5. OIL SUPPLY

OIL

The burner is factory-set to burn 28 sec. Kerosene Class C2 to
BS 2869.

Trianco makes no guarantee as to the satisfactory operation of
the boiler using fuels other than that which is stated above.

STORAGE TANK

The tank should be fitted with weather-protected fill and vent
connections, a drain-off cock, and an oil level indicator.

Size and Location of Tank

The tank should be large enough to allow for economic
deliveries and be located in an unobtrusive position, having
regard to the need for safety, filling, maintenance, and head of
oil required (see 

figs 13, 14, 15

).

Steel Tanks

Steel tanks must comply with the requirements of BS 799 Part
5: 1987 and should be mounted on brick or block piers, with a
waterproof membrane fitted between the piers and tank.

Plastic Tanks

Polyethylene tanks may be used, having several advantages
over traditional steel tanks:

(a)  Pier supports are not required; the tank may be fitted

directly onto a flat surface.

(b)  They do not corrode; therefore never require repainting.

(c)  They are easier to handle because of lower weight.

(d)  They are generally supplied with a 10-year manufacturer’s

guarantee.

Fire Protection

Whilst it is highly unlikely that a fire could start from a domestic
oil tank, protection is required from a fire which may originate
elsewhere. The tank should be at least 1.8 metres from a
building and 750mm from a site boundary. Where it is not
feasible to adhere to these limits, the building wall must not
have any openings other than those for ventilation, the wall
must have at least a half-hour resistance to fire, and must
extend 1.8 metres from any part of the tank.

Alternatively, a non-combustible radiation barrier can be
employed, which meets all the requirements of BS 5410 Part 1.
This standard applies to tanks up to a capacity of 3,500 litres.

See current OFTEC regulations for further details.

To comply with Building Regulations, 

section J5:

1.  Where the tank is close to a dwelling, fire protection must

be provided to the eaves, if less than 1.8 metres from the
top of the tank.

2.  Cladding must extend at least 300mm beyond the tank.

3.  The tank must be fitted on a non-combustible base.

Pollution Protection

To comply with Building Regulations, 

section J6

, the tank

must be bunded (double-walled) if:

1.  The tank is less than 10m from a stream

2.  The tank is less than 50m from a well, spring, or other

source of drinking water.

3.  The tank cannot be viewed from the point of delivery.

4.  There is risk of oil reaching a manhole cover or drain in

the event of a leak.

5.  The tank capacity exceeds 2,500 litres.

SUPPLY

A long-life flexible oil hose is supplied with the boiler. A filter
and shut-off valve are also required. These should be fitted as
shown on 

figs 13, 14, 15

.

All oil line joints must be completely sealed and the total pipe
run should be flushed thoroughly before connection is made to
the burner. No soldered joints are permitted in the oil line.

Fire Valve

A remote-operated fire valve must be fitted in the oil supply
line, externally to the boiler, with the sensing phial located at a
point within the boiler casings, above the burner.

Single-Pipe Oil Supply (fig 14)

Where the lowermost part of the tank is above the level of the
burner, a single-pipe gravity system can be used. The oil
supply pipe should be connected to the suction port on the
burner pump via the flexible hose supplied.

When using the single-pipe system, it is important to convert
the fuel pump on the burner to operate as such: remove the
end cover and filter, then remove the bottom screw and insert
a ‘U’-shaped washer. Replace the screw, making sure it is fully
inserted. See the burner details leaflet for further information.

Two-Pipe Oil Supply (fig 15)

Where the lowermost part of the tank is below the level of the
burner, a two-pipe suction lift is necessary.

A spring-loaded non-return valve must be fitted in the suction
line to prevent the oil running back to the tank. No valves are
permitted in the return line. An additional flexible oil line will
also be required.

The oil pump is factory-set for use with a two-pipe system.

To comply with OFTEC regulations, a CD/10 form must

be completed and left with the appliance upon

installation.

Содержание Contractor WM70 HE INTERNAL

Страница 1: ...CENTRAL HEATING BOILER FOR BALANCED FLUE USER INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS To be retained by the householder Please read these instructions carefully before installing commission...

Страница 2: ...se disposable gloves face masks and eye protection After handling wash hands and other exposed parts When disposing reduce dust with water spray and ensure all parts are securely wrapped Glues Sealant...

Страница 3: ...ng and clearances System design Heating hot water systems Condensate Pipework 5 OIL SUPPLY Oil Storage tank Single pipe oil supply Two pipe oil supply Oil de aerators 6 ELECTRICAL SUPPLY Wiring diagra...

Страница 4: ...is switched off or the time switch programmer if fitted is set to the OFF position BOILER CONTROL THERMOSTAT The boiler control thermostat allows you to adjust the temperature of the water leaving th...

Страница 5: ...ner and potentially reducing the life of the pump After a delivery of oil it is recommended that it be allowed to settle in the tank for about half an hour before restarting the boiler Sludge and wate...

Страница 6: ...by the Trianco service centre TECHNICAL ASSISTANCE A team of trained technical advisors are available to discuss any problem with the appliance which may occur In many cases the problem may be solved...

Страница 7: ...igh level horizontal formats As a balanced flue boiler the Contractor WM70 HE is a room sealed appliance which conforms to the requirements specified in OFSA100 All flue types are suitable for install...

Страница 8: ...8 FIG 3 OUTLINE DIMENSIONS 3 TECHNICAL INFORMATION ALL DIMENSIONS IN mm FIG 4 PIPEWORK CONNECTIONS...

Страница 9: ...69 Class C2 Hot Water Thermostat Adjustable between 55 C and 80 C High Limit Thermostat Factory set at 110 C manual reset Casing Finish Stove enamel painted white Thermal Insulation Boiler shell and c...

Страница 10: ...amplify noise particularly if the wall construction is hollow or the surface tiled c A chimney passing through a bedroom will sometimes transmit noise d Low level flue terminals produce some exhaust n...

Страница 11: ...pon successful installation of the condensate pipework fill the trap via the fill point on the condensate unit pouring a small amount of water within until retained within the U section Examine the co...

Страница 12: ...e eaves if less than 1 8 metres from the top of the tank 2 Cladding must extend at least 300mm beyond the tank 3 The tank must be fitted on a non combustible base Pollution Protection To comply with B...

Страница 13: ...Oil Supply with De aerator fig 13 Where a two pipe suction lift is required but the return pipe requirement is too long or impractical to run an oil de aerator can be used The burner should be piped...

Страница 14: ...14 FIG 14 SINGLE PIPE SUPPLY...

Страница 15: ...15 FIG 15 TWO PIPE SUPPLY...

Страница 16: ...able is PVC sheathed flexible cord 0 75mm 24x0 2mm code designation H05 VV F or H05 VVH2 F as specified in table 16 of BD 6500 All cables entering the control box must be secured in position by the us...

Страница 17: ...all Drill 6mm holes where indicated and if using a horizontal balanced flue cut a hole 130mm diameter in the wall Remove the wall template and fix the two mounting brackets provided to the wall where...

Страница 18: ...nt or confined space see fig 19 The air opening should be positioned so as to cause the least possible draught to the occupants and located so it is not liable to be accidentally blocked British Code...

Страница 19: ...returns it as pre heated air to the burner to aid combustion Balanced flue condensing boilers are designed to operate at low noise levels INSTALLATION NOTES 1 At certain times during operation a plum...

Страница 20: ...re locating through the wall 6 Connect the hose from the burner to the socket on the internal air chute using the jubilee clip provided 7 Seal around terminal on the inside and outside wall with an ap...

Страница 21: ...HOLE REQUIRED 130mm DIAMETER THROUGH WALL TO TAKE TERMINAL IMPORTANT WHEN INSTALLING THE FLUE SYSTEM IT IS ESSENTIAL THAT THE FLUE INCLINES SLIGHTLY FROM THE BOILER THIS WILL ALLOW ANY CONDENSATION WH...

Страница 22: ...22 FIG 23 2355 2356 Horizontal Balanced Flue to be used in conjunction with 2357 High Level Adaptor Kit only...

Страница 23: ...23 FIG 24 2357 High Level Adaptor Kit used in conjunction with 2355 or 2356 Horizontal High Level Balanced Flue Kits only...

Страница 24: ...24 FIG 25 2357 HIGH LEVEL ADAPTOR KIT USED IN CONJUNCTION WITH 2355 AND 2356 FLUE KITS ONLY...

Страница 25: ...ntil the outer sections meet Use the remaining clamping strap to fasten these items securely together 7 Use the clip provided to secure the air hose from the burner to the connection on the air box as...

Страница 26: ...in the same manner Note both instances of item 7 can be discarded if they are not required Of the main flue sections only the use of items 8 is mandatory Fit these together in the manner described ab...

Страница 27: ...27 FIG 26 VERTICAL BALANCED FLUE KIT 2360...

Страница 28: ...Note X Shorter flue distances can be achieved by discarding these sections Longer flue distances can be achieved by purchasing additional sections of pipe see page 29 Permanent obstructions may be av...

Страница 29: ...to offset the vertical sections of flue on both the high level and vertical flue kits Ensuring all O ring seals are in position and well lubricated push the elbow and flue pipe firmly together fixing...

Страница 30: ...DING OVER After satisfactorily completing the boiler installation and commissioning a thorough check of the system should be made and the use of any boiler and system controls demonstrated to the end...

Страница 31: ...replace the nozzle 12 Using the diagram below replace the flue baffles in the correct arrangement Failure to ensure the correct placement of baffles will result in incorrect combustion reducing the ef...

Страница 32: ...ver 208331 1 16 Burner 2 224390 1 17 Flexible Oil Line 2 207019 2 18 Acoustic Hose 208388 1 19 Burner Mounting Flange 224392 1 20 Burner Mounting Gasket 224391 1 21 Condensate Pipework 224388 1 22 Ret...

Страница 33: ...Press red reset button under control panel and check function of boiler stat Ensure all controls are calling for heat Fit new fuse 5A If problem persists check for short circuit in wiring Check for ro...

Страница 34: ...nst settings shown in burner leaflet Raise tank or fir two pipe system Replace nozzle with one of same specification see burner leaflet Check pump pressure and adjust to settings shown in burner leafl...

Страница 35: ...35...

Страница 36: ...he drawings or illustrations contained within are vested in Trianco Heating Products and neither the brochure or any part thereof may be reproduced without prior written consent TRIANCO HEATING PRODUC...

Отзывы: