Alarm Status Menu

 ABR.

ON-BOARD 

DISPLAY

DASHBOARD DISPLAY

FULL NAME

DESCRIPTION

PSA

PSA

PRESSURE SENSOR

Pressure Sensor Alarm

Suction pressure sensor is shorted, open or pressure out of range

SSA

SSA

SUCTION TEMP SENSOR

Suction Sensor Alarm

Suction temperature sensor is shorted or open

ASA

ASA

AIR TEMP SENSOR

Air Sensor Alarm

Return air temperature sensor is shorted or open

CSA

CSA

COIL TEMP SENSOR

Coil Sensor Alarm

Coil temperature sensor is shorted or open

HSH

HSH

HIGH SUPERHEAT

High Superheat Alarm

Superheat above upper limit

LSH

LSH

LOW SUPERHEAT

Low Superheat Alarm

Superheat below lower limit

HtA

HtA

HIGH AIR TEMP

High Temperature Alarm

Room temperature is above ROOM TEMP  + AIR TEMP DIFF + HIGH TEMP 

ALARM OFFSET  for longer than HIGH TEMP ALARM DELAY

LtA

LtA

LOW AIR TEMP

Low Temperature Alarm

Room temperature is below ROOM TEMP - LOW TEMP ALARM OFFSET for 

longer than LOW TEMP ALARM DELAY

EdF

EdF

EXCESS DEFROST

Excess Defrost Alarm

32 defrosts or more within 48 hours

dtt

dtt

DEFR TERM ON TIME

Defr Term on Time Alarm

Defrost terminated on time instead of temperature for two consecutive cycles

dor

dor

DOOR SWITCH

Door Open Alarm

If door is open and room temperature is 5 degrees above ROOM TEMP + AIR 

TEMP DIFF for DOOR ALARM DELAY time

CoA

CoA

COMMUNICATION ERROR

Communication Error

ONLY FOR BONDED CONTROLLERS: No communication between controllers 

for one minute or more

EA1

EA1

EXTERNAL ALARM 1

External Alarm 1

If AU1 IN MODE =  EXT ALARM: The digital input is in an active state

EA2

EA2

EXTERNAL ALARM 2

External Alarm 2

If AU2 IN MODE =  EXT ALARM: The digital input is in an active state

EA3

EA3

EXTERNAL ALARM 3

External Alarm 3

If AU3 IN MODE =  EXT ALARM: The digital input is in an active state

EFL

EFL

EMAIL FAILURE

Email Failure Alarm

Email alert was not confirmed by email server provided after seven consecu

-

tive attempts

A1A

A1A

AUX1 SENSOR

AU1 Temp sensors Alarm

AU1 temperature sensor is shorted or open

A2A

a2a

AUX2 SENSOR

AU2 Temp sensors Alarm

AU2 temperature sensor is shorted or open

A3A

a3a

AUX3 SENSOR

AU3 Temp sensors Alarm

AU3 temperature sensor is shorted or open

Pdt

Pdt

PUMPDOWN TIMEOUT

Pump Down Timeout

Max time for LPCO pumpdown exceeded

SCC

SCC

SHORT COMP CYCLE

Short Compressor Cycle

Compressor is started an excessive number of times to maintain suction pressure

LPA

LPA

LOW PRESSURE

Low Pressure Alarm

Suction pressure dropped below expected point excessive number of times

PrF

PrF

N/A

Process Failure

Basic Display is not communicating to the controller

Variables Menu   

Use the

and

arrows to move through the available options.

ABR.

ON-BOARD 

DISPLAY

DASHBOARD 

DISPLAY

 FULL NAME 

me

DESCRIPTION 

ription

rtP

rtP

ROOM TEMP

Room Temp

Room Temperature as measured by controller

CLt

CLt

COIL TEMP

Coil Temp

Coil Temperature as measured by controller

SYS

SYS

SYSTEM MODE

System Mode

Current operating status

SHt

SHt

SUPERHEAT

Superheat

Superheat as calculated by the controller

PrS

PrS

SUCTION PRESSURE

Suction Pressure

Suction Pressure as measured by controller

SUt

SUt

T1 SUCTION TEMP

Suction Temp

Suction Temperature as measured by controller

SAt

SAt

SATURATION TEMP

Saturation Temp

Saturation Temperature as calculated by control-

ler

oPn

oPn

VALVE % OPEN

Valve% Open

Percentage EEV is open

Cor

Cor

COMPRESSOR RELAY

Compressor Relay

Current status of LLS/compressor relay

dEr

dEr

DEFROST RELAY

Defrost Relay

Current Status of Defrost relay

FAr

FAr

FAN RELAY

Fan Relay

Current Status of Fan relay

AU1

AU1

DIG 1 STATUS

Aux Input 1

Current Status/Temperature as measured by con-

troller at Aux input 1

AU2

AU2

DIG 2 STATUS

Aux Input 2

Current Status/Temperature as measured by con-

troller at Aux input 2

AU3

AU3

DIG 3 STATUS

Aux Input 3

Current Status/Temperature as measured by con-

troller at Aux input 3

iP1

iP1

IP OCTET 1

IP Address Part 1

First 3 digits of IP address

iP2

iP2

IP OCTET 2

IP Address Part 2

Second 3 digits of IP address

iP3

iP3

IP OCTET 3

IP Address Part 3

Third 3 digits of IP address

iP4

iP4

IP OCTET 4

IP Address Part 4

Fourth 3 digits of IP address

Fir

Fir

FIRMWARE VERSION

Firmware Version

Current Version of firmware on controller

System Modes

ABR.

ON-BOARD 

DISPLAY

DASHBOARD 

DISPLAY

FULL NAME / DESCRIPTION

rEF

rEF

REFRIGERATE

Refrigeration

ddF

ddF

DEFROST DELAY FAN

Defrost Delay Fans

dEF

dEF

DEFROST

Defrost

drn

drn

DRAIN TIME

Drain Time

FdL

FdL

FAN DELAY

Fan Delay

SoF

SoF

SYSTEM OFF

System Off (External System Off)

oFF

oFF

OFF

Off (Satisfied on Temperature)

Refrigerants

ABBREVIATION

FULL NAME

R22

R-22

134

R-134a

42d

R-422D

42A

R-422A

40C

R-407C

40A

R-407A

507

R-507

404

R-404A

513

R-513A

450

R-450A

449

R-449A

448

R-448A

744

R-744

410

R-410A

407

R-407F

409

R-409A

408

R-408A

438

R-438A

717

R-717

452

R-452A

MENUS AND PARAMETERS (cont’d)

T30-ESP-OM--1

11/09/20

- 6 -

Содержание ESP+

Страница 1: ...Support Resources 2 3 3 6 7 8 9 10 11 12 14 15 17 BACK Intuitive Evaporator Control Technology Bulletin T30 ESP OM 2 1 Part 1107522 OPERATING INSTRUCTIONS PRODUCT SUPPORT web www t rp com esp email e...

Страница 2: ...default view Manual Valve Control Press and hold the BACK button arrow to put the EEV in Manual Control mode and arrows will control the valve opening ENTER will advance to the next digit and BACK wi...

Страница 3: ...ULT DESCRIPTION tS tS ROOM TEMP Room Temp Setpoint 50 0 F 90 0 F 10 F or 35 F Walk in freezer 10 F or cooler 35 F room temp to be main tained rFG rF REFRIGERANT Refrigerant N A N A R 404A Type of refr...

Страница 4: ...or The amount of time in minutes before an alarm condition is initiated if door is open room temperature is 5 degrees above ROOM TEMP AIR TEMP DIFF AU1 AU1 AUX IN 1 MODE Aux Input 1 mode N A N A Coil...

Страница 5: ...vap Defrost Synchronized or Independent Synchronized Synchronized synchronize bonded controller in defrost mode Inde pendent bonded controllers defrost independently MULTI EVAP SENSOR Multi Evap Senso...

Страница 6: ...umber of times to maintain suction pressure LPA LPA LOW PRESSURE Low Pressure Alarm Suction pressure dropped below expected point excessive number of times PrF PrF N A Process Failure Basic Display is...

Страница 7: ...List sticker on the inside of the access panel of the evaporator 5 On a computer connected to the same network as your ESP controller open any browser Chrome Firefox Edge etc 6 Enter the ESP controll...

Страница 8: ...iP1 5 Record the four IP iP1 iP2 iP3 iP4 values a Use the and arrows to find iP1 iP1 c Press and release the ENTER button to display the current setting d Record this number e Press the BACK button f...

Страница 9: ...If using a mobile device open the WIFI network settings to see available networks There are 2 wireless networks available a KE2WIFIST wireless network is Open and no password is required b KE2LDA wir...

Страница 10: ...Select submit or press enter on your keyboard 7 Click Discover The IP addresses of the available controllers will populate Click OK if prompted by browser to confirm 8 Type 1 in the Bond State area of...

Страница 11: ...method is used to control the temperature 16 Click Save to save the settings 17 The second controller and subsequent controllers must be configured to match the Multi settings of the first controller...

Страница 12: ...SAMPLE WIRING DIAGRAM 208 230 1 60 AIR DEFROST MODELS w SAMPLE ONLY Refer to Product Data and Installation for details specific to your unit SAM PLE O N LY T30 ESP OM 1 11 09 20 12...

Страница 13: ...SAMPLE WIRING DIAGRAM 208 230 1 60 ELECTRIC DEFROST MODELS w SAMPLE ONLY Refer to Product Data and Installation for details specific to your unit SAM PLE O N LY T30 ESP OM 1 11 09 20 13...

Страница 14: ...CLo Closed Setpoint Option for Aux Input State A1A A2A A3A setpoints Input will be Active when it reads a closed circuit CLt CLt Coil Temp Variables Coil temperature TCoil Sensor as measured by the co...

Страница 15: ...drops on the walk in s surfaces Fir Fir Firmware Version Variables Current version of the firmware on the controller FoC FoC Fans on with Compressor Setpoint Option under Refrig Fan Type rFt setpoint...

Страница 16: ...by the Auxiliary Input SA SA KE2 Smart Access Setpoint Turn KE2 Smart Access on or off EnA enable KE2 Smart Access diS disable KE2 Smart Access SAt SAt Saturation Temp Variables Saturation temperature...

Страница 17: ...NOTES T30 ESP OM 1 11 09 20 17...

Страница 18: ...NOTES T30 ESP OM 1 11 09 20 18...

Страница 19: ...PRODUCT SUPPORT RESOURCES Visit www t rp com esp for product information manuals FAQ and more T30 ESP OM 1 11 09 20 19...

Страница 20: ...com call 1 844 893 3222 x501 email shipping t rp com call 1 844 893 3222 x503 web www t rp com warranty email warranty t rp com call 1 844 893 3222 x507 Due to the manufacturer s policy of continuous...

Отзывы: