Installation instruction

14

8  CONCENTRIC FLUE SYSTEM

The concentric flue system is composed of an inner flue and 
an outer flue. These flues have been set up concentrically so 
the combustion gases will be discharged via the internal flue 
while the fresh combustion air is supplied via the gap between 
the inner and outer flues.

8.1  Components of the concentric 

flue system

Different connections are possible using the concentric flue 
system. These are:

Through the roof face and through the exterior wall

The pathway used for this system can be laid in different ways, 
but there are a few important conditions:

  The total allowed vertical flue length must not exceed 

9 metres (the sum of the flue length and calculation lengths 
for the bends).

  90° bends have a 2-metre horizontal calculation length.

  45° bends have a 1-metre horizontal calculation length.

  The outlet can be installed at any point on the roof face or 

exterior wall (supply and discharge in an identical pressure 
area), but must meet applicable regulations.

  Flue pathways must not be insulated.

 NOTE

Ensure the restriction plate is mounted in the correct 
manner, as indicated in these instructions.

The correct restriction plate will provide the unit with the 
most optimal efficiency, flame image and combustion.

Mounting an incorrectly placed restriction plate may cause 
malfunction of the unit.

8.2  Indirect/direct façade connection if 

applicable (See Chapter 8)

The outlet may also be installed above the exhaust in the 
wall, taking any hindrance to the surrounding area into 
consideration, in accordance with national, regional, local 
standards and regulations.

 NOTE

Ensure wind pressure on the outlet is not excessive, 
such as in locations with a balcony, flat roof, corners and 
very narrow alleys, etc., as this can negatively affect the 
performance of the unit. 

  Make a recess in the façade of around 155mm when 

using Ø100-150 flues (keep an extra space of 50mm in 
a refractory façade around the outer tube) and fit the façade 
pass-through with the wall plate on the inside of the wall. 
The wall plate of the exterior façade pass-through must be 
sealed sufficiently against the wall on the outside to avoid 
moisture and/or flue gas leaks leaking into the living space. 
We recommend our clearance box use as a direct façade 
pass-through through a refractory façade. 

  The flue should be encased if necessary. Even if the flue 

is to be installed along non-refractory materials, sufficient 
fire-resistant measures must be taken.

  Determine the position of the unit and outlet and begin 

construction of the flue with the connection on the 
unit, paying attention to the direction of installation and 
connecting the elements by means of clamp strips.

  The fitted pipe can be used between the bends or when 

connecting to the unit. If necessary, use wall brackets 
to support the flue.

Mounting using the roof pass-through option

  The flue outlet can be located at any random place on the 

roof face (supply and exhaust in identical pressure areas) 
and must meet the applicable rules and regulations.

  A roofing sheet for a flat roof or a roofing sheet lead for 

sloping tiled roofs can be used for a watertight duct. Use 
various bends for the slope, if required. The recess in the 
roof decking should be 5cm larger all around to ensure 
sufficient fire resistance.

  One needs to take into account the regulation regarding 

fire resistance between rooms (See national, regional, local 
standards and regulations). A casing of fireproof material 
(for example, 12mm Promatect fire-resistant plate) should 
be applied up to 25mm from the outer flue.

  Determine the position of the unit and the outlet and begin 

the construction of the flue with the connection on the unit 
(always 1 metre vertical first) pay attention to the direction 
of installation. The inner flue must be installed for draining 
purposes. Connect the elements using the clamping straps. 
Ensure all connections are gastight.

  A fitted pipe can be used between the bends or when 

making the connection to the unit and/or the roof pass-
through. Use 2 wall brackets to support the flue on each 
floor.

8.3  Installation instructions regarding 

existing flues (See Appendix 2)

Instructions

The flue gas exhaust system falls within category: C91 and 
must be built in accordance with national rules and regulations 
and the instructions of the manufacturer, as specified in the 
documentation and installation instructions.
This means, among other things, that the chimney pass-
through must not be smaller than 150mm round/square, 
but no larger than 200mm, and not ventilated by grilles, etc. 
In the case of larger chimney pass-throughs, a flexible hose of 
around 150 mm may possibly be used in combination with a 
flexible hose of around 100mm, as described below. For other 
situations, consult your supplier/manufacturer.

8.4 Parts

Check all parts for damage before commencing the 
installation. For the conversion of a brick flue to concentric 
flue, connected to CC flue system, you need the components 
described in Appendix 2.

Comment: The renovation/sanitation set consists of parts:
4. Interior mounting plate
5. Sliding element
8. Chimney mounting plate

Содержание 38 FS

Страница 1: ...INSTALLATION INSTRUCTION Trimline 38 FS 1071 GBR IRL...

