con aire oxigeno u oxido n...

Страница 9: ...no estar soportado adecuadamente durante una falla de energ a hasta que la bater a interna se haya cargado de 4 a 6 horas Tomar hasta 8 horas a la bater a cargarse completamente 2 Conexiones de Salida...

Страница 10: ...spaldo On Battery a fin de ajustar el voltaje a un nivel seguro Vea la secci n En Respaldo Bater a Baja Sobre Carga abajo En Respaldo Bater a Baja Sobre Carga Durante una falla de la energ a del servi...

Страница 11: ...star iluminada Segundo desconecte el equipo conectado Tercero desconecte el cable de alimentaci n de corriente de la toma de corriente de la pared Si el sistema UPS ser almacenado por un periodo prolo...

Страница 12: ...or el establecimiento que lo vendi junto con el producto en el lugar donde fue adquirido TRIPP LITE se compromete a reparar y en caso de que a su juicio no sea posible la reparaci n a cambiar el equip...

Отзывы: