1.

 

DISCLAIMER OF LIABILITY

 

The  installation,  handling  and  use  of  Trina  Solar  Crystalline  series  modules  are  beyond  company  control.  Accordingly, 
Trina Solar does not assume responsibility for loss, damage, injury or expense resulting from improper installation, handling, 
use or maintenance. 
Trina Solar assumes no responsibility for any infringement of patents or other rights of third parties that may result from use 
of the module. No license is granted by implication or under any patent or patent rights. 
Specifications included in this manual are subject to change without prior notice. 
 

2.

 

SAFETY PRECAUTIONS 

1.

 

When  designing  the  PV  system,  please  always  take  into  consideration  the  variation  of  the  voltage  under  different 
temperatures  (please  check  the  respective  temperature  coefficients  of  the  modules,  the  Voc  of  the  modules  will  rise 
when the temperature drops);  

2.

 

We  require  that  every  series  PV  module  string  should  be  fused  prior  to  be  connected  with  other  strings.  For  the 
maximum fuse rate, please refer to the detailed SPEC in the last page. 

3.

 

Solar photovoltaic (PV) modules generate electricity when exposed to light. An array of many modules can cause lethal 
shocks and/or burn hazards. Only authorized and trained personnel should have access to the modules. 

4.

 

Use properly insulated tools and appropriate protective equipment to reduce risk of electric shock. 

5.

 

Do not stand or step on the module. 

6.

 

Do not damage or scratch the front or backside surfaces of the module. 

7.

 

Never use a module with broken glass or top substrate. Broken modules should not  be repaired and contact with any 
module surface can lead to electrical shock. 

8.

 

Do not disassemble the modules or remove any part of the module. 

9.

 

Protect plug contacts against soiling and do not make any plug connections using soiled plug contacts. 

10.

 

Do not install or handle modules when they are wet or during periods of high wind. 

11.

 

Do not connect cable from the positive terminal to the positive terminal of one single PV module. 

12.

 

Make sure connectors have no gap between insulators. A gap can cause fire hazard and/or danger of an electrical shock. 

13.

 

Make sure that the polarity of each module or a string is not reversed relative to the other the modules or strings. 

14.

 

Artificially concentrated sunlight should not be used on the PV module. 

15.

 

In markets conforming to IEC standard, maximum system voltage must not exceed 1500V DC. In markets conforming 
to UL standard, maximum system voltage must not exceed 1000V DC. For roof use, the maximum system voltage must 
not exceed 600V according to National Electrical Code. 

16.

 

Under  normal  conditions,  a  photovoltaic  module  is  likely  to  experience  conditions  that  produce  more  current  and/or 
voltage  than reported at  standard test  conditions.  The requirements  of  the  National  Electrical  Code  (NEC) in  Article 
690  shall  be  followed  to  address these  increased  outputs.  In  installations not  under  the requirements  of  the  NEC, the 
values of ISC and VOC marked on this module should be multiplied by a factor of  1.25 when determining component 
voltage ratings, conductor ampacities , over-current device ratings, and size of controls connected to the PV output. 

17.

 

Our  module  application  class  is  class  A,  modules  rated  for  use  in  this  application  class  may  be  used  in  systems 
operating at greater than 50V DC or 320W, where general contact access is anticipated. 

18.

 

Installation  shall  be  in  accordance  with  CSA  C22.1,  Safety  Standard  for  Electrical  Installations,  Canadian  Electrical 
Code, Part 1. 

19.

 

A  module  with  exposed  conductive  parts  is  considered  to  be  in  compliance  with  IEC&UL  1703  only  when  it  is 
electrically  grounded  in  accordance  with  the  instructions  presented  below  and  the  requirements  of  the  National 
Electrical Code. 

20.

 

Module achieved fire rating 

Type 13

 according UL1703 updated on 20

th

 May 2014. And this fire rating of this module 

is valid only when mounted in the manner specified in the mechanical mounting instruction. 

21.

 

The system fire rating should be evaluated with roof cover and mounting racking. 

 

3.

 

UNPACKING AND STORAGE 

1.

 

Before installation, keep all modules and electrical contacts clean and dry. 

2.

 

If it is necessary to store modules temporarily, a dry, ventilated room should be used. 

3.

 

When unpacking, carry modules with both hands. Do not place modules on top of each other. 

4.

 

The double glass module is should be handle carefully, so non-slip gloves are required when handling and installation. 

5.

 

Please use the supporting removal tool when dismantling the plywood cases. 

 

Содержание DUOMAX

Страница 1: ...G5 47 TSM PDG14 40 TSM PDG14 47 Duomax TSM PEG40 40 TSM PEG40 47 TSM PEG5 40 TSM PEG5 47 TSM PEG14 40 TSM PEG14 47 Duomax M Plus TSM DEG40 40 TSM DEG40 47 TSM DEG5 40 TSM DEG5 47 TSM DEG14 40 TSM DEG14 47 TSM DEG40 40 II TSM DEG40 47 II TSM DEG5 40 II TSM DEG5 47 II TSM DEG14 40 II TSM DEG14 47 II ...

Страница 2: ...L CONDITIONS AND SITE SELECTION 4 5 1 CLIMATE CONDITION 4 5 2 SITE SELECTION 4 6 MOUNTING INSTRUCTIONS TRINA HOOK 4 6 1 COMPONENTS OVERIEW 4 6 2 MOUNTING METHODS 5 6 3 REMARKS OF INSTALLATION 6 7 MODULE WIRING 8 8 MODULE TILT ANGLE 8 9 MECHANICAL DRAWING OF PV MODULE 8 10 MAINTENANCE AND CARE 9 11 SPECIFICATIONS 9 12 BYPASS DIODES AND BLOCKING DIODES 9 13 WARNING 10 14 CHANGE HISTORY 10 ...

Страница 3: ...e sure that the polarity of each module or a string is not reversed relative to the other the modules or strings 14 Artificially concentrated sunlight should not be used on the PV module 15 In markets conforming to IEC standard maximum system voltage must not exceed 1500V DC In markets conforming to UL standard maximum system voltage must not exceed 1000V DC For roof use the maximum system voltage...

Страница 4: ...by buildings trees chimney etc at any time of the day 3 Do not install in corrosive environments such as beaches or landfill that can be easily flooded 4 Do not install PV modules in a location where modules could be immersed in water or continually exposed to water from a sprinkler or fountain 5 Do not install PV modules over naked flames or flammable materials 6 Interspaces the clearance between...

Страница 5: ...e beginning the installation Also be sure that the site has been completely prepared before beginning the installation STEP 1 Install the specified bolts Setting the specified bolts into the hook STEP 2 Insert the bolt hole 1 Lift up the module ensure the bolt over the racking 2 Aim the bolt to racking 3 Insert the bolt hole STEP 3 Tighten the nut M8 Tighten to a torque of 16 20N m M10 Tighten to ...

Страница 6: ...il 2016 Doc No PS M 0433 Ver A Page 6 of 10 Tighten the nut 16N m 20N m STEP 4 Install the module Repeat steps 1 3 install the module 6 3 REMARKS OF INSTALLATION Keep more than 10 mm gap between each module Gap ...

Страница 7: ...ead of the insert place As shown above Note For PV module landscape installation the supporting rails need change as shown in below add two rails For 60 cell Duomax module For 72 cell Duomax module Note Please consult with Trina Solar engineers to confirm whether the rail match Trina hook or not ...

Страница 8: ...Datasheet Specifications for the maximum electrical rating of series fuse 8 MODULE TILT ANGLE Trina Solar PV modules connected in series should be installed at the same orientation and angle Different orientation or angle may cause loss of output power because each module may be exposed to different amounts of solar irradiation Trina Solar PV modules produce the most power when they are perpendicu...

Страница 9: ...Association Through the pre financed PV Cycle program Trina Solar PV modules will be taken back and treated in an environmentally sustainable manner WARNING For any electrical maintenance the PV system must first be shut down Improper maintenance can cause lethal electric shock and or burns 11 SPECIFICATIONS For module specifications please see the Datasheet included in the shipment carton and vis...

Страница 10: ...allation is not working properly then contact your installer immediately 1 Contact your installer 2 Contact Trina Solar after sales service team at http customerservice trinasolar com 3 Submit the Customer Feedback form at www trinasolar com one of our technical service representatives will contact you as quickly as possible A username and password is required to send feedback from the customer se...

Отзывы: