Preliminary Instructions

1. Verify that the heat exchanger kit is correct for

the model of boiler. See table on page 1.

2. Turn off power to the unit at the main service

panel and allow the unit to cool.

ELECTRICAL SHOCK HAZARD!

Ensure power to the boiler has been switched  off

prior to servicing the unit.

3. Remove the front jacket panel of the boiler by

removing the thumbscrew located on the upper

edge of the unit.  Lift the panel up and pull for-

ward to remove the front panel from the unit.

4. Using a voltmeter verify there is no electrical

power to the boiler by checking for power on

the boiler’s power supply terminals L and N

5. Shut off gas supply to the inlet of the unit at the

external main manual shutoff valve.

6. Close  external  system  isolation  valves  to  the

boiler supply and return piping and on the sys-

tem make up / fill piping.

7. Attach  a  hose  to  external  boiler  drain.  Place

other end of this hose to a suitable drain.

8. Open  external  boiler  drain  valve  and  begin

draining the boiler.

To assist in the draining of the boiler, remove the

air  vent  at  the  top  of  the  unit  or  manually  lift

open the pressure relief valve.

Removal of Venting Connection

1. Use a flat head screw driver to loosen the banding

clamp located on the vent outlet adapter.  (Fig. 2).  

2.  Remove vent piping from  vent outlet adapter as

the internal flue tube / vent outlet adapter must be

removed.

3.    Disconnect  the  yellow  wire  leads/Molex  plug

from  the  flue  temperature  sensor    (shown  as

Item 1 in Fig. 1). The flue temperature sensor

may be located in the vent pipe or the conden-

sate  pan  depending  on  the  model.    Use  care

when  disconnecting  the  wire  leads  as  not  to

damage the sensor terminals or the wire leads.

Before disconnecting any wire connections mark and

label all connections and location of the connections.

NOTICE

WARNING

NOTICE

PRESTIGE Excellence

HX Field Replacement

Kit 

2

4

5

3

2

1

Fig. 1: Prestige Excellence

Содержание PRESTIGE Excellence PSRKIT01

Страница 1: ...1 PSRKIT01 Heat Exchanger Assembly X 1 PTRKIT124 Heat Exchanger Assembly X 1 PSRKIT76 Heat Exchanger Assembly X 1 PTRKIT125 Heat Exchanger Assembly X Indicates a potentially hazardous situation which...

Страница 2: ...Attach a hose to external boiler drain Place other end of this hose to a suitable drain 8 Open external boiler drain valve and begin draining the boiler To assist in the draining of the boiler remove...

Страница 3: ...d from the boiler it should be inspected for deformation damage or corrosion If there are any signs of deformation damage or corrosion on the vent outlet adapter replace it immediately Check condition...

Страница 4: ...ated at the top of the heat exchanger 10 Disconnect the blue wire leads from return tem perature sensor Shown as item 4 in Fig 1 located at the bottom of the heat exchanger 11 Disconnect the orange wi...

Страница 5: ...hillips Torx head screw driver provided in the kit and remove the blower gas valve venturi Gas valve and ven turi assembly can remain connected to the blower housing Discard old blower gasket Fig 5 Re...

Страница 6: ...avoid vertical motion of the heat exchanger during transport and is not required to be installed with the replacement heat exchanger 2 Lift the heat exchanger about 4 to 6 to disen gage from the rear...

Страница 7: ...ly connection of the new heat exchanger Use a new boiler piping gasket provided in the kit between heat exchanger and supply pipe Tighten the brass union nut ensuring a leak tight seal Use care when t...

Страница 8: ...le Connect the condensate drain assembly to the retaining nut and tighten Ensure the condensate drain assembly contains the plastic seated ball Do not install the conden sate drain assembly if the bal...

Страница 9: ...and the gasket is reseated in the adapter Failure to comply could result in leakage of flue prod ucts into the surrounding area resulting in death or personal injury Installation of Polypropylene Vent...

Страница 10: ...erature sensor wires of the boiler wiring harness using the included Wire Taps Follow the Harness Adapter instructions above then plug the Harness Adapter into the supply tem perature sensor 4 Reconne...

Страница 11: ...8 Connect ignition cable to the TriMax control module and install rear control box cover 9 Install the air intake pipe back on the venturi air inlet connection Make sure the ignition cable is secured...

Страница 12: ...ents must be performed with calibrated equip ment to ensure proper readings and accuracy Failure to perform a complete combustion test at both high and low input rates may result in incom plete combus...

Страница 13: ...enter the access code 3 Press the RIGHT button to highlight the Manual Operation icon then press the OK button 4 Press the OK button while the FAN icon is highlighted to manually fire the burner and...

Страница 14: ...the plastic OFFSET SCREW see Fig 14 using a T 40 Torx wrench as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire 1 firing rate O2 increases and CO2 decreases Clockwise adjustment of OF...

Отзывы: