Pre-Installation Items
2
SECTION I - Pre-Installation Items
General Requirements
Installation of the vent/air system must comply with
local codes and requirements and with the National
Fuel Gas Code NFPA 54, ANSI Z223.1 for installa-
tions in the U.S. For Installations in Canada, the
installation must comply with CSA B149.1 or
B149.2.
The vent/air system must be fully constructed using
ONLY the Prestige Concentric Vent/Air System
components from Triangle Tube. Do not mix other
vent components or joining methods from other
manufacturers.
Do not mix vent components or joining meth-
ods from any other vent manufacturer with
Triangle Tube’s Prestige Concentric Vent/Air
System. Failure to comply with this require-
ment could cause vent failure resulting in
leakage of flue products into the living space
of the building.
WARNING
Do not connect more than a single boiler into the
vent/air system.
All penetrations of the vent/air system through ceil-
ings, floors or walls must be properly fire stopped.
Check with local codes and requirements regarding
fire stops and vent penetrations.
The vent/air system must not penetrate or be routed
through any active vent system or chimney.
Vent/Air System Kit Components
Prior to installation of the vent/air system check to
ensure all parts required for the completion of the
system are present. See Figure 1 for complete
breakdown of concentric vent/air system kit parts
and Fig. 3, page 3 for optional components.
Termination Assembly
Elbow
Locking Band
Vent/Air Adapter
Support Plate
Fig. 1: Concentric Vent/Air System Kit Components - PSVKIT03
Note:
Mounting Hardware Not Shown