IQ4E/.. Installation Instructions - Mounting TG201338 Issue 4, 19-Jan-2016. Applies to v3.33. 5

Installation Instructions - Mounting IQ4E/..

9

Connect Universal Inputs IN1 to IN10 

(if required)

8

Connect Inputs/outputs - overview

3 INsTAllATIoN 

(continued)

Note: The input type (i.e. voltage, thermistor, digital or current) 

is defined in the controller’s strategy.

ensure correct 

polarity

Thermistor input

Current input

Voltage input

Digital input

Terminal size:  

0.5 to 2.5 mm

2

 (20 to 14 AWG).

Terminal screw torque: 0.45 to 0.62 Nm (4 to 5.5 lb.in).

TP/1/1/22/HF/200 (Belden 8761) cable recommended for all 

inputs/outputs.

Screened  cable  is  not  generally  required  unless  the  cable 

passes  through  electrically  noisy  environments.  Where  it 

is  used  the  screen  must  be  connected  to  the  local  panel/

enclosure ground and left unterminated at the far end.

Plug-in connectors with screw terminals

n

n

n

S

+

-

n

n

n

0 to 10 Vdc

S

n

n

n

24V

AUX

n

n

n

n

S

Externally powered

Loop powered (using AUX output supply - see step 11)

External 

Power 

Supply

ensure correct 

polarity

ensure correct 

polarity

Common (C) terminal is linked internally to AUX 

supply common - no connection required

volt free 

contact

open 

collector

n

n

n

ensure correct 

polarity

logic

circuit

270 μA

TTL / 

CMOS

0V

Содержание IQ4E

Страница 1: ...reinforced insulation 3 Installation 1 Box Contents 2 Storing Contents 1 Box Contents 1 2 Storing 1 3 Installation 1 Note For temperatures below 0 C 32 F special care must be taken that there is no co...

Страница 2: ...tinued Must be installed in an enclosure rated to at least IP20 or equivalent Note For temperatures below 0 C 32 F special care must be taken that there is no condensation on or within the unit Protec...

Страница 3: ...structions Mounting IQ4E 3 Mount Unit on DIN Rail 4 Attach large Barcode label to Panel 5 open Rotating Covers 3 INsTAllATIoN continued I QECO Q3 B_ X7 3 0 8 0 0 3 1 SERIAL No IQ4e Q3B_X73080031 TREND...

Страница 4: ...0 C or greater This equipment must be earthed grounded 230 230 Vac 10 50 60 Hz at up to 70 VA The 230 V supply must include a dedicated 5 A fuse complying with IEC60269 BS1362 and a suitably rated swi...

Страница 5: ...5 lb in TP 1 1 22 HF 200 Belden 8761 cable recommended for all inputs outputs Screened cable is not generally required unless the cable passes through electrically noisy environments Where it is used...

Страница 6: ...equired 11 Connect Auxiliary Supply Output s if required 3 Installation continued Output voltage 0 to 10 Vdc Maximum current 20 mA source 3mA sink Output voltage 24 Vdc 5 Maximum current Terminals 70...

Страница 7: ...ystem 4 wire system T R T R T R T R panel enclosure ground T R R X T Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Maximum cable length depends on cab...

Страница 8: ...nnection to an RS 485 4 wire system a suitable 2 to 4 wire converter will be required RS 232 system RJ12 FFC68 Plug Local Supervisor Port 1 RX 2 NC 3 CTS 4 RTS 5 GND 6 TX TX RX RTS CTS GND pin 1 Note...

Страница 9: ...d Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Cable type Unscreened twisted pair Maximum cable length 60 m 200 ft in total used to connect all wallb...

Страница 10: ...rigid interconnectors Maximum number of I O modules on I O bus IQ4 IO Installation Instructