background image

www.tridonic.com

5

Subject to change without notice. Information provided without guarantee.

Data sheet 10/20-EM091-6

Emergency lighting units

EM converterLED

1. Standards

•  EN 61347-1
•  EN 61347-2-13
•  EN 61347-2-7
•  EN 55015
•  EN 61000-3-2
•  EN 61000-3-3
•  EN 61547
•  EN 60068-2-64
•  EN 60068-2-29
•  EN 60068-2-30
•  EN 62384
•  DALI standard EN 62386-202
•  according to EN 50172
•  according to EN 60598-2-22
•  according to EN 62034

1.1 Glow-wire test

according to EN 61347-1 with increased temperature of 850 °C passed.

1.2 Insulation and electric strength testing of luminaires

Electronic LED-Drivers can be damaged by high voltage. This has to be consid-
ered during the routine testing of the luminaires in production.

According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, 
each luminaire should be submitted to an insulation test with 500 V

DC

 for 1 sec-

ond. This test voltage should be connected between the interconnected phase 
and neutral terminals and the earth terminal. The insulation resistance must be 
at least 2 MΩ.

As an alternative, IEC 60598-1 Annex Q describes a test of the electrical 
strength with 1,500 V

AC

 (or 1,414 x 1,500 V

DC

). To avoid damage to the electronic 

devices this test 

must not be conducted

.

3. Installation / Wiring

3.1 Wiring diagram

One or more LED modules with a total forward voltage of 10 to 54 V can be 
connected to the EM converterLED. These LED module(s), marked with “Emer-
gency” are operated in emergency mode from the associated battery. In normal 
mains mode all LED modules are operated by the mains LED Driver.

Meaning of marking 
Double or reinforced insulation for built-in electronic LED Drivers. The control 
gear relies upon the luminaire enclosure for protection against accidental contact 
with live parts.

2. Thermal details and life-time

2.1 Life-time

Average life-time 50,000 hours under rated conditions with a failure rate of 
less than 10 %. Average failure rate of 0.2 % per 1000 operating hours.

Expected life-time with LiFePO

4

 batteries

EM converterLED PRO 202 
MH/LiFePO4 50V

tc

65 °C

70 °C

75 °C

80 °C

life-time

> 100,000 h > 100,000 h > 100,000 h > 79,000 h

EM converterLED PRO 203 
MH/LiFePO4 50V

tc

65 °C

70 °C

75 °C

80 °C

life-time

> 100,000 h > 100,000 h > 100,000 h > 78,000 h

EM converterLED PRO 204 
MH/LiFePO4 50V

tc

65 °C

70 °C

75 °C

80 °C

life-time

> 100,000 h > 100,000 h > 100,000 h > 78,000 h

The emergency lighting LED Driver is designed for a life-time stated above 
under reference conditions and with a failure probability of less than 10 %.

The relation of tc to ta temperature depends also on the luminaire design. 
If the measured tc temperature is approx. 5 K below tc max., ta tempera-
ture should be checked and eventually critical components (e.g. ELCAP) 
measured. Detailed information on request.

Expected life-time with NiMH batteries
EM converterLED PRO 202 
MH/LiFePO4 50V

tc

65 °C

70 °C

75 °C

80 °C

life-time

> 100,000 h > 100,000 h > 100,000 h 73,000 h

EM converterLED PRO 203 
MH/LiFePO4 50V

tc

65 °C

70 °C

75 °C

80 °C

life-time

> 100,000 h > 100,000 h 99,000 h

70,000 h

EM converterLED PRO 204 
MH/LiFePO4 50V

tc

65 °C

70 °C

75 °C

80 °C

life-time

> 100,000 h > 100,000 h 96,000 h

68,000 h

Содержание EM converterLED ST 202 MH/LiFePO4 50V

Страница 1: ...D module changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Addressing function patented EZ easy addressing Two colour status display LED Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by 3 pole connector Automatic detect...

Страница 2: ...0 pc s 1 600 pc s 0 07 kg Specific technical data Type Battery technology Rated duration Typ λ at 230 V 50 Hz Typ output power P emergency Mains current in charging operation Rated power in charging operation Initial charge Fast recharge Trickle charge2 Initial charge Fast recharge Trickle charge2 EM converterLED PRO 202 MH LiFePO4 50V NiMH 1 h 0 65C 1 5 W 15 mA 16 mA 15 11 mA 1 9 W 2 2 W 1 9 1 4 ...

Страница 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Страница 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Страница 5: ...ssociated battery In normal mains mode all LED modules are operated by the mains LED Driver Meaning of marking Double or reinforced insulation for built in electronic LED Drivers The control gear relies upon the luminaire enclosure for protection against accidental contact with live parts 2 Thermal details and life time 2 1 Life time Average life time 50 000 hours under rated conditions with a fai...

Страница 6: ...ED PRO with a standard LED LED Driver and one LED module for mains and emergency operation EM converterLED PRO with a standard LED LED Driver and series operation of LED modules Neutral P O Lout Lin N Dali Dali L L N EM ConverterLED PRO Neutral Dali Dali Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear Battery Battery LED Module Emerge...

Страница 7: ...itched Line Switched Line out Switched Line in One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4...

Страница 8: ...nducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the emc performance of the luminaire The length of LED leads to the LED module must not be exceeded...

Страница 9: ...M converterLED PRO MH LiFePO4 50V 90 130 130 130 180 260 260 260 10 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver i...

Страница 10: ...tery discharge current tolerance EM converterLED PRO 203 MH LiFePO4 50V Article number 89800628 NiMH battery 3 6 V battery voltage 890 960 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 770 830 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 204 MH LiFePO4 50V Article number 89800629 NiMH battery 4 8 V battery vol...

Страница 11: ...mand from the control system If the DALI bus is disconnected the EM converterLED PRO does not revert to self testing mode Note If the battery is connected the DALI communication is only possible after power reset Addressing The EM converterLED PRO includes the EZ easy addressing system which allows addressing and identification by using the bi colour LED Binary address codes given by the LED can b...

Страница 12: ...nitiate a 5 seconds function test press 200 ms T 1 s Execute function test as long as switch pressed press 1 s Reset selftest timer adjust local timing press 10 s Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is activated the discharging of the battery will be minimized by switching off the LED output If the Inhibit Mode ...

Страница 13: ...B CON 28002319 side by side 4 x 1 Accu LiFePO44B CON 28002323 side by side 5 x 1 Accu LiFePO45B CON 28002326 EM converterLED PRO 1 2 3 h NiMH Type EM converterLED PRO 202 MH LiFePO4 50V EM converterLED PRO 203 MH LiFePO4 50V EM converterLED PRO 204 MH LiFePO4 50V Article no 89800627 89800628 89800629 Duration 1 h 2 3 h 1 h 2 3 h 1 h 2 3 h Battery charge time Initial charge 20 h Fast recharge 10 h ...

Страница 14: ...n life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number discharge cycles 50 cycles total Max storage time 12 months at 5 C to 25 C Only use Tridonic batteries Comply with UN 38 3 and IEC 62133 safety testing protected against over charge over discharge charging at excessive temperatures short circuit and over c...

Страница 15: ...arameters provide information about the mains battery LED output and emergency operation The BlackBox can be read out with the masterCONFIGURATOR and deviceANALYSER In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no b...

Отзывы: