TriangleTube PRESTIGE Excellence PSRKIT01 Скачать руководство пользователя страница 13

PRESTIGE Excellence

HX Field Replacement

Kit 

13

The  control  panel  will  display  a  L  followed  by

the current boiler temperature when placed into

low fire test mode.

4.  If the CO2 combustion level  during low fire is

not /- 0.2 of the combustion level mea-

sured at high fire, remove the offset cover screw

and adjust the plastic OFFSET SCREW (see Fig

14) using a T-40 Torx wrench as follows:

Counter-clockwise  adjustment  of  the  OFFSET

SCREW at Low Fire:

O2 increases and CO2 decreases

Clockwise adjustment of the OFFSET SCREW

at Low Fire:

O2 decreases and CO2 increases

TriMax Control Procedure

1. Press the round INSTALLER button. See Fig.

15.

2.  Enter the installer access code “054” by using the

LEFT

and 

RIGHT

buttons to select a digit and

the 

UP

and 

DOWN

buttons to change the digit.

Press the 

OK

button to enter the access code.

3. Press  the 

RIGHT

button  to  highlight  the

Manual Operation icon

then press the 

OK

button.

4.  Press  the

OK

button  while  the  FAN  icon  is

highlighted  to  manually  fire  the  burner  and

power the CH circulator.

An adequate CH load must be present to dis-

sipate the heat generated during the combus-

tion test.  If an adequate CH load is not avail-

able, an indirect water heater can be used to

dissipate  the  heat  by  creating  a  DHW  call

which will enable the DHW circulator.

5.  Press the 

RIGHT

button to adjust the firing rate

to 100% (high fire).  Hold down the  

RIGHT

button to rapidly increase the firing rate.

6. If  the  combustion  levels  during  high  fire  are

outside  the  recommended  combustion  settings

adjust  the THROTTLE  SCREW  (see  Fig.  14)

using a flat-blade screwdriver as follows:

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

NOTICE

NOTICE

Installer
Button

Fig. 15: Trimax Navigation Buttons

Manual Operation

Released

Off

Off

Off

CH

CH1

FAN

DHW

SYS

CH2

Throttle

Screw

Offset Pressure

Cover Screw

Fig. 14: Combustion Adjustment - Prestige Burner

Содержание PRESTIGE Excellence PSRKIT01

Страница 1: ...1 PSRKIT01 Heat Exchanger Assembly X 1 PTRKIT124 Heat Exchanger Assembly X 1 PSRKIT76 Heat Exchanger Assembly X 1 PTRKIT125 Heat Exchanger Assembly X Indicates a potentially hazardous situation which...

Страница 2: ...Attach a hose to external boiler drain Place other end of this hose to a suitable drain 8 Open external boiler drain valve and begin draining the boiler To assist in the draining of the boiler remove...

Страница 3: ...d from the boiler it should be inspected for deformation damage or corrosion If there are any signs of deformation damage or corrosion on the vent outlet adapter replace it immediately Check condition...

Страница 4: ...ated at the top of the heat exchanger 10 Disconnect the blue wire leads from return tem perature sensor Shown as item 4 in Fig 1 located at the bottom of the heat exchanger 11 Disconnect the orange wi...

Страница 5: ...hillips Torx head screw driver provided in the kit and remove the blower gas valve venturi Gas valve and ven turi assembly can remain connected to the blower housing Discard old blower gasket Fig 5 Re...

Страница 6: ...avoid vertical motion of the heat exchanger during transport and is not required to be installed with the replacement heat exchanger 2 Lift the heat exchanger about 4 to 6 to disen gage from the rear...

Страница 7: ...ly connection of the new heat exchanger Use a new boiler piping gasket provided in the kit between heat exchanger and supply pipe Tighten the brass union nut ensuring a leak tight seal Use care when t...

Страница 8: ...le Connect the condensate drain assembly to the retaining nut and tighten Ensure the condensate drain assembly contains the plastic seated ball Do not install the conden sate drain assembly if the bal...

Страница 9: ...and the gasket is reseated in the adapter Failure to comply could result in leakage of flue prod ucts into the surrounding area resulting in death or personal injury Installation of Polypropylene Vent...

Страница 10: ...erature sensor wires of the boiler wiring harness using the included Wire Taps Follow the Harness Adapter instructions above then plug the Harness Adapter into the supply tem perature sensor 4 Reconne...

Страница 11: ...8 Connect ignition cable to the TriMax control module and install rear control box cover 9 Install the air intake pipe back on the venturi air inlet connection Make sure the ignition cable is secured...

Страница 12: ...ents must be performed with calibrated equip ment to ensure proper readings and accuracy Failure to perform a complete combustion test at both high and low input rates may result in incom plete combus...

Страница 13: ...enter the access code 3 Press the RIGHT button to highlight the Manual Operation icon then press the OK button 4 Press the OK button while the FAN icon is highlighted to manually fire the burner and...

Страница 14: ...the plastic OFFSET SCREW see Fig 14 using a T 40 Torx wrench as follows Counter clockwise adjustment of OFFSET SCREW at Low Fire 1 firing rate O2 increases and CO2 decreases Clockwise adjustment of OF...

Отзывы: