7
Operation
14. UPS Fault Information
Holding Register (Read Function 0x03)
Address
Description
Unit
Example Response
Hex
Decimal
0x02A3
675
Fault kind ASCII 00:no fault default:FF
See Appendix 3
0x3030 (Not Fault)
0x4646 (Fault)
0x02E5 - 0x02EC
741 - 748
Fault kind1 ASCII module ID : 01-07
See Appendix 3
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x03B0 - 0x03CB
944 - 971
Fault kind1 ASCII module ID : 08-35
See Appendix 3
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x3031
0x3132
0x0000
0x0000
0x3336
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
0x0000
15. Loss Point
Holding Register (Read Function 0x03)
Address
Description
Unit
Hex
Decimal
0x034A
842
High efficiency mode Voltage high loss point
V
0x034B
843
High efficiency mode Voltage low loss point
V
0x034C
844
Free run mode frequency high loss point
0.1 Hz
0x034D
845
Free run mode frequency low loss point
0.1 Hz
0x034E
846
Bypass Freq. high loss point
0.1 Hz
0x034F
847
Bypass Freq. low loss point
0.1 Hz
0x0350
848
Bypass Voltage high loss point
V
0x0351
849
Bypass Voltage low loss point
V