11
2. When using Capacitance function, discharge capacitor(s) before making any
measurements. Large value capacitors should be discharged through an appropriate
resistance load
DC
A Current function
Inputs are made through the test lead terminals COM/+.
Application notes:
The DC
A function is designed especially for HVAC/R flame sensor applications. The
0.1
A resolution is useful for identifying the minute current changes in flame detector
applications. Flame signal current check should indicate steady flame signal of at least
2
A for a rectification type, or 1.5
A for an ultraviolet type (8
A for self checking
systems). If a flame signal current with inadequate strength or fluctuation beyond 10%,
check the following to avoid the risk of unwanted flame relay dropout :
For gas or oil flames (Minipeeper):
Low supply voltage
Detector location
Defective detector wiring
Dirty viewing windows
Faulty Minipeeper
For oil flames (Photocell):
Detector location & wiring
Smoky flame or poorly adjusted air shutter
Faulty Photocell
Temperature over 165
o
F (74
o
C) at photocell
For gas flames (Flame Rod):
Ignition interference (A flame signal current difference with the ignition both on and
off greater than 0.5
A indicates the presence of ignition interference)
Insufficient ground (must be at least 4 times the detector area)
Flame lifting off burner head (ground), or not continuously in contact with the flame
rod
Temperature in excess of 600
o
F (316
o
C) at the flame electrode insulator causing
short to ground.