The twenty fifth page shows the Waveform for current in R-phase. Here user can see
if harmonic distortion is occurring in the wave form due to non-linear loads like
rectifier and UPS etc. Likewise, the wave form for current in both Y-phase and B-
phase will also be shown on 27th and 29th
pages.
The 30
th
display page shows relay status with its selected parameter for which alarm
has to be generated. Value displayed in bracket indicates the value programmed for
assigned parameter. Value displayed without bracket indicates run time value of
assigned parameter.
Run Mode in 3P3W
The similar pages for the various parameters including Harmonic values, Histograms
and Waveforms such as shown before in 3P4W can also be seen in 3P3W except
the individual PF in three phases.
Run Mode in 1P2W
The similar pages for the various parameters including Harmonic values, Histograms
and Waveforms such as shown before in 3P4W can also be seen in 1P2W for single
phase Voltage & Current. In 1P2W mode, it considers R-Phase Voltage & Current for
measurement.