T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015. 7
Installation Instructions
T/PI
13
Test System
12
Set up Sensor Type
2 InSTallaTIon
(continued)
It is recommended to use SET (Software Tool) for the setting
of the sensor type module. For all IQ2 series controllers with
firmware version 2.1 or greater, or IQ3/4 series controllers,
the following SET Unique Sensor References should be used:
PRT
I
-10+40
(T/PI/40, °C)
PRT
I
+14+104 F
(T/PI/40, °F)
PRT
I
-10+110
(T/PI/110, °C)
PRT
I
+14+230 F
(T/PI/110, °F)
PRT
I
-40+50
(T/PI/-40, °C)
PRT
I
-40+122 F
(T/PI/-40, °F)
Alternatively set scaling mode to 5 (characterise) and enter
scaling manually as defined in the appropriate table.
Note: for IQ3/4, the scaling mode and exponent do not need
to be set up.
For all other IQ controllers see Sensor Scaling Reference
Card (TB100521A).
Unit
/40
/110
/-40
Y
input type
2 (current)
2 (current)
2 (current)
E
Exponent
3
3
3
Units
°C
°F
°C
°F
°C
°F
U
Upper
40
104
110
230
50
122
L
Lower
-10
14
-10
14
-40
-40
P
Points
2
2
2
2
2
2
x
Ix
Ox
Ox
Ox
Ox
Ox
Ox
1
4
-10
14
-10
14
-40
-40
2
20
40
104
110
230
50
122
∆
T
IQ