background image

www.tridonic.com

11

Subject to change without notice. Information provided without guarantee.

Data sheet 10/20-EM091-6

Emergency lighting units

EM converterLED

6.2 Status indication

System status is indicated by a bi-colour LED and by a DALI status flag.

LED indication

Status

Comment

Permanent green

System OK

AC mode

Fast flashing green
(0,1 sec on – 0,1 sec off)

Function test 

underway

Slow flashing green
(1 sec on – 1 sec off)

Duration test 

underway

Red LED on

Load failure

Open circuit / Short circuit / LED failure

Slow flashing red
(1 sec on – 1 sec off)

Battery failure

Battery failed the duration test or function 
test / Battery is defect or deep discharged/ 
Incorrect battery voltage

Fast flashing red
(0,1 sec on – 0,1 sec off)

Charging failure Incorrect charging current

Double pulsing green

Inhibit mode

Switching into inhibit mode via controller

Binary transmission of address 
via green/red LED

Address

identification

During address identification mode

Green and red off

DC mode

Battery operation (emergency mode)

6.3 Testing

DALI Control

A DALI command from a suitable control unit can be used to initiate func-
tion and duration tests at individually selected times. Status flags are set for 
report back and data logging of results.

When a DALI bus has not been connected or when a DALI bus is connected 
but the DALI default DELAY and INTERVAL times have not been re-set 
by sending appropriate DALI commands, then the EM converterLED PRO 
will conduct self-tests in accordance with the default times set within the 
EEPROM. 
These default times are factory pre-set, in accordance with the DALI stan-
dard EN 62386-202, to conduct an automatic function test every 7 days and 
a duration test every 52 weeks. Since the DELAY time is factory pre-set to 
Zero, all units are tested at the same time. Test times can be changed with a 
command over the DALI bus.

The  DELAY and INTERVAL time values must be re-set when the emergency 
system test times are to be scheduled by a DALI control and monitoring 
system.
Note that once the default values have been set to Zero, tests will only be 
conducted following a command from the control system. If the DALI bus is 
disconnected the EM converterLED PRO does not revert to self-testing 
mode.

Note: If the battery is connected the DALI communication is only possible 
after power reset.

Addressing

The EM converterLED PRO includes the EZ easy addressing system which 
allows addressing and identification by using the bi-colour LED. Binary 
address codes given by the LED can be simply converted to the DALI 
addresses 0 to 63. For single handed addressing using this method it is 
necessary to send a broadcast ident command every 3 to 9 seconds. During 
this command the LEDs will be switched off and the indication LED will flash 
the 6 bit binary address preceded by a 3 second start indication period.

5.4 LED Driver compatibility

The EM converterLED emergency unit use 3 pole technology and is compa-
tible with most LED Drivers on the market, however it is important to check 
that the rating of the LED Driver does not exceed the values specified below:

•  The max. allowed output current rating of the associated LED Driver is  

2.4 A peak (current rating of switching relays of EM converterLED)

•  The max. allowed inrush current rating of the associated LED Driver is  

60 A peak for 1 ms or 84 A for 255 μs (inrush current rating of switching 
relay of EM converterLED)

•  The max. allowed output voltage of the associated LED Driver applied to 

the EM converterLED output is 450V (voltage withstand between adja-
cent contact of the single switching relay of the EM converterLED)

•  The max. allowed LED load of the associated LED Driver is 150 W in  

operation. The load must be an LED module.

Check compatibility with the carried out function test (duration at least 5 
seconds) individually for each device.

6. Functions

6.1 Duration link selection

Emergency lighting LED Driver supplied with duration link in 3 hours positi-
on (position A).

The position of the link will only be read on first power up. If it is changed  
afterwards both the battery and mains supply must be disconnected for 10 
seconds to enable the EM converterLED to read the new link position on  
reconnection of the battery and mains. It will lead to a false battery failure  
indication if the link is changed after installation without this reset.

2 hr

3 hr

No duration link

Position A

Duration

Link position

1 hr

Position B

Содержание EM converterLED ST 202 MH/LiFePO4 50V

Страница 1: ...D module changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Addressing function patented EZ easy addressing Two colour status display LED Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by 3 pole connector Automatic detect...

Страница 2: ...0 pc s 1 600 pc s 0 07 kg Specific technical data Type Battery technology Rated duration Typ λ at 230 V 50 Hz Typ output power P emergency Mains current in charging operation Rated power in charging operation Initial charge Fast recharge Trickle charge2 Initial charge Fast recharge Trickle charge2 EM converterLED PRO 202 MH LiFePO4 50V NiMH 1 h 0 65C 1 5 W 15 mA 16 mA 15 11 mA 1 9 W 2 2 W 1 9 1 4 ...

Страница 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Страница 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Страница 5: ...ssociated battery In normal mains mode all LED modules are operated by the mains LED Driver Meaning of marking Double or reinforced insulation for built in electronic LED Drivers The control gear relies upon the luminaire enclosure for protection against accidental contact with live parts 2 Thermal details and life time 2 1 Life time Average life time 50 000 hours under rated conditions with a fai...

Страница 6: ...ED PRO with a standard LED LED Driver and one LED module for mains and emergency operation EM converterLED PRO with a standard LED LED Driver and series operation of LED modules Neutral P O Lout Lin N Dali Dali L L N EM ConverterLED PRO Neutral Dali Dali Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear Battery Battery LED Module Emerge...

Страница 7: ...itched Line Switched Line out Switched Line in One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4...

Страница 8: ...nducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the emc performance of the luminaire The length of LED leads to the LED module must not be exceeded...

Страница 9: ...M converterLED PRO MH LiFePO4 50V 90 130 130 130 180 260 260 260 10 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver i...

Страница 10: ...tery discharge current tolerance EM converterLED PRO 203 MH LiFePO4 50V Article number 89800628 NiMH battery 3 6 V battery voltage 890 960 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 770 830 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 204 MH LiFePO4 50V Article number 89800629 NiMH battery 4 8 V battery vol...

Страница 11: ...mand from the control system If the DALI bus is disconnected the EM converterLED PRO does not revert to self testing mode Note If the battery is connected the DALI communication is only possible after power reset Addressing The EM converterLED PRO includes the EZ easy addressing system which allows addressing and identification by using the bi colour LED Binary address codes given by the LED can b...

Страница 12: ...nitiate a 5 seconds function test press 200 ms T 1 s Execute function test as long as switch pressed press 1 s Reset selftest timer adjust local timing press 10 s Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is activated the discharging of the battery will be minimized by switching off the LED output If the Inhibit Mode ...

Страница 13: ...B CON 28002319 side by side 4 x 1 Accu LiFePO44B CON 28002323 side by side 5 x 1 Accu LiFePO45B CON 28002326 EM converterLED PRO 1 2 3 h NiMH Type EM converterLED PRO 202 MH LiFePO4 50V EM converterLED PRO 203 MH LiFePO4 50V EM converterLED PRO 204 MH LiFePO4 50V Article no 89800627 89800628 89800629 Duration 1 h 2 3 h 1 h 2 3 h 1 h 2 3 h Battery charge time Initial charge 20 h Fast recharge 10 h ...

Страница 14: ...n life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number discharge cycles 50 cycles total Max storage time 12 months at 5 C to 25 C Only use Tridonic batteries Comply with UN 38 3 and IEC 62133 safety testing protected against over charge over discharge charging at excessive temperatures short circuit and over c...

Страница 15: ...arameters provide information about the mains battery LED output and emergency operation The BlackBox can be read out with the masterCONFIGURATOR and deviceANALYSER In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no b...

Отзывы: