Delta ELITE Combination Heater
Oil-Fired Direct Vent Instructions
Indicates the presence of a hazardous situation
which, if ignored, will result in death, serious
injury or substantial property damage.
Indicates the presence of a hazardous situa-
tion which, if ignored, can result in death, seri-
ous injury or substantial property damage.
Failure to follow information below can
result in severe personal injury, death or
substantial property damage:
• Instructions are for use only by a quali-
fied installer/service technician.
• Read all instructions before proceeding.
• Follow instructions in proper order.
• These instructions apply to the installa-
tion of the F-25 or F-30/35 and Triangle
Tube’s Oil Fired Vent Kit.
• Refer to the Delta ELITE Installation
manual for additional information.
WARNING
WARNING
DANGER
Location of the Delta ELITE Combination Heater
Give special attention to location of the
Combination Heater vent to avoid possibility of
severe personal injury, death or substantial
property damage.
•
Locate the unit utilizing the shortest vent pipe
length and most direct path to an outside wall.
• Flue gases will form a white plume in colder
climates which may obstruct a favorite window
view.
•
Prevailing winds could cause freezing of con-
densate and water/ice build-up may occur on
building, plants or roof.
Location of the Vent Termination
•
Locate or guard the vent termination in a manner
to prevent accidental contact by people or pets.
•
Vent must terminate at least 4 feet below and 4
feet horizontally or 1 feet above from any win-
dow, door or gravity air inlet to the building.
•
Vent must terminate not less than 7 feet above
grade when located adjacent to a public sidewalk.
•
Terminate the vent at least 6 feet from adjacent
walls.
•
The bottom of the vent terminal shall be located
at least 1 foot above the grade, including the
normal snowline.
•
DO NOT terminate vent into window well,
stairwell, alcove, courtyard or other recess area.
•
DO NOT terminate vent above any window,
door or gravity air inlet Condensate can freeze
causing ice formations.
Venting Restrictions
•
Maintain 1-inch minimum clearance from com-
bustibles to the vent pipe.
•
Maximum allowable wall thickness for the vent
termination is 14 inches.
•
Maximum allowable vent length is 20 feet.
Vent kits are available in 10 and 20 foot lengths.
•
DO NOT splice lengths of vent pipe together.
To avoid personal injury or substantial property
damage, do not splice lengths of vent pipe, do not
drill or penetrate the vent pipe and do not use
any vent pipe which has been crushed.
DANGER
WARNING
1
2004-11 HMF D. Vent Instr.
2/23/04