Instinct FSB (Floor Standing Boiler) 

HMI (Human Machine Interface) Removal

7.  Programming new Display Board

1.  Follow the instructions in step 2 to gain access to 

the installer menu.

2.  Go to boiler settings and click appliance setting, as 

seen in Fig. 14 and Fig. 15.

CH & DHW Settings

Boiler Settings

Fig. 14:  Installer Menu

Boiler Settings

Modbus Address

Pump settings

Ignition Level

Mix zone high limit

WP diff trigger

Appliance setting

0=BCST

3500rpm

114ºF

0pcsi

Fig. 15:  Appliance Setting

3.  The required code is written on the data plate 

located at the side of the boiler. Use the code for 

the gas type, either Natural Gas or Propane.

4.  Increase/decrease the value (from 0 to 9, then A 

to Z) using the UP or DOWN keys to, then change 

position with the LEFT or RIGHT keys.

5.  Follow the instructions on the screen to enter the 

appliance code for your boiler.

6.  The boiler will now be factory set for that particular 

model. Return to step 2 and enter settings recorded 

in Table 1 back into the controls to return the boiler 

to the customized settings of the old control.

7.  Return to step 2 and enter settings recorded in 

Table 1 back into the controls.

Содержание Instinct FSB

Страница 1: ...ool before pro ceeding to avoid possible electrical shock and scald hazard Failure to do so can cause severe personal injury or death WARNING Failure to follow instructions below can result in severe...

Страница 2: ...dule s Use Table 1 to record the existing settings Do not revise any settings when recording settings 1 To access the Installer screen touching simultane ously the up and down soft keys for 3 seconds...

Страница 3: ...Enabled Switch 186 F 140 F 6 F 46 F Fig 7 DHW Settings 9 Press the DOWN button to highlight the Boiler Settings icon if present icon then press the OK button 10 Press the UP and DOWN buttons to scroll...

Страница 4: ...screws 1 Locate and undo the 2 M6 access screws Fig 8 Access Screws 2 Raise the HMI Pod 3 Disconnect the high and low voltage connectors Fig 9 High and Low Voltage Connectors 4 Rotate the HMI Pod down...

Страница 5: ...2 Remove the Wi Fi Module 21 and remove the 8 way harness from the aperture Keep the harness plugged into the Wi Fi Module 21 Reset Power Fig 13 8 way harness 5 Fitting Wi Fi Module on replacement HMI...

Страница 6: ...pliance Setting 3 The required code is written on the data plate located at the side of the boiler Use the code for the gas type either Natural Gas or Propane 4 Increase decrease the value from 0 to 9...

Страница 7: ...reeze Protection Enabled Frost Protection Setpoint 22 F 30 C 22 F 30 C 50 F 10 C Parallel Shift Value 0 F 0 C 0 F 0 C 144 F 80 C CH Call Blocking 2 Minutes 0 Minutes 30 Minutes DOMESTIC SETTING SOLO F...

Страница 8: ...dbus Address 0 BCST 0 BCST 247 Flex Relay 1 CH CH1 Flex Relay 2 DHW DHW Flex Relay 3 P3 CH1 CH2 DHW Flex Relay 4 ERR ERROR Flex Relay 5 Flame FLAME Flex Relay 6 P4 CH2 Error Relay On Lockout Blocking...

Отзывы: