TriangleTube Instinct FSB Скачать руководство пользователя страница 7

7

Instinct FSB (Floor Standing Boiler) 

HMI (Human Machine Interface) Removal

Table 1:  Controls Settings 

HEATING SETTING

FACTORY DEFAULT

MINIMUM SETTING

MAXIMUM SETTING

EXISTING SETTING

Heating Operation

Enabled

Demand Type

Thermostat & Outd. 

Curve

Absolute Max CH Setpoint

185°F [85°C]

68°F [20°C]

188°F [87°C]

CH1 Maximum Setpoint

180°F [82°C]

68°F [20°C]

188°F [87°C]

CH1 Minimum Setpoint

80°F [27°C]

60°F [15°C]

188°F [87°C]

Outdoor Curve Coldest Day

10°F [-12°C]

-30°F [-34°C]

50°F [10°C]

Outdoor Curve Warmest Day

64°F [18°C]

60°F [15°C]

78°F [25°C]

CH2 Circuit

Enabled

CH2 Maximum Setpoint

140°F [60°C]

68°F [20°C]

194°F [90°C]

CH2 Minimum Setpoint

80°F [27°C]

60°F [15°C]

190°F [88°C]

Warm Weather Shutdown

Off

Off

78°F [25°C]

Circulation Pump 

Permanent

Disabled

CH Post Pump Time

5 Minutes

Off

20 Minutes

Freeze Protection

Enabled

Frost Protection Setpoint

-22°F [-30°C]

-22°F [-30°C]

50°F [10°C]

Parallel Shift Value

0°F [0°C]

0°F [0°C]

144°F [80°C]

CH Call Blocking

2 Minutes

0 Minutes

30 Minutes

DOMESTIC SETTING

SOLO 

FACTORY 

DEFAULT

COMBI 

FACTORY 

DEFAULT

MINIMUM 

SETTING

MAXIMUM 

SETTING

EXISTING 

SETTING

DHW Operation

Enabled

Enabled

Demand Type

Thermostat

N/A

DHW Boiler Setpoint

168°F [76°C]

168°F [76°C]

96°F [35°C]

188°F [87°C]

DHW Setpoint

140°F [60°C]

140°F [60°C]

68°F [20°C]

168F [75°C]

DHW Warmstart Setpoint

N/A

125°F [52°C]

86°F [30°C]

140°F [60°C]

DHW Warmstart Hysteresis

N/A

30°F [17K]

9K

36K

DHW On Differential

6°F [3°C]

N/A

4°F [2°C]

18°F [10°C]

DHW Storage Adder

27°F [15°C]

18°F [10°C]

10°F [5°C]

54°F [30°C]

DHW Post Pump Time

2 Minutes

2 Minutes

Off

30 Minutes

DHW Priority Timeout

Off

Off

Off

120 Minutes

DHW Priority

Enabled

Enabled

DHW Call Blocking

1 Minute

1 Minute

0 Minute

30 Minutes

DHW to CH Call Blocking

1 Minute

1 Minute

0 Minute

30 Minutes

Antilegionella Function

Disabled

Enabled

Содержание Instinct FSB

Страница 1: ...ool before pro ceeding to avoid possible electrical shock and scald hazard Failure to do so can cause severe personal injury or death WARNING Failure to follow instructions below can result in severe...

Страница 2: ...dule s Use Table 1 to record the existing settings Do not revise any settings when recording settings 1 To access the Installer screen touching simultane ously the up and down soft keys for 3 seconds...

Страница 3: ...Enabled Switch 186 F 140 F 6 F 46 F Fig 7 DHW Settings 9 Press the DOWN button to highlight the Boiler Settings icon if present icon then press the OK button 10 Press the UP and DOWN buttons to scroll...

Страница 4: ...screws 1 Locate and undo the 2 M6 access screws Fig 8 Access Screws 2 Raise the HMI Pod 3 Disconnect the high and low voltage connectors Fig 9 High and Low Voltage Connectors 4 Rotate the HMI Pod down...

Страница 5: ...2 Remove the Wi Fi Module 21 and remove the 8 way harness from the aperture Keep the harness plugged into the Wi Fi Module 21 Reset Power Fig 13 8 way harness 5 Fitting Wi Fi Module on replacement HMI...

Страница 6: ...pliance Setting 3 The required code is written on the data plate located at the side of the boiler Use the code for the gas type either Natural Gas or Propane 4 Increase decrease the value from 0 to 9...

Страница 7: ...reeze Protection Enabled Frost Protection Setpoint 22 F 30 C 22 F 30 C 50 F 10 C Parallel Shift Value 0 F 0 C 0 F 0 C 144 F 80 C CH Call Blocking 2 Minutes 0 Minutes 30 Minutes DOMESTIC SETTING SOLO F...

Страница 8: ...dbus Address 0 BCST 0 BCST 247 Flex Relay 1 CH CH1 Flex Relay 2 DHW DHW Flex Relay 3 P3 CH1 CH2 DHW Flex Relay 4 ERR ERROR Flex Relay 5 Flame FLAME Flex Relay 6 P4 CH2 Error Relay On Lockout Blocking...

Отзывы: