Storage & Service

Before storing your UPS, disconnect all equipment to avoid battery drain, then place the UPS in
the OFF mode by putting it in STANDBY mode, then disconnecting it from utility power (see
Basic Operation). If you store your UPS for an extended period of time, recharge the UPS batteries
once every three months by following Steps 1 and 2 in the Connection section and allowing the
UPS to charge its batteries for 4-6 hours before placing it back in storage. If you leave your UPS
batteries discharged for an extended period of time, they will suffer a permanent loss of capacity.

If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will
refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING
MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem.
If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.

Model:

OM500RMX

Series:

AGOM700KSR61

Output Capacity (VA/Watts):

500/300

Battery Runtime in Minutes (Half Load/Full Load):

17/5

Battery Recharge Time:

2-4 hrs.

Approvals:

FCC Part 15 Class A

Input Voltage (120V); Input Frequency (60 Hz); Online Input Voltage Range (79-147 volts); Voltage-Regulated
Output Voltage Range (120 ±9%); On-Battery Output Voltage Range (115 ±5%); Output Waveform Line Mode
(filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE
587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Surge Protection Modes (H to N, H to G, N to G).

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.

Tripp Lite has a policy of continuous improvement. Specifications are subject to change.

Specifications

Storage

Service

93-2041 (200208100)

8

200208100 93-2041 OM500RMX Manual.qxd  9/11/2002  3:09 PM  Page 8

Содержание 500 VA

Страница 1: ...ns 2 Mounting 3 Connection 4 Basic Operation 5 Storage and Service 8 Copyright 2002 Tripp Lite All rights reserved OmniSmart is a trademark of Tripp Lite OmniSmart RMX 500 VA 120V Input Output UPS System Intelligent Line Interactive Industrial Cabinet Specifications 8 200208100 93 2041 OM500RMX Manual qxd 9 11 2002 3 08 PM Page 1 ...

Страница 2: ...ept battery replacement There are no user serviceable parts inside Battery replacement must be performed by qualified service personnel Because the batteries present a risk of electrical shock and burn from high short circuit current observe proper precautions Unplug and turn off the UPS before performing battery replacement Use tools with insulated handles and take caution that the battery termin...

Страница 3: ...ount Installation Mounting Suggested DIN Rail Installation DIN RAIL DIN MOUNT BRACKET 1 1 2 Attach the DIN mounting brackets A to the mounting ears by lining the brackets captive nuts up with the mounting ears holes then attaching them with the bolts provided B Attach mounting ears C to the rear mounting holes of the UPS using the screws provided D Note that there is a left mounting bracket and a ...

Страница 4: ...o the GROUND OUT green yellow terminal Connect the incoming hot wire to the HOT IN brown terminal Connect the incoming neutral wire to the NEUTRAL IN blue terminal Connect the outgoing hot wire to the HOT OUT black terminal Connect the outgoing neutral wire to the NEUTRAL OUT white terminal Turn utility power on Your UPS will enter STANDBY mode The LINE POWER LED will begin flashing The UPS system...

Страница 5: ...tteries but its output is not active Pressing the POWER button while the UPS is in STANDBY mode will put the UPS in the ON mode Cutting AC power to the UPS while it is in STANDBY mode will put the UPS in the OFF mode ON The light is on The UPS is receiving AC power charging its batteries and delivering power to connected equipment If AC power is lost while the UPS is ON i e a blackout occurs the U...

Страница 6: ...the load on the UPS If the LOW BATTERY alarm a constant beep sounds your UPS s batteries may need replacing or the batteries may simply be less than fully charged Let the UPS charge for twelve hours then perform a second self test If the LOW BATTERY alarm sounds again contact Tripp Lite for service LINE POWER This green light will turn ON whenever your UPS is receiving normal AC line power It will...

Страница 7: ...omatically save open files and shut down equip ment during a blackout see Connection page 4 Battery Door Qualified service personel can remove this plate to remove and replace the UPS batteries All Battery Warnings must be observed see Important Safety Warnings page 2 Automatic Voltage Regulation Internal During brownouts your UPS will automatically correct low AC line voltage When automatic volta...

Страница 8: ...gulated Output Voltage Range 120 9 On Battery Output Voltage Range 115 5 Output Waveform Line Mode filtered sinewave Output Waveform Battery Mode PWM sine wave AC Surge Suppression exceeds IEEE 587 Cat A B standards AC Noise Attenuation 40 dB AC Surge Protection Modes H to N H to G N to G This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This...

Отзывы: