Trenton ESP+ Скачать руководство пользователя страница 16

ABR.

REMOTE 

DISPLAY

FULL NAME 

 TYPE 

DESCRIPTION 

ription

NTP

ntp

Time Server Comm Alarm

Alarms

Controller cannot communicate with external time of day server (SNTP server).

oFF

oFF

Off

System Mode

System has satisfied on temperature.

oFF

oFF

Defrost Heaters Off

Auxiliary Input

Defrost Interlock is active on the Auxilliary Input, defrost heaters forced off (oFF).

oFF

oFF

Off (Lead/Lag)

Setpoint

Option for Multi Evap Mode (tEt) setpoint.  (oFF)  lead/lag control is disabled.

oni

on

i

Monitor Temp

Auxiliary Input

Monitor Temp as measured by the Auxiliary Input.

oPn

oPn

Valve % Open

Variables

Percentage the EEV is open (only available if EEV is selected).

oPn

oPn

Open

Setpoint

Option for Aux Input State (A1A, A2A, A3A) setpoints.  Input will be Active when it reads an open 

circuit.

PAR

PAr

Pair L/L

Setpoint

Press and hold ENTER until red LED blinks.  (PAS) successful pairing.  (FAi) pairing failed.  

Only two controllers can be present on network. 

PAS

PAS

Web password reset

Setpoint

Press and hold to reset the web password to the factory default.

Pdt

Pdt

Pump Down Timeout

Alarms

Max time for LPCO pumpdown exceeded.

PEr

PEr

Permanent Fan

Setpoint

Option for Refrig Fan Type (rFt) setpoint. (PEr) permanent forces fans to run during off cycle.

PrF

PrF

Process Failure

Alarms

KE2 Remote (Basic) Display is not communicating to the controller.

Prn

Prn

Permanent 

Setpoint

Option for Electric Defrost Mode (Htn) setpoint.  Applies if DEFROST TYPE = ELE.  Permanent 

(Prn) forces the defrost relay to stay energized during the entire defrost cycle.

PrS

PrS

Suction Pressure

Variables

Suction pressure measured by the controller (only available if suction pressure transducer 

used).

PSA

PSA

Pressure Sensor Alarm

Alarms

Suction pressure sensor is shorted, open or pressure out of range.

PUL

PUL

Pulse

Setpoint

Option for Electric Defrost Mode (Htn) setpoint.  Applies if DEFROST TYPE = ELE.  Pulse (PUL) 

uses the advanced defrost algorithm to manage the defrost relay during the defrost cycle.

rEF

rEF

Refrigeration

System Mode

System is currently in Refrigeration mode.

rFG

rF

G

Refrigerant

Setpoint

Refrigerant used.  See table on page 10.

rFt

rft

Refrigeration Fan Type

Setpoint

Select evaporator fan management.  (CYC) cycle, i.e. manage, fans during refrigeration and 

off cycle.  (FoC) fans on w/ compressor will primarily manage fans only during the off cycle.  

(PEr) permanent forces fans to run during refrigeration and off cycle.  (t24)  Title 24 cycles 

fans based on Title 24 regulations.

rnt

rnt

Compressor Run Time

Setpoint

Option for Defrost Initiation Mode (ind) setpoint.  (rnt) Compressor Run Time,  system will de-

frost after a set number of cumulative hours of run time.  Other options are (SCH) Scheduled, 

and (dnd) Demand Defrost.

rS

r5 

RSV

Valve Type

Pre-configured EEV selection.  (RSV) KE2 Therm’s Refrigeration Stepper Valve.

rtP

rtp

Room Temp

Variables

Walk-in freezer or cooler room temperature (TAir Sensor) as measured by the controller.

rtP

rtp

Room Temp

Auxiliary Input

Room temp as measured by the Auxiliary Input.

SA

SA 

KE2 Smart Access

Setpoint

Turn KE2 Smart Access on or off.  (EnA) enable KE2 Smart Access.  (diS) disable KE2 Smart 

Access.

SAt

SAt

Saturation Temp

Variables

Saturation temperature as calculated by the controller (requires suction pressure transducer 

and T1 suction temperature sensor).

SCC

SCC

Short Compressor Cycle

Alarms

Compressor has started an excessive number of times to maintain suction pressure.

SCH

SCH

Scheduled Defrost

Setpoint

Option for Defrost Initiation Mode (ind) setpoint.  (SCH) Scheduled,  system will defrost a set 

number of times per day, spaced evenly throughout the day.  Other options are (dnd) Demand 

Defrost, and (rnt) Compressor Run Time.

SEi

SE

i

SEI

Valve Type

Pre-configured EEV selection.  Sporlan Valve with 1,600 Steps.

SEr

SEr

SER

Valve Type

Pre-configured EEV selection.  Sporlan Valve with 2,500 Steps

SHt

SHt

Superheat

Variables

Superheat as calculated by the controller (requires suction pressure transducer and T1 suc-

tion temperature sensor).

SoF

SoF

System Off Switch

Auxiliary Input

Inactive (Son), system runs as normal.  Active (SoF), system enters pumpdown mode and will 

not refrigerate or defrost until cleared.

SoF

SoF

System Off

System Mode

System off has been activated from the display, or by an external signal to an Auxiliary Input.

Son

Son

System Off Switch - System On

Auxiliary Input

System Off Auxiliary Input is Inactive (Son), system runs as normal.  

SSA

SSA

Suction Sensor Alarm

Alarms

Suction temperature sensor is shorted or open.

Stt

Stt

Superheat

Setpoint

Target superheat value. Only applies when non-mechanical valve selected.  When mechanical 

valve is selected, it is the high superheat alarm threshold.

SUt

SUt

Suction Temp

Variables

Suction Temperature as measured by controller.

SYS

S

Y

S

System Mode

Variables

Current operating status.

t2F

t2F

2nd Room Temp Setpoint Off

Auxiliary Input

2nd Temp Auxiliary Input is Inactive (t2f).  System is controlling to the regular Room Temp 

setpoint.

t2n

t2n

2nd Temp Switch Setpoint On

Auxiliary Input

2nd Temp Auxiliary Input is Active (t2n).  System is controlling to the 2nd Room Temp 

Setpoint.

tHr

tHr

Mechanical

Valve Type

Thermostatic Expansion Valve in the Expansion Device Type (Edt) setpoint.

t24

t24

Title 24

Setpoint

Option for Refrig Fan Type (rFt) setpoint. (t24) Title 24, cycle fans to comply with California 

Title 24 regulations.  

tEt

tEt

Multi Evap Mode

Setpoint

Mode for lead/lag operation.  (oFF) Off.  (LGC) Redundant cool.  (LGF) Redundant off.  (ALt) 

Alternate.

tS

tS 

Room Temp SP

Setpoint

Room temperature to be maintained.

tS2

tS2

2nd room temp SP

Setpoint

If AU1, AU2, or AU3 = (t2n) 2ND ROOM TEMP:  This value becomes the ROOM TEMP setpoint 

when the Auxiliary Input is active.

Unb

Unb

Unbond

Setpoint

Press and hold ENTER until red LED blinks.  Controllers will unbond and restart.  Only works if 

bonded to one other controller.

UnP

UnP

Unpair L/L

Setpoint

Press and hold ENTER until red LED blinks.  (PAS) successful unpairing.  (FAi) unpairing 

failed.

Unt

Unt

Temperature Units

Setpoint

Option for Temp Units (Unt) setpoint.  (FAH) Fahrenheit.  (CEL) Celsius.

GLOSSARY OF ABBREVIATIONS (cont’d)

Alphabetical List of Abbreviations (continued)

T30-ESP-OM--1

11/09/20

- 16 -

Содержание ESP+

Страница 1: ...Support Resources 2 3 3 6 7 8 9 10 11 12 14 15 17 BACK Intuitive Evaporator Control Technology Bulletin T30 ESP OM 2 1 Part 1107522 OPERATING INSTRUCTIONS PRODUCT SUPPORT web www t rp com esp email e...

Страница 2: ...default view Manual Valve Control Press and hold the BACK button arrow to put the EEV in Manual Control mode and arrows will control the valve opening ENTER will advance to the next digit and BACK wi...

Страница 3: ...ULT DESCRIPTION tS tS ROOM TEMP Room Temp Setpoint 50 0 F 90 0 F 10 F or 35 F Walk in freezer 10 F or cooler 35 F room temp to be main tained rFG rF REFRIGERANT Refrigerant N A N A R 404A Type of refr...

Страница 4: ...or The amount of time in minutes before an alarm condition is initiated if door is open room temperature is 5 degrees above ROOM TEMP AIR TEMP DIFF AU1 AU1 AUX IN 1 MODE Aux Input 1 mode N A N A Coil...

Страница 5: ...vap Defrost Synchronized or Independent Synchronized Synchronized synchronize bonded controller in defrost mode Inde pendent bonded controllers defrost independently MULTI EVAP SENSOR Multi Evap Senso...

Страница 6: ...umber of times to maintain suction pressure LPA LPA LOW PRESSURE Low Pressure Alarm Suction pressure dropped below expected point excessive number of times PrF PrF N A Process Failure Basic Display is...

Страница 7: ...List sticker on the inside of the access panel of the evaporator 5 On a computer connected to the same network as your ESP controller open any browser Chrome Firefox Edge etc 6 Enter the ESP controll...

Страница 8: ...iP1 5 Record the four IP iP1 iP2 iP3 iP4 values a Use the and arrows to find iP1 iP1 c Press and release the ENTER button to display the current setting d Record this number e Press the BACK button f...

Страница 9: ...If using a mobile device open the WIFI network settings to see available networks There are 2 wireless networks available a KE2WIFIST wireless network is Open and no password is required b KE2LDA wir...

Страница 10: ...Select submit or press enter on your keyboard 7 Click Discover The IP addresses of the available controllers will populate Click OK if prompted by browser to confirm 8 Type 1 in the Bond State area of...

Страница 11: ...method is used to control the temperature 16 Click Save to save the settings 17 The second controller and subsequent controllers must be configured to match the Multi settings of the first controller...

Страница 12: ...SAMPLE WIRING DIAGRAM 208 230 1 60 AIR DEFROST MODELS w SAMPLE ONLY Refer to Product Data and Installation for details specific to your unit SAM PLE O N LY T30 ESP OM 1 11 09 20 12...

Страница 13: ...SAMPLE WIRING DIAGRAM 208 230 1 60 ELECTRIC DEFROST MODELS w SAMPLE ONLY Refer to Product Data and Installation for details specific to your unit SAM PLE O N LY T30 ESP OM 1 11 09 20 13...

Страница 14: ...CLo Closed Setpoint Option for Aux Input State A1A A2A A3A setpoints Input will be Active when it reads a closed circuit CLt CLt Coil Temp Variables Coil temperature TCoil Sensor as measured by the co...

Страница 15: ...drops on the walk in s surfaces Fir Fir Firmware Version Variables Current version of the firmware on the controller FoC FoC Fans on with Compressor Setpoint Option under Refrig Fan Type rFt setpoint...

Страница 16: ...by the Auxiliary Input SA SA KE2 Smart Access Setpoint Turn KE2 Smart Access on or off EnA enable KE2 Smart Access diS disable KE2 Smart Access SAt SAt Saturation Temp Variables Saturation temperature...

Страница 17: ...NOTES T30 ESP OM 1 11 09 20 17...

Страница 18: ...NOTES T30 ESP OM 1 11 09 20 18...

Страница 19: ...PRODUCT SUPPORT RESOURCES Visit www t rp com esp for product information manuals FAQ and more T30 ESP OM 1 11 09 20 19...

Страница 20: ...com call 1 844 893 3222 x501 email shipping t rp com call 1 844 893 3222 x503 web www t rp com warranty email warranty t rp com call 1 844 893 3222 x507 Due to the manufacturer s policy of continuous...

Отзывы: