
29
When determining the flue length on non-typical flue courses, it is important to take into consideration that each
additional elbow added to the run will dectract from the overall permitted flue length.
A 90° elbow should be classed as reducing the length of the overall run by 1500mm.
A 45° elbow should be classed as reducing the length of the overall run by 750mm.
Do not include the first 90° elbow on the boiler when calculating the maximum permitted length on the horizontal
flue; this has already been taken into consideration. See
figs 40
&
41
for example configurations.
6.17
ALTERNATIVE FLUEING EXAMPLES
Example 1 (horizontal)
- Maximum permitted flue length: 4000mm
1 x additional 90° elbow: 1500mm
Maximum permitted length of A + B:
4000 minus 1500
=
2500mm
FIG. 40
FIG. 41
Example 2 (vertical)
- Maximum permitted flue length: 6000mm
2 x additional 45° elbows: 750mm each (1500mm)
Maximum permitted length of D + E:
6000 minus 1500
=
4500mm
Содержание TRISTAR OPTIMA JUNIOR K CB
Страница 2: ...2...
Страница 4: ...4...
Страница 7: ...7 2 TECHNICAL SPECIFICATION...
Страница 9: ...9 2 2 WALL MOUNTING TEMPLATE FIG 2...
Страница 28: ...28 6 16 VERTICAL BALANCED FLUE SCHEMATIC FIG 39...
Страница 32: ...32...
Страница 42: ...42...
Страница 43: ...43...
Страница 44: ...44 Issue 1 Rev 0 July 2005 Item No 510062 LB 1480 01 09 2005...