Data sheet 11/20-EM098-7
Emergency lighting units
EM converterLED
EM converterLED SELFTEST with a standard LED Driver and parallel operation of LED modules
Neutral
+
+
–
–
+
–
–
+
P
O
L
N
Test
switch
Indicator
LED
Control gear
LED
LED
Control gear
Battery
Battery
LED Module
Emergency
–
+
–
+
LED Module
–
+
LED Module
LED control gear
max. 150 W in operation
Switched Line in
L
out
L
in
N
Rest
Rest
L
Neutral
Rest mode control
Rest mode control
Un-Switched Line
Switched Line out
EM ConverterLED
SELFTEST
One LED module is operated in emergency mode.
All LED modules are operated in mains mode.
8 – 9 mm
wire preparation:
0.5 – 1.5 mm²
3.2 Wiring type and cross section
Solid wire with a cross section of 0.5 – 1.5 mm². Strip 8 – 9 mm of insulation
from the cables to ensure perfect operation of terminals.
3.4 Wiring guidelines
• The output to the LED is DC but has high frequency content, which should be
considered for good EMC compliance.
• LED leads should be separated from the mains and DALI connections and
wiring for good EMC performance.
• Maximum lead length on the LED terminals is 3 m. For a good EMC
performance keep the LED wiring as short as possible.
• The secondary wires (LED module) should be routed in parallel to ensure
good EMC performance.
3.5 Maximum lead length
LED
3 m
1
Status indication LED 1 m
Batteries
0.8 m
1
Note: The length of LED leads to the LED module must not be exceeded. Note that the length
of the EM converterLED leads is added to the length of the leads from the LED Driver to the EM
converterLED module when considering max. permitted lead length of the LED Driver. Leads
should always be kept as short as possible.
• Maximum lead length for the Test switch and Indicator LED connection is 1 m.
The test switch and Indicator LED wiring should be separated from the LED
leads to prevent noise coupling.
• Battery leads are specified with 0.5 mm cross section and a length of 0.8 m
• DALI terminals are mains proof
• To avoid the damage of the control gear, the wiring must be protected against
short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.)
To ensure that a luminaire containing LED emergency units complies with EN
55015 for radio frequency conducted interference in both normal and emergency
mode it is essential to follow good practice in the wiring layout.
Within the luminaire the switched and unswitched 50 Hz supply wiring must be
routed as short as possible and be kept as far away as possible from the LED
leads.Through wiring may affect the emc performance of the luminaire.
The length of LED leads to the LED module must not be exceeded. Note that
the length of the EM converterLED leads to the LED module is added to the
length of the leads from the LED Driver to the EM converterLED module when
considering the max. permitted lead length of the LED Driver.
3.3 Loose wiring
Loosen wire through twisting
and pulling or using a Ø 1 mm
release tool