background image

 

 

20 

6.4  ELECTRICAL INSTALLATION 

6.4.1 

SAFETY INSTRUCTION 

All wiring installation should be carried out by qualified installers in accordance with local electrical 
construction codes, procedures, and regulations. 

Modules  can  be  connected  in  series to  increase the  operating  voltage  by  connecting  the  positive 
terminal of one module into the negative terminal of the next one. Before connecting, always ensure 
that the contacts are corrosion-free, clean, and dry. 

The product can be irreparably damaged if an array string is connected in reverse polarity to another. 
Always verify the voltage and polarity of each string before making a parallel connection. If a reversed 
polarity or a difference of more than 10V between strings was detected, check the string configuration 
before connection. 

The  standard  copper  cables  applied  in  Trina  Solar  modules  are  UV  resistant  and  with  a  cross-
sectional area of 

≥4 mm

2

 (12 AWG). All other cables applied to connect the DC system should be 

provided with a similar or larger wire cross section. Trina Solar recommends that all cables are routed 
in appropriate conduits or rails where water does not accumulate. 

The string voltage must not be higher than the maximum system voltage, as well as the maximum 
input voltage of the inverter and the other electrical devices installed in the system.  In order to ensure 
this, the open circuit voltage of an array needs to be calculated at the lowest expected local ambient 
temperature, which can be determined using the following formula: 

Max System Voltage

N × 𝑉

𝑜𝑐

× [1 + 𝑇𝐶

𝑉𝑂𝐶

× (𝑇

𝑚𝑖𝑛

− 25)]

 

where 

N

 

Number of modules in series 

𝑉

𝑜𝑐

 

Open circuit voltage (refer to product label or data sheet) 

𝑇𝐶

𝑉𝑂𝐶

 

Thermal coefficient of open circuit voltage (refer to data sheet) 

𝑇

𝑚𝑖𝑛

 

The lowest expected environment temperature 

The number of modules that can be connected shall be determined by a qualified institution or person 
in accordance with the design specifications of the photovoltaic system and the local electrical design 
specifications. The calculation formula recommended by Trina Solar shall be for reference only. 

Every module is provided with two standard output cables, and each terminated with a plug-and-play 
connector. All wiring and electrical connections must be installed in accordance with the electrical 
design and construction specifications, procedures and regulations at the place of installation. 

The minimum and maximum outer diameters of the cable are 5 to 7 mm (0. 20 to 0.28 in). 

For wiring connections, please use standard PV copper wires with a cross-section area of at least 4 
mm

2

 (12 AWG), and should be light-resistant and temperature-resistant at a minimum of 90 °C. 

 

Do not bend the cables less than 43 mm (1.69 inch) radius. PV cables will be damaged if bending 

radius less than 43 mm.  

Figure 4: The correct routing and minimum bending radius of cables. 

Содержание 210 Vertex Series

Страница 1: ......

Страница 2: ...DE18M 08 II DE19 DE20 DE21 Bifacial products DEG18MC 20 II DEG19C 20 DEG20C 20 DEG21C 20 Contents of this document are subject to change without notice For the latest document please refer to Trina S...

Страница 3: ...INSTALLATION SAFETY 11 6 2 INSTALLATION METHOD 13 6 2 1 SCREW INSTALLATION 13 6 2 2 CLAMP INSTALLATION 14 6 2 3 SINGLE AXIS INSTALLATION 18 6 3 GROUNDING 19 6 4 ELECTRICAL INSTALLATION 20 6 4 1 SAFET...

Страница 4: ...manual Warning Otherwise the product may be damaged or the user s personal safety may be endangered Prohibition Otherwise the product may be damaged or the user s personal safety may be endangered 2...

Страница 5: ...em Do not artificially concentrate sunlight on the module Do not drop PV modules or allow objects to hit or fall directly on the modules Do not carry modules on your head Do not carry modules with rop...

Страница 6: ...is a risk of corrosion if the module is placed in a salt spray i e a marine environment or in an environment containing sulfur e g volcanoes etc In the place 50 500 m away from the sea stainless steel...

Страница 7: ...ing to the weight and size of the module Please adjust the position of the sling to keep the modules steady To ensure the safety of the module wooden sticks boards or other fixtures of the same width...

Страница 8: ...river it is recommended to drive backwards during the forklift and arrange for special supervision and command to prevent bumping into people or items causing personal injury or damage to the modules...

Страница 9: ...dary transport is not allowed for the monofacial modules that are packaged horizontally There is no stacking of pallets allowed for both vertical landscape and vertical portrait packages when transpor...

Страница 10: ...cm 5 UNPACKING INTRODUCTION 5 1 UNPACKING SAFETY Before unpacking please check the product type power bins serial number and relevant suggestions on the A4 paper of the packaging box and read the unpa...

Страница 11: ...ter of gravity and are prohibited from unpacking on non horizontal or soft grounds to avoid personal injury or even death If unpacking the vertical portrait packages on non horizontal ground anti tilt...

Страница 12: ...struction can be seen on the packing box 4 Cut the two packing belts on the short side of the pallet and cut the side carton in the vertical direction 5 Cut off the short side tape lift the cardboard...

Страница 13: ...e side cover 4 Take out the modules from one side 1 Remove the wrapping film and packing belts 2 Remove the top cover and sealing tape 3 Remove the carton box 4 Place the stand supporter from the glas...

Страница 14: ...s or connectors etc If any of such situation is found please contact Trina Solar customer service in time Before installation please keep modules electrical components clean and dry Connectors can cor...

Страница 15: ...nstallation During installation and wiring of PV modules please use opaque material to cover the PV module surface completely Installation work must be carried out by at least two persons Do not stand...

Страница 16: ...s and or the professional engineers For detailed information please follow local structural code or contact your professional structural engineer The modules shall be mounted on continuous rails that...

Страница 17: ...s modules with a number of clamps from different manufacturers it is recommended to use fixing bolt of at least M8 The clamp should have length of 50 mm 1 97 inch with thickness of 3 mm 0 12 inch The...

Страница 18: ...g rails run perpendicular to the long side frame Use 4 clamps on the long side Mounting rails run parallel to the long side frame DE09 DE09 05 DE09 08 A 250 350 mm Uplift load 4000 Pa Downforce load 6...

Страница 19: ...M 08 II A 0 200 mm Uplift load 1000 Pa Downforce load 1200 Pa DE18M II DE18M 08 II DEG18MC 20 II A 0 200 mm Uplift load 1000 Pa Downforce load 1300 Pa DEG18MC 20 II A 0 200 mm Uplift load 1000 Pa Down...

Страница 20: ...200 mm Uplift load 1800 Pa Downforce load 1800 Pa DE18M II DE18M 08 II A 250 450 mm B 100 250 mm Uplift load 1000 Pa Downforce load 1200 Pa DEG18MC 20 II A 250 450 mm B 100 250 mm Uplift load 1000 Pa...

Страница 21: ...roduced by different manufacturers please check Appendix A for details If the tracker is provided with a bumper and hold hoop they should be tightening together onto the torque using a hex driver Plea...

Страница 22: ...a Solar s modules The grounding device should be installed in accordance with the operating manual prescribed by the manufacturer Trina Solar recommends using grounding wires with resistances that are...

Страница 23: ...es installed in the system In order to ensure this the open circuit voltage of an array needs to be calculated at the lowest expected local ambient temperature which can be determined using the follow...

Страница 24: ...Otherwise during the operation of the modules this could lead to electric arc due to poor connections and can burn the connectors Before the commissioning and operation of the power station please che...

Страница 25: ...ot responsible for determining the minimum rating of fuse The fuse rated current should be chosen depending on different standards as follows 1 5 1 56 where Fuse rated current A Short circuit current...

Страница 26: ...rent losses Before cleaning make sure to wear PPE such as insulated protective gloves protective glasses hard hats safety insulated shoes etc When using scaffolding make sure that the scaffolding is i...

Страница 27: ...hen cleaning the back of the bifacial module avoid any sharp objects that may cause damage or penetrate the base material The other cleaning requirements are the same as the front side Cleaning activi...

Страница 28: ...ucted with non conductive materials to minimize risk of electric shock and that they are not abrasive to the glass or the aluminum frame If grease is present an environmentally friendly cleaning agent...

Страница 29: ...trinasolar com and one of our technical service representatives will contact you within 5 business days A username and password is required to send feedback from the customer service link For module s...

Страница 30: ...20 Array Technologies Inc DuraTrack HZ v3 400 mm purlin Uplift load 1600 Pa Downforce load 1600 Pa DEG18MC 20 II DEG19C 20 Array Technologies Inc DuraTrack HZ v3 600 mm purlin Uplift load 2400 Pa Down...

Страница 31: ......

Отзывы: