108
Serial Port Pattern Match Alert
– This alert will be triggered if a regular expression is found in
the serial ports character stream that matches the regular expression you enter in the
Pattern
field. This alert type will only be applied serial ports.
UPS Power Status Alert
- This alert will be triggered when the UPS power status changes
between On Line, On Battery, and Low Battery. This alert type will only be applied to UPSs.
Environment and power alert
- Refer to next section for details on selecting and configuring this
alert type.
7.2.3 Configuring Environment and Power Alert Type
This alert type will be applied to any UPS’s, RPC’s and EMD temperature and humidity sensors you have
nominated:
Select
Sensor Alert
to activate.
Specify which
Sensor Type
to alert on (Temperature, Humidity, Power Load and Battery
Charge).
Set the levels at which
Critical
and/or
Warning
alerts are to be sent. You can also specify
High
and/or
Low Set Points
for sending alerts and the Hysteresis to be applied before
resetting off the alerts.
Note
Specify the
Set Point
values are in:
Degrees Celsius for Temperature
Amps (Current) for Power Load
% (Percentage) for Humidity and Battery Charge