4
Operation
4. Control Result
Holding Register (Read Function 0x03)
Addresses start at 0 and are numbered 1-16 address as 0-15.
Address
Description
Value 0/Value 1
Hex
Decimal
0x0025
37
Bit15 = Flag:Silence buzzer beep (Audible Alarm)
0:FAIL/1:SUCCESS
Bit14 = Flag:buzzer beep open (Audible Alarm)
0:FAIL/1:SUCCESS
Bit13 = Flag:Test until battery low
0:FAIL/1:SUCCESS
Bit12 = Flag:Remote turn off UPS
0:FAIL/1:SUCCESS
Bit11 = Flag:Remote turn on UPS
0:FAIL/1:SUCCESS
Bit10 = Flag:Cancel shutdown
0:FAIL/1:SUCCESS
Bit9 = Flag:Cancel test
0:FAIL/1:SUCCESS
Bit8 = Flag:10 seconds test
0:FAIL/1:SUCCESS
Bit7 = Reservation
N/A
Bit6 = Reservation
N/A
Bit5 = Reservation
N/A
Bit4 = Reservation
N/A
Bit3-Bit0 = Reservation
N/A
0x0026
38
Bit10 = UPS turn to bypass
0:FAIL/1:SUCCESS
Bit9-Bit0 = Reservation
N/A
0x0423
1059
Bit15 = EPO function in normal open
0:FAIL/1:SUCCESS
Bit14 = EPO function in normal close
0:FAIL/1:SUCCESS
Bit13 = Mode output frequency 50 Hz
0:FAIL/1:SUCCESS
Bit12 = Mode output frequency 60 Hz
0:FAIL/1:SUCCESS
Bit11 = Charger On
0:FAIL/1:SUCCESS
Bit10 = Charger Off
0:FAIL/1:SUCCESS
Bit9 = Enable independent battery
0:FAIL/1:SUCCESS
Bit8 = Disable independent battery
0:FAIL/1:SUCCESS
5. Setting Parameter to Default Value
Holding Register (Read Function 0x03, Write Function 0x10)
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Description
Value 0/Value 1
Type
Hex
Decimal
0x0030
48
Bit15 = Setting control parameter to default value
Y:8000
Read / Write
Bit14-Bit0 = Reservation
N/A
N/A
0x003B
59
Bit15 = Flag:Setting control parameter to default value
0:FAIL/1:SUCCESS
Read Only
Bit14-Bit0 = Reservation
N/A
N/A