Страница 2: ...9 5 INSTRUCTIONS FOR THE MERTIK MAXITROL GV60 10 6 GAS TECHNICAL SPECIFICATIONS 11 7 CONCENTRIC PATHWAYS 13 8 CONCENTRIC FLUE SYSTEM 14 8 1 Components of the concentric flue system 14 8 2 Indirect dir...

Страница 3: ...eeds to be placed a minimum distance of 50mm from the wall unless stated otherwise in these instructions WARNING Gas fires become hot when in use After installation of the unit the glass surface is co...

Страница 4: ...the lower part outwards Both the upper and lower covers can be removed These are attached with 4 hooks per cover Use the swivel legs to ensure the fireplace is level Adjust the height between the mant...

Страница 5: ...become damaged 1 upwards 2 outwards 3 down to remove Removing the side glass panes To remove the side glass panes for replacement the upper and lower covers must be removed The side glass panes are fi...

Страница 6: ...r 7 Concentric pathways contains a table that describes when a baffle plate and or a restriction must be put in place This is important to ensure the gas fire works correctly Before the lower cover is...

Страница 7: ...e chips around the burner bed on the ventilation grid ensure even distribution here as well 2 Then put the ceramic wooden blocks into place as shown in the photo 3 4 5 6 7 8 9 J K Handle the blocks ca...

Страница 8: ...4 6 8 5 7 9 11 10 B D E F G H C A Trimline 38 FS Installation instruction 8...

Страница 9: ...ition control type B6R R8P Wifi Ready Ignition Remote control and Piezo ignition Gas connection 3 8 External A Gas inlet B Gas burner outlet C Thermocouple connection D pilot light burner connection U...

Страница 10: ...ntenna wire and that they do not cross each other The high voltage released during ignition may damage the sensitive receiver circuit of the antenna This could mean the unit becomes less responsive or...

Страница 11: ...ow position kW 2 6 2 6 3 1 3 1 NOx Hi classe 5 5 5 5 Efficiency class NE613 2 2 2 2 Useful return NCV system For nominal heat output 79 80 80 80 For minimal heat output 76 5 76 77 77 Supplementary ele...

Страница 12: ...s NE613 2 2 Useful return NCV system For nominal heat output 79 79 For minimal heat output 72 6 72 6 Supplementary electricity consumption Nominal kWh 0 0 Stand by kWh 0 0 Energy efficiency Energy eff...

Страница 13: ...om 2 meter Roof pass through with 90 slope E 1 12 0 3 From 2 meter 90 bend calculation length 2 metres length including roof or exterior wall outlets Always adhere to a starting length of 1 metre Rati...

Страница 14: ...ant measures must be taken Determine the position of the unit and outlet and begin construction of the flue with the connection on the unit paying attention to the direction of installation and connec...

Страница 15: ...e to the chimney coping watertight on the roof 8 using silicone sealant and stainless steel screws Install the roof pass through 9 and secure it in place using the supplied clamping strip 10 The slide...

Страница 16: ...500 F Under a carport roof or balcony inside and outside corners 500 G From vertical ground pipes or drain pipes 300 H Inside and outside a corner 500 I Above an external gas pressure regulator 1000 S...

Страница 17: ...bustion air supply circuit 2 The seal of the pressure hatches at the top and bottom of the fireplace check the gasket 3 Check of the pressure hatches above and below 1 2 3 Can they open and close free...

Страница 18: ...end our thermoCet Cleaner Remove frame with glass pane See Paragraph 2 2 Preparation and placement on page 3 Important After the first use there will be a white haze on the inside of the glass pane th...

Страница 19: ...head Check distance is approximately 4mm 5 Pilot light difficult to ignite Gas supply pressure too high nervous flame Adjust gas supply pressure or adjust the pilot light pressure using the gas valve...

Страница 20: ...nings Check and clean with a vacuum cleaner or similar device Logs etc in wrong position Check and correct see instructions 11 Low main flame Gas supply pressure too low Check gas supply pressure and...

Страница 21: ...190 618 385 1193 314 100 150 500 183 446 Trimline 38 FS Installation instruction 21 Appendix 1 DIMENSIONAL DRAWINGS Trimline 38 FS Mantle Measurements in mm...

Страница 22: ...e Renovation package 7 Existing flue 9 Clamping strap 10 Roof pass through 1 Clamping strap 3 Clamping strap 4 Interior mounting plate Renovation package 5 Sliding element Renovation package 6 Flexibl...

Отзывы: