MENUS AND PARAMETERS (cont’d)
ADVANCED Setpoints Menu
Press and hold the
BACK
button to enter the
Advanced Setpoints
menu.
ABR.
ON-BOARD
DISPLAY
DASHBOARD
DISPLAY
FULL NAME
MIN
MAX
DEFAULT
DESCRIPTION
FoC
FOC
FANS ON COMP
Fans on with Compres-
sor
—
—
—
Manage fans in OFF, then ON in refrigeration
PEr
PEr
FANS PERMANENT
Permanent Fan
—
—
—
Fans on permanently during refrigeration cycle - RECOMMENDED
CYC
CYC
CYCLE
Cycle
—
—
—
Cycle (Managed) manage fans during refrig cycle. Not Recom-
mended for Equipment Equipped with 2 Speed EC Motors (Smart-
Speed) or Variable Speed EC Motors
t24
t24
TITLE 24
Title 24
—
—
—
Cycle fans based on compliance with California Title 24 regula-
tions (Available only with Equipment Equipped with Variable
Speed EC Motors)
Stt
Stt
SUPERHEAT
Superheat
5.0 °F
30.0 °F
8.0 °F
Target superheat value. Not available on Basic Display
LPt
LPt
LOW PRESSURE
CUT OUT TIME
Low Pressure Cut Out
Time
0 min
15 min
0 min
Only applies when non-mechanical valve selected; 0=Disabled
LPC
LPC
LOW PRESSURE
CUT OUT
Low Pressure Cut Out
-5.0 psig 138.0 psig
8.0 psig
Displays when LOW PRESSURE CUTOUT TIME (LPt) is
greater than zero. And,only applies if non-mechanical valve is
selected
LPd
LPd
PRESS DIFF FOR
LPCO
Pressure Differential
for LPCO
1.0 psig 20.0 psig
15.0 psig
Displays when LOW PRESSURE CUTOUT TIME (LPt) is
greater than zero. And,only applies if non-mechanical valve is
selected
Att
Att
LPCO ATTEMPTS
CONTACT FACTORY
1
5
5
If LPt greater then 0: Advanced topic. CONTACT FACTORY
rnt
rnt
COMP RUN TIME
Compressor Run Time
0 hrs
24 hrs
6 hrs
When rnt selected, number of hours of cooling before starting
defrost
Htn
Htn
ELECTRIC DE-
FROST MODE
Electric Defrost Mode
N/A
N/A
Permanent for
AD /
Pulse for ED
If DEFROST TYPE = ELE: Whether to leave the defrost relay
energized during the defrost cycle or to utilize advanced
defrost algorithm. PUL = Pulse, Prn = Permanent
HAo
HAo
HIGH TEMP
ALARM OFFSET
High Temp Alarm
Offset
0 °F
99.9 °F
10.0 °F
The number of degrees above ROOM TEMP for a HIGH TEMP
ALARM condition.
HAd
HAd
HIGH TEMP
ALARM DELAY
High Temp Alarm Delay
0 min
120 min
60 min
Minutes the room temperature must remain above ROOM TEMP
+ HIGH TEMP ALARM OFFSET before issuing a HIGH TEMP
ALARM
LAo
LAo
LOW TEMP
ALARM OFFSET
Low Temp Alarm Offset
0 °F
20.0 °F
4.0 °F
The number of degrees below ROOM TEMP for a LOW TEMP
ALARM condition.
LAd
LAd
LOW TEMP
ALARM DELAY
Low Temp Alarm Delay
0 min
30 min
10 min
Minutes the room temp must remain below ROOM TEMP-LOW-
TEMP ALARM OFFSET before issuing a LOW TEMP ALARM
dAd
dAd
DOOR ALARM
DELAY
Door Alarm Delay
0 min
180 min
30 min
If AU IN (1, 2 and/or 3) MODE = dor The amount of time, in
minutes, before an alarm condition is initiated, if door is open
& room temperature is 5 degrees above ROOM TEMP + AIR
TEMP DIFF
AU1
AU1
AUX IN 1 MODE
Aux Input 1 mode
N/A
N/A
Coil Temp See Auxiliary Input Modes table
A1A
A1A
AUX IN 1 STATE
Aux Input 1 state
N/A
N/A
Closed
oPn= active if input is an open / CLo=active if input is shorted
AU2
AU2
AUX IN 2 MODE
Aux Input 2 mode
N/A
N/A
Disabled
See Auxiliary Input Modes table
A2A
A2A
AUX IN 2 STATE
Aux Input 2 state
N/A
N/A
Closed
oPn= active if input is an open / CLo=active if input is shorted
AU3
AU3
AUX IN 3 MODE
Aux Input 3 mode
N/A
N/A
Sys Off
See Auxiliary Input Modes table
A3A
A3A
AUX IN 3 STATE
Aux Input 3 state
N/A
N/A
Closed
oPn= active if input is an open / CLo=active if input is shorted
tS2
tS2
ROOM TEMP
2nd room temp SP
-50.0 °F
90.0 °F
-50.0 °F
If AU IN (1, 2 and/or 3) MODE = (t2n) 2ND ROOM TEMP: This
value becomes the ROOM TEMP setpoint when the digital input
is active
10t
10t
0 TO 10 VDC MODE
CONTACT FACTORY
-
-
Alarm Relay (ALr) Alarm relay. (FSd) Evap Fan Speed Control. (dAL) Door
alarm relay.
tEt
tEt
MULTI EVAP MODE
CONTACT FACTORY
-
-
Off
Mode for Lead/Lag operation. (oFF) Off. (LGC) Redundant
Cool. (LGF) Redundant Off. (ALt) Alternate.
PAd
PAd
PAIRED DEFROST
MODE
CONTACT FACTORY
-
-
Off
Select operation when lead/lag pair controller goes into
defrost. (oFF) Off. (AUt) Auto.
LLt
LLt
LEAD/LAG TIME
CONTACT FACTORY
1 hour 168 hours
12 hours
Time to toggle between lead/lag
Unt
Unt
TEMP UNITS
temperature units
N/A
N/A
Fahrenheit Units for temperature’s display in °F or °C; FAH = Fahrenheit,
CEL = Celsius
EdF
EdF
EXTREME TEMP
DIFF
Extreme Temp Diff.
0
0
F
99.9 °F
20.0 °F
ADVANCED TOPIC: Call factory for assistance
CLA
CLA
CLEAR ALARMS
Clear Alarms
N/A
N/A
Press and hold to clear all active alarms
PAS
PAS
WEB PASSWORD
RESET
Web password reset
N/A
N/A
Press and hold to reset the web password to the factory
default
PAr
PAr
PAIR L/L
Pair controllers
-
-
-
Press and hold ENTER until red LED blinks.
(PAS) successful pairing. (FAi) pairing failed.
Only two controllers can be present on network.
UnP
UnP
UNPAIR L/L
Unpair controllers
-
-
-
Press and hold ENTER until red LED blinks.
(PAS) successful unpairing. (FAi) unpairing failed.
bnd
bnd
BOND
Bond controllers
-
-
-
Press and hold ENTER until red LED blinks.
(PAS) successful bond. (FAi) bond failed. Only two controllers
can be present on network to bond from display.
Unb
Unb
UNBOND
Unbond controllers
Press and hold ENTER until red LED blinks. Controllers will un-
bond and restart. Only works if bonded to one other controller.
SA
SA
SMART ACCESS
Smart Access
N/A
N/A
Disabled
Turn Smart Access on or off: EnA to enable smart access /
diS to disable Smart Access (CONTACT FACTORY)
dHC
dHC
DHCP
DHCP Mode
N/A
N/A
Disabled
Turn DHCP mode on or off: EnA to enable DHCP mode / diS to
disable DHCP mode
T30-ESP-OM--1
11/09/20
- 4 -