triOS TTrig 12C100000 Скачать руководство пользователя страница 3

TTrig 

//

 

Quick Guide

3

D04-05Aen201908 Quick Guide TTrig

TriOS Mess- und Datentechnik GmbH · Bürgermeister-Brötje-Str. 25 · D-26180 Rastede · Germany 

Phone: +49 (0) 4402 69670 - 0 · Fax: +49 (0) 4402 69670 - 20 · [email protected] · www.trios.de

Commissioning

Electrical installation

After opening the protective cover, the TTrig is first connected to a power supply (12..24 VDC). A 2-pin Phoenix connector is locat-
ed on the left-hand side for this purpose. 

Sensor connection and wiper connection

The sensor must then be connected to the M12 socket and optionally a wiper to the M8 socket. The following table shows the 
configuration options.

Function test

The WIPER and SENSOR buttons should be operated manually one after the other for the subsequent function test. The function 
of the wiper is visible by its movement. For OPUS it is recommended to download the data logger and check the completeness 
of the measurements.

Configuration of automatic measurement

The measurement interval is set on site on the TTrig (rotary encoder "1. INTERVAL"). In addition, a start delay (rotary encoder "2. 
DELAY") can be activated.  The following table shows the configuration options.

Cable 

bushing

M8 

connection

M12 
connection

Rotary encoder position

1.Interval

0

15 minutes

1

30 minutes

2

1 h

3

2 h

4

3 h

5

4 h

6

6 h

7

8 h

8

12 h

9

24 h

Rotary encoder position

2. Delay

0

No delay time

1

1 h

2

2 h

3

3 h

4

4 h

5

6 h

6

8 h

7

10 h

8

15 h

9

20 h

Содержание TTrig 12C100000

Страница 1: ... Remote or self sufficient measuring stations can thus be operated maintenance free for several months An RJ 45 Ethernet interface provides access to the sensor s G2 web interface for downloading the measurement data from the data logger with a notebook Technical Specifications POWER SUPPLY Voltage supply 12 24 VDC max 4A Power in standby 1mW SENSOR INTERFACES Connection M12 for TriOS G2 sensors 1...

Страница 2: ...permanently for data download Sensor single measurement Wiper activation Reset reset program If the red power fail LED flashes this button can be pressed to start a manual attempt to restore normal operation LEDs Description Colour Function Behaviour Start white Measurement interval active LED flashes briefly once every 20 seconds white Sensor initialisation LED flashes continuously Wiper white Wi...

Страница 3: ...nfiguration options Function test The WIPER and SENSOR buttons should be operated manually one after the other for the subsequent function test The function of the wiper is visible by its movement For OPUS it is recommended to download the data logger and check the completeness of the measurements Configuration of automatic measurement The measurement interval is set on site on the TTrig rotary en...

Страница 4: ...ice LED flashes every 20 s please refer to the section Troubleshooting Sensor not found Data storage and retrieval All measurement data is only stored on the internal 2GB SD card of the sensor A notebook can be connected via an RJ 45 socket on the TTrig so that the stored measurement data can be downloaded via the web interface Press the Service button on the TTrig to supply the sensor with power ...

Страница 5: ...set to 1 1 INTERVAL and 2 DELAY can now be reconfigured By pressing the start button the TTrig takes over the settings of the rotary encoders into the new automatic measurement All stored data of the sensor is retained If the web interface is also not available please contact us at support trios de Troubleshooting Power fail A power fail occurs when the power supply is no longer sufficient for the...

Отзывы: