Trianco TRISTAR OPTIMA JUNIOR K CB Скачать руководство пользователя страница 5

5

This booklet, along with the accompanying user
manual, should be kept by the householder and
should always stay with the boiler, even when the
appliance is transferred to another system.

Please read these instructions carefully, as they
provide important directions for the safe installation,
use and maintenance of the appliance.

Any use of the boiler not sanctioned by these
instructions is strictly prohibited and will invalidate the
guarantee.

Installation, commissioning and servicing of the boiler
must only be carried out by a CORGI-trained and
registered engineer.

Any person(s) who carries out other remedial work,
e.g. electrical fault-finding, must have suitable
engineering qualifications.

The appliance contains no asbestos or other
substances which contravene the COSHH
Regulations (Control of Substances Hazardous to
Health Regulations, 1988).

Flue systems must not be modified in any way other
than as described in the installation manual.

Do not store or use any combustible materials close
to, or within the appliance.

In the case of structural work or maintenance close to
the pipework, flue system, appliance or accessories,
switch off the boiler prior to the commencement of
such work. Only reactivate the boiler once these have
been thoroughly checked by suitably-qualified
personnel.

The appliance must be serviced annually by a
CORGI-registered engineer, unless the requirements
of the installation demand more frequent service.

Do not obstruct the clean air supply to the boiler, or
the flue terminal.

When installing the appliance, do not mount it on
chairs, ladders, stools or any other unstable surface.

To clean the appliance casing, switch off the boiler
and isolate the power supply. Wipe with a damp cloth.
Do not use detergents, harsh liquids, or other toxic
products.

Before operating the appliance, please ensure that all
gas and water supply valves are open, and that the
system has been correctly filled with water.

The system must be flushed of all deposits before
filling.

Installation is the purchaser’s responsibility.

Any repair should be carried out using original spares.
Failure to do so may invalidate the guarantee and
jeopardise the safety of the boiler. Trianco is not held
liable for the malfunction of any of these components

It is forbidden to climb on the appliance.

Always turn off the gas cock before carrying out any
work on components which carry gas.

If you smell gas:

-

 

do not operate any electrical appliances

-

 

extinguish any fires

-

 

close the main gas valve upstream of the meter

-

 

open all windows and doors to ventilate the room

-

 

telephone the gas company

If you smell combustion fumes from the boiler:

-

 

switch off the boiler

-

 

open all windows and doors to ventilate the room

-

 

call your local authorised engineer

Before carrying out any work on the

boiler, always switch off the power to

the appliance at the mains isolation

.

This appliance is in accordance with the applicable
requirements of the Gas Appliance Directive, Boiler
Efficiency Directive, Electromagnetic Compatibility
Directive, and the Low Voltage Directive.

PIN

CE 0694 BM 3593

Category UK

II

2H 3P

Appliance Type

C

13

, C

83

, B

23

, B

33

The boiler carton should include:

-

 

Boiler

-

 

Pipework connection manifold

-

 

Wall mounting bracket and templates

-

 

Instruction/guarantee pack

-

 

Bag of screws/fixings

-

 

Diverter valve connection (SB model only)

-

 

External controls connection (SB model only)

1

WARNINGS & SAFETY ADVICE

1.1 E.C. DECLARATION OF CONFORMITY

1.2 CONTENTS OF PACK

Содержание TRISTAR OPTIMA JUNIOR K CB

Страница 1: ...TRISTAR OPTIMA JUNIOR K CB AND SB WALL MOUNTED GAS BOILERS INSTALLATION INSTRUCTIONS TO BE RETAINED BY HOUSEHOLDER CB MODEL G C No 47 897 06 SB MODEL G C No 41 898 39...

Страница 2: ...2...

Страница 3: ...ge 23 6 5 High Level Flue Kit Components page 23 6 6 Vertical Flue Kit Components page 23 6 7 90 Concentric Bend Components page 24 6 8 45 Concentric Bend Components page 24 6 9 500mm Pipe Components...

Страница 4: ...4...

Страница 5: ...ean the appliance casing switch off the boiler and isolate the power supply Wipe with a damp cloth Do not use detergents harsh liquids or other toxic products Before operating the appliance please ens...

Страница 6: ...erfere with the normal operation of the boiler without the written permission of Trianco Ltd could invalidate the appliance guarantee and infringe the Gas Safety Installation and Use Regulations Wall...

Страница 7: ...7 2 TECHNICAL SPECIFICATION...

Страница 8: ...ting Flow _ B Domestic Hot Water CB only _ C Gas Inlet _ D Domestic Cold Water Inlet _ E Heating Return _ F Flue Pipe Collar 60 100mm H Wall Mounting Holes 8mm L Condensate Trap Pipe 2 1 BOILER DIMENS...

Страница 9: ...9 2 2 WALL MOUNTING TEMPLATE FIG 2...

Страница 10: ...Sensor 15 Bypass 16 Secondary Heat Exchanger 17 Gas Valve 18 Filling Valve 19 Domestic Water Pressure Switch 20 Drain Tap 21 Pump 22 Automatic Air Valve 23 Three way Valve 24 Expansion Vessel 25 Cond...

Страница 11: ...witch 17 Three way Valve 18 Bypass 19 Pump 20 Expansion Vessel 21 Primary Heat Exchanger 22 Burner 23 Overheat Thermostat 24 Ignition Transformer 25 Ionisation Probe 26 Automatic Air Valve A Heating F...

Страница 12: ...at the template is level mark and drill the holes required for mounting the wall plate pipework manifold connections and flue Mark and drill the holes required for the boiler mounting plate and insert...

Страница 13: ...operation 1 Remove screw A fig 8 2 Turn the rotator knob taking care not to apply excessive force 3 Replace screw A Check that the circulator is operating correctly and if necessary bleed of air by tu...

Страница 14: ...As external condensate pipe runs may be susceptible to freezing during very cold weather it is advisable to terminate the pipe into an internal waste system where possible If there is no alternative...

Страница 15: ...provided and the manifold as shown on fig 11 Connect the pipework to the manifold ensuring all joints are sealed correctly The correct pipework placement can be seen on fig 10 After the system fill ch...

Страница 16: ...behind the control panel 3 Lift the front door upwards and then forward to remove 4 Remove screws marked a on fig 15 from the combustion chamber cover and lift off 5 Remove screws marked b on fig 16 f...

Страница 17: ...ault the electrical system should be thoroughly checked for fuse failure short circuits incorrect polarity resistance to earth and earth continuity In the event of replacement use a cable with the sam...

Страница 18: ...control becomes inactive when the temperature is set via the cylinder thermostat System SB Model The boiler should be connected to a double channel programmer with volts free switching to give the opt...

Страница 19: ...19 5 4 Y PLAN WIRING 5 5 S PLAN WIRING CONNECTION PLUG SEE SECTION 5 2 PAGE 16 FOR DETAILS CONNECTION PLUG SEE SECTION 5 2 PAGE 16 FOR DETAILS FIG 22 FIG 23...

Страница 20: ...alve TA Room Thermostat TSI Installation Safety Thermostat TS High Limit Thermostat PM Low Pressure Switch NTC1 Outlet Probe NTC3 DHW Probe CB Model Only TB Boiler Thermostat FS DHW Flow Switch MV Fan...

Страница 21: ...ise stated always comply with the recommendations of the relevant codes of practice Keep clear of infra red security light sensors If the terminal discharges onto a path or passageway ensure that comb...

Страница 22: ...ly inclines slightly 2 up from the boiler to allow any condensation formed to run back to the appropriate drain 1 Having decided the position of the boiler accurately mark out the position of the fixi...

Страница 23: ...510033 Wall Seal 2 8 510026 500mm Concentric Flue Pipe 1 Item Part No Description Qty 1 510025 1000mm Concentric Flue Pipe 1 2 510027 60mm Seal Blue 1 3 510028 100mm Seal 1 Item Part No Description Q...

Страница 24: ...t No Description Qty 1 510023 90 Concentric Bend 1 2 510027 60mm Seal Blue 1 3 510028 100mm Seal 1 Item Part No Description Qty 1 510023 90 Concentric Bend 1 2 510027 60mm Seal Blue 1 3 510028 100mm S...

Страница 25: ...25 6 10 REAR OUTLET HORIZONTAL BALANCED FLUE SCHEMATIC 6 11 REAR OUTLET HIGH LEVEL HORIZONTAL BALANCED FLUE SCHEMATIC FIG 33 FIG 34...

Страница 26: ...26 6 12 R H SIDE OUTLET HORIZONTAL BALANCED FLUE SCHEMATIC 6 13 R H SIDE OUTLET HIGH LEVEL HORIZONTAL BALANCED FLUE SCHEMATIC FIG 35 FIG 36...

Страница 27: ...27 6 14 L H SIDE OUTLET HORIZONTAL BALANCED FLUE SCHEMATIC 6 15 L H SIDE OUTLET HIGH LEVEL HORIZONTAL BALANCED FLUE SCHEMATIC FIG 37 FIG 38...

Страница 28: ...28 6 16 VERTICAL BALANCED FLUE SCHEMATIC FIG 39...

Страница 29: ...750mm Do not include the first 90 elbow on the boiler when calculating the maximum permitted length on the horizontal flue this has already been taken into consideration See figs 40 41 for example co...

Страница 30: ...ED L boiler running LED M comfort function running LED P comfort function on off button R multifunction display S pressure gauge The display R will briefly display the temperature being set before ret...

Страница 31: ...display will show a 1 followed by the value this parameter is set at default 60 Repeatedly pressing the reset button will cycle through the available parameters to view and change The value of these...

Страница 32: ...32...

Страница 33: ...DE button E for 15 seconds Repeatedly pressing the reset button will cycle through the available parameters to view To exit from this function press the MODE button once more or leave the reset and bu...

Страница 34: ...as been returned to normal switch the boiler off then on using ON OFF button A If during normal operation the system pressure drops on a regular basis in most cases there will be a heating system faul...

Страница 35: ...he following table If the values are found to be inconsistent with these turn the gas valve regulator item B fig 44 in the appropriate direction Turning anti clockwise will increase the CO2 turning cl...

Страница 36: ...ttach the fan ensuring that gasket G is fitted correctly and has not been damaged by the dismantling process This must be replaced if damage has occurred Failure to do so will impair the correct opera...

Страница 37: ...ck the combustion analysis figures for the CO2 against those given in section 10 page 35 Check the gas and water systems for leaks On the combi CB model only check the hot water outlet temperature doe...

Страница 38: ...rush To prevent damage to the fan bearings do not use pressurised air while cleaning Take out nuts 7 and remove the combustion chamber inspection door Using a brush and vacuum cleaner remove all depos...

Страница 39: ...Room thermostat set too high Central heating temperature set too high Room thermostat programmer not calling for heat Faulty cylinder thermostat No power to boiler Room thermostat programmer incorrect...

Страница 40: ...tton A An attempt can also be made to reset the operation by holding reset button D for two seconds The boiler will perform a self diagnostic cycle and restart if the problem has been eliminated If th...

Страница 41: ...itted is the diverter valve power cable connection box Cut the plug from the cable which feeds from the control box and feed the cut end into the box Feed into the other end the cable from the diverte...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...44 Issue 1 Rev 0 July 2005 Item No 510062 LB 1480 01 09 2005...

Отзывы: