Program Access of  the MCBA Control

PROGRAM ACCESS OF THE MCBA 
CONTROL

The factory default setting for the PRESTIGE Control
Module  to  operate  the  IDWH  is  through  an  aquastat
control.  The PRESTIGE Control Module must be pro-
grammed as described in the following instruction to
correctly operate the IDWH through the IDWH sensor. 

To  adjust  the  factory  parameter  settings  of  the  PRES-
TIGE  MCBA  Control,  the  installer  must  enter  into  the
parameter menu of the control.

Do not attempt to revise any other control parameter
settings  except  those  listed  in  this  supplement.
Perform only those parameter revisions described in
this  supplement.    Failure  to  comply  could  result  in
erratic  or  unreliable  operation  of  the  PRESTIGE
resulting  in  severe  personal  injury,  death  or  sub-
stantial property damage.

For  additional  information  on  revising  the  PRES-
TIGE  MCBA  Control  Module  operational  parameter
settings, 

reference 

the 

PRESTIGE 

Control

Supplement.

ACTIVATING THE ACCESS CODE

To enter the parameter listing of the MCBA control, the
installer must enter the activation code as follows:

1.  Press and hold the MODE button

2. Continue holding the MODE and press STEP button

until 

STBY

appears and hold both STEP and MODE

buttons for 2 to 3 seconds.

The display should read 

CODE

3.  Release the STEP and MODE buttons on the control

panel.

4.  Press STEP once.

NOTICE

WARNING

NOTICE

The display should read 

C_

XX

(XX should be

a random number from 00 to 99)

5.  Press the + or - button to change the display num-

ber 

C_

XX

to read 

C_54

.  Press and release the +

or  -  to  change  the  display  one  number  at  a  time.
Press and hold the + or - to rapidly change the dis-
play number.

6.  When  the  display  reads 

C_54

press  STORE  to

save the activation code.  The display 

C_54

should

flash when the code is entered and saved.

After the activation code is entered press the MODE but-

ton  until  the  display  shows 

PARA

.    At  this  point  the

installer can access the parameters required for applica-
tion.

Once in the parameter mode, press the STEP repeated-
ly to reach the appropriate parameter setting.  The dis-
play should show the following sequence, as the STEP
button is press repeatedly:

Press STEP once- 

1140

Press STEP x2 - 

2_01

Press STEP x3 - 

3_01

Press STEP x4 - 

4186

Press STEP x5 - 

P_10

Press STEP x6 - 

P_11 

Etc......

After Parameter 4 the display will continue to show P fol-
lowed  by  a  two-digit  number  that  increases  with  each
press of the STEP button.

The  actual  parameter  values  displayed  on  the
unit may vary depending on the application.  The
parameter  sequence  will  always  occur  in  the
order shown.

NOTICE

10

Содержание MiniSmart

Страница 1: ...he guidelines within this manual can result in severe per sonal injury death or substantial property damage When receiving the Mini SMART unit any claims for damage or shortage in ship ment must be filed immediately against the transportation company by the con signee NOTICE Instantaneous Water Heater Prestige Series 3 Boiler Supplement Smart Mini Product Information Application Installation Maint...

Страница 2: ...al Expansion 6 Thermostatic Mixing Valve 6 Domestic Piping Diagram 7 BOILER PIPING INSTALLATION General Requirements 8 Boiler Piping Diagram 8 IDWH SENSOR INSTALLATION WIRING IDWH Sensor Installation 9 Wiring IDWH Sensor to PRESTIGE Boiler 9 PROGRAM ACCESS OF THE MCBA CONTROL Program Access of the MCBA Control 10 Activating the Access Code 10 11 To Change a Parameter Setting 11 IDWH SENSOR PARAMET...

Страница 3: ...Table of Contents ii OPTIONAL AQUASTAT INSTALLATION Optional Aquastat Installation Various Boilers 18 Optional Aquastat Wiring Various Boilers 18 PRODUCT SPECIFICATIONS Product Specifications 19 ...

Страница 4: ...inor injury or substantial property damage Indicates special instructions on installation opera tion or maintenance which are important to the equipment but not related to personal injury hazards Indicates recommendations made by Triangle Tube for the installers which will help to ensure optimum operation and longevity of the equipment BEST PRACTICES NOTICE CAUTION WARNING DANGER DEFINITIONS Trian...

Страница 5: ...t installation or from the use of components or fittings not specified by Triangle Tube NOTICE NOTICE NOTICE WARNING HOT WATER CAN SCALD Water temperatures over 125 F can cause severe burns instantly or death from scalding Children disable and elderly are at highest risk of being scald Never leave them unattended in or near show er bathtub or sink Never allow small children to use a hot water fauc...

Страница 6: ...8 NOTICE CODE COMPLIANCE This product must be installed in accordance with the instructions in this manual and where applicable With all local state provincial and national codes laws regulations and ordinances Where recommendations in this manual differ from local or national codes the local or national codes take prece dence CODE RESTRICTIONS The Mini SMART contains a single wall heat exchanger ...

Страница 7: ...ng 5 16 wall anchors DO NOT mount or attempt to mount the water heater to hollow sheet rock or lathe walls using wall anchors Only install the water heater to wall studs solid walls or equivalent wood structure CAUTION NOTICE MOUNTING INSTALLATION STUD WALLS 1 Locate a wall stud in the general location of the water heater placement 2 Place the water heater mounting bracket against the wall centeri...

Страница 8: ...and drill the required diameter and depth hole for the wall anchors position in the center of each mark 4 Mount the anchors flush or slightly recessed in the drilled holes with threaded side of anchor inside the wall 5 Mount the bracket onto the water heater using the provided mounting bolts Ensure the mounting bolts are fully tightened and the bracket is securely fas tened to the water heater See...

Страница 9: ...ity of the discharge Should terminate with a plain end not threaded The material of the piping should have a serv iceable temperature rating of 250 F or greater Should not be subject to conditions where freez ing could occur CAUTION Should not contain any shut off valves or obstructions No shut off valve should be piped between the water heater and the relief valve Failure to comply with the guide...

Страница 10: ...ion valve 2 Backflow preventer or pressure reducing valve May be required by code 3 Thermal expansion tank optional 4 Pressure relief valve 150 psi 5 Mixing valve 6 Check valve 3 2 5 6 1 4 1 Cold Cold Hot Mix Fig 3 Mini Smart Domestic Piping ...

Страница 11: ...cal boiler piping dia gram Reference the PRESTIGE Boiler Installation Manual for additional information and require ments regarding boiler piping If antifreeze is used in the boiler system local codes may require a backflow preventer on the domestic cold water supply piping Use antifreeze specifically intend ed for hydronic heating systems Inhibited propylene glycol is recommended at a maximum 50 ...

Страница 12: ... secure with the thumb screw 7 Restore power to the PRESTIGE boiler IDWH SENSOR INSTALLATION Install the IDWH Sensor provided with water heater into the bottom coupling of the water heater as shown in Fig 5 Ensure the IDWH Sensor is tight and leak free WIRING IDWH SENSOR TO PRESTIGE BOILER ELECTRICAL SHOCk HAZARD Turn power off to the PRESTIGE boiler before proceeding with instal lation of the con...

Страница 13: ...appears and hold both STEP and MODE buttons for 2 to 3 seconds The display should read CODE 3 Release the STEP and MODE buttons on the control panel 4 Press STEP once NOTICE WARNING NOTICE The display should read C_XX XX should be a random number from 00 to 99 5 Press the or button to change the display num ber C_XX to read C_54 Press and release the or to change the display one number at a time P...

Страница 14: ... matically store the setting after 15 minutes Ensure all parameters settings are either factory default or revised based on the application Review all parameters settings on page 16 when completed and prior to commission of the boiler Failure to comply could result in erratic or unre liable operation of the PRESTIGE boiler WARNING Once a parameter setting value has been revised and stored if the S...

Страница 15: ...r has been stored and accepted in the control module change the display readout to Parameter mode by pressing MODE until the display shows PARA 2 Press STEP to enter the first parameter setting Continue pressing STEP until the display shows P_46 By pressing STEP you will sequence through the parameter settings as follows 1140 2_01 3_01 4186 P_10 P_11 P_12 P_46 The display readout will continue sho...

Страница 16: ...s P_21 This parameter setting is the DHW Set Value Addition parameter After releasing the STEP button the dis play will show the current setting NOTICE IDWH Sensor Parameters 13 Parameter 46 has several other possible settings available The factory setting of the IWH is aquastat control or _13 The required revised setting of the IWH sensor control or _12 Any other setting of parameter 46 could res...

Страница 17: ...tilize a anti scald thermostatic mix ing valve on the hot water outlet of the water heater Failure to comply could result in severe personal injury death or substantial property damage DANGER NOTICE NOTICE IDWH Sensor Parameters 14 To revise the parameter setting within the PRESTIGE Control Module for DHW Detention ON control the installer must activate the access code for the control module as pr...

Страница 18: ...s correctly set for 12 and is stored properly Once the condition is corrected the errors will automati cally reset and the PRESTIGE will return to normal oper ation The Detection OFF setting of Parameter 39 greatly affects the production of domestic hot water A max imum setting of Parameter 39 could result in an excessive domestic water temperature resulting in a potential scald hazard It is stron...

Страница 19: ...Prestige Parameter Information PRESTIGE FACTORY SETTINGS FOR PARAMETERS 16 ...

Страница 20: ...ind the first position flashes to indicate that the boiler is in INFO mode The ignition counters and burner hours are split into three two digit numbers For example Write the numbers down from left to right to arrive at 123 456 CH ignitions In the INFO Mode a temperature reading of 22 typically indicates an open circuit A temperature reading of 240 typically indi cates a short circuit NFO I NOTICE...

Страница 21: ...IONAL AQUASTAT INSTALLATION VARIOUS BOILERS In lieu of the factory supplied sensor the installer may opt to use an aquastat for this type of application the fol lowing parts must be supplied by the installer Honeywell L4008A1130 or equivalent 1 2 NPT X 3 Long Drywell Honeywell 12137A or equivalent The aquastat used in this application must have a maximum setting of 200ºF Failure to comply can resu...

Страница 22: ... 2 10 6 1 4 4 1 4 Wall Surface 1 2 NPT Domestic hot 3 4 NPSC Boiler Supply 1 2 NPT Domestic Cold Typ 1 4 1 4 2 9 1 4 OD 18 Boiler Supply Domestic Boiler Return Front View Bottom View Top View NOTE 1 Domestic capacity is based on an intermittent draw with 50ºF inlet temperature and 120ºF outlet tempera ture ...

Страница 23: ...el construction Available in 8 sizes and 2 models Limited LIFETIME residential warranty 15 year limited commercial warranty Self cleaning self descaling design Freeway Center 1 Triangle Lane Blackwood NJ 08012 Tel 856 228 8881 Fax 856 228 3584 E mail Sales triangletube com For domestic water snow melting radiant floor refrigeration Plates made of stainless steel with a 99 9 copper and brazed ensur...

Отзывы: