ELECTRICITY SAFETY - Before making any electrical checks, switch off mains supply to boiler.
FAULT POSSIBLE
CAUSE
ACTION
BURNER WILL NOT START
Control box locked out - Light on
Press reset button on front of burner.
N.B. ONLY TRY TWICE
Boiler over heat thermostat or
Ensure all controls are calling for heat and
other system controls satisfied
over heat thermostat reset.
Fuse blown
Fit new 5 amp fuse, if it blows again, check
for short circuit in wiring.
Check for live continuity up
If live supply confirmed, change control box
to burner
Motor or pump seized
Check for rotation and replace as
necessary.
BURNER STARTS
No oil supply
Check oil level in tank and feed to burner.
BUT FLAME NOT
ESTABLISHED
Photo-cell not seeing flame
Clean photo-cell and ensure it is fully plugged in.
Air trapped in pump
Bleed off air through pressure gauge tapping.
Solenoid valve faulty
Check coil for continuity and replace if faulty.
Nozzle blocked
Replace nozzle with one of same specification.
Electrodes incorrectly set
Reset gap and position electrodes as shown in Burner
diagram.
Electrode insulator cracked
Check and replace if insulator cracked or crazed.
Ignition transformer and H.T. contacts
Check for spark and condition of H.T. contacts.
faulty
Replace as necessary.
Low oil pressure
Check pump pressure and adjust to correct setting.
FLAME ESTABLISHED
Oil contaminated with water
Run off oil at burner until free of water and drain
BUT BURNER LOCKS
condensation from tank
OUT AFTER FEW SECONDS
Oil filter partially blocked
Wash filter clean with kerosene.
Photo-cell fault
Clean photo-cell and ensure it is fully plugged in.
Replace if faulty.
Oil pressure low
Check pump pressure and adjust to correct setting.