Burner Input
Standard
Standard
Overfire
Air Box
Breech
Head
F-Model
No. 2 Oil
Burner Model
Combustion
Draft
Setting
Draft
Setting
GPH
Control
F-25
0.70
EZ-1
60200-02
+0.035
0.65
+0.01
.60/.65
F-30
0.85
EZ-1
60200-02
+0.05
0.85
+0.02
.60/.65
F-35
1.00
EZ-1
60200-02
+0.07
1.20
+0.02
.85/1.00
Oil Burner Nozzle Data
Nozzle/
F-Model
Primary Nozzle
Alternate Nozzle
Pump
Suntec
Gear
Size
Angle
Type
Size
Angle
Type
Pressure
3450 RPM
Capacity
GPH
GPH
PSIG
GPH
F-25
0.60
60
A-Delavan
0.60
60
SS-Hago
150
A2VA73006
3/17
F-30
0.65
60
W-Delavan
0.65
60
B-Hago
150
A2VA73006
3/17
F-35
0.85
70
B-Delavan
0.85
60
W-Delvan
150
A2VA73006
3/17
•
Oil ratings based on No. 2 fuel oil with heating value of 140,000 Btu per gallon.
•
CCT combustion safety control uses a cadmium sulfide cell flame detector to monitor oil flame, pro-
vides interrupted direct spark ignition of oil flame and manual lock-out switch.
•
Setting shown are for initial start-up. Final settings should be determined after combustion readings.
•
Combustion Air Box is factory installed and preset to the recommended air setting.
Carlin EZ-1 Model with Air Box
Description
EZ-1
Insertion Depth (air tube to flange)
2 5/8"
Air Tube Pitch
3º
Motor Size - HP/RPM
1/7 HP 3450 RPM
Power Supply
120/60/1
Motor Amps
2.7A
Control Type
Interrupted Ignition
30 sec. Pre-purge
8