Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
FMS-1655L PROGRAMMING
Basic Programming
-
34
-
The brightness of the FMS-1655L main
display screen may also be adjusted using the
Set Brightness
option on the
Display Setup
menu. All brightness settings are stored to
non-volatile memory and remain in effect
through a power cycle.
When configured for single sensor mode, the
main display screen may be customized using
options on the
Display Setup
menus. The
Display Options
menu option allows specific
information to be individually suppressed by
deselecting the unwanted items from the
Set
Display Options
selection screen. Dual sensor
models do not have configurable display
settings, other than the brightness of the
Safety Halo
TM
settings.
Built-in Diagnostics
The FMS-1655L incorporates several
diagnostic tools (see Figure 8) including
an
About This FMS
option, an
Override
option, a
Real-Time View
feature, and an
option to perform a
Factory Restore
of the
FMS-1655L. The
About This FMS
option on
the
Diagnostics
menu provides information
specific to this particular unit, including
the firmware versions and electronic serial
number of the display module, the Neuron ID
associated with the controller module, as well
as its network address.
During the test and balance phase, it is often
convenient to be able to adjust exhaust
damper actuators to a specific position to
force a specific airflow condition.
The analog outputs may be individually
overridden by selecting the
Overrides
option
from the
Diagnostics
menu, the
Analog
Outputs
option, and then selecting the specific
analog output to be overridden.
The user can then, in real-time, dynamically
move the damper actuator to a specific
position using the slider on the override
screen.
While in override mode, the selected analog
output is disconnected from its PID control
loop, if configured for PID mode. Canceling
override mode effectively resumes the PID or
direct analog output control.
The FMS-1655L incorporates a convenient
feature that allows the installer to view the
real-time conditions of all of the hardware
resources as well as several system
variables. These include the analog inputs,
analog outputs and digital inputs. Selecting
the
Real-Time View
option from the
Diagnostics
menu allows the user to view
the real-time conditions of any of the listed
resources.
For example, selecting the
Analog Inputs
option from the
Real-Time View
menu invokes
the real-time view configuration screen. To
skip to the next set of resources to view, tap
the
Next
button. To cancel the real-time view
display at any time, tap the
Exit
button to
return to the
Real-Time View
menu.
To reset all of the modifiable configuration
parameters of the FMS-1655L to their original
default settings, the
Factory Restore
option on
the
Diagnostics
menu may be selected.
Selecting this option invokes a warning
message informing the user that all existing
configuration settings will be erased and
replaced with the factory-configured default
settings. The user is then prompted for a
password before proceeding to completely
reset all configuration settings to their factory
default values.
Figure 8. Built-in diagnostics
FMS-1655L
Triatek reserves the right to change product specifications without notice.