6
Instinct FSB (Floor Standing Boiler)
HMI (Human Machine Interface) Removal
7. Programming new Display Board
1. Follow the instructions in step 2 to gain access to
the installer menu.
2. Go to boiler settings and click appliance setting, as
seen in Fig. 14 and Fig. 15.
CH & DHW Settings
Boiler Settings
Fig. 14: Installer Menu
Boiler Settings
Modbus Address
Pump settings
Ignition Level
Mix zone high limit
WP diff trigger
Appliance setting
0=BCST
3500rpm
114ºF
0pcsi
Fig. 15: Appliance Setting
3. The required code is written on the data plate
located at the side of the boiler. Use the code for
the gas type, either Natural Gas or Propane.
4. Increase/decrease the value (from 0 to 9, then A
to Z) using the UP or DOWN keys to, then change
position with the LEFT or RIGHT keys.
5. Follow the instructions on the screen to enter the
appliance code for your boiler.
6. The boiler will now be factory set for that particular
model. Return to step 2 and enter settings recorded
in Table 1 back into the controls to return the boiler
to the customized settings of the old control.
7. Return to step 2 and enter settings recorded in
Table 1 back into the controls.