T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015.

T/PI 

Installation Instructions 

2

Requirements

2 InSTallaTIon 

(continued)

H O

2

0 %RH 

95 %RH

Protection 

: IP67 (NEMA6)

Ensure  no  stratification  (e.g. 

downstream  of  mixing  valves, 

junctions) 

d

-40 °C 

(-40 °F)

+50 °C 

(+122 °F)

-40 °C 

(-40 °F)

+110 °C 

(+230 °F)

to

to

Immersion

Immersion

Measurement range 

(minimum distance from junctions =10xd).

/40

  -10 °C 

(14 °F)

+40 °C

(104 °F)

/110

  -10 °C 

(14 °F)

+110 °C 

(230 °F)

/-40

  -40 °C 

(-40 °F) 

+50 °C

(122 °F)

-40 °C 

(-40 °F)

+50 °C 

(+122 °F)

to

-40 °C 

(-40 °F)

+110 °C 

(+230 °F)

to

Duct

Ensure no stratification 

(e.g. downstream of mixing 

dampers, heating coils, 

cooling coils) otherwise 

use averaging sensor.

Duct

Immersion

Cl

2

Note: WS150 or WB150 are NOT suitable for use in chlorine 

rich environments

Immersion

Содержание T/PI

Страница 1: ...ttps partners trendcontrols com 1 Dimensions 2 Installation 1 Box Contents T PI Installation Instructions TG200825 Pockets for use as immersion sensor Brass WB150 Stainless Steel WS150 6 mm 0 24 T PI...

Страница 2: ...40 C 40 F 50 C 122 F 40 C 40 F 110 C 230 F to to Immersion Immersion Measurement range minimum distance from junctions 10xd 40 10 C 14 F 40 C 104 F 110 10 C 14 F 110 C 230 F 40 40 C 40 F 50 C 122 F 4...

Страница 3: ...nto probe Adjust probe length Mount in pocket if pocket has grub screw discard spring and clip clip spring brass brush tighten use 2 mm hexagonal socket key pocket length clip engages in groove probe...

Страница 4: ...No 6 3 4 s s self tapping screws integral foam gasket Or Use compression fitting compression fitting duct mounting flange Separate compression fitting Loosen nut Unscrew fitting Or for thinner materi...

Страница 5: ...e screen at IQ end only Analogue input channel configured for current I IQ system TP I 22 HF 200 600V Belden 8761 cable recommended Terminal size 0 5 to 2 5 mm2 20 to 14 AWG Note if connecting to an I...

Страница 6: ...ector 10 Replace lid 11 Con gure Controller 2 InSTallaTIon continued Note IP67 NEMA6 rating is only achieved if the sensor is correctly installed with cable or conduit connection fully tightened IQ IQ...

Страница 7: ...40 T PI 40 C PRT I 14 104 F T PI 40 F PRT I 10 110 T PI 110 C PRT I 14 230 F T PI 110 F PRT I 40 50 T PI 40 C PRT I 40 122 F T PI 40 F Alternatively set scaling mode to 5 characterise and enter scalin...

Страница 8: ...tzerland by its Authorized Representative Trend Control Systems Limited Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content he...

Отзывы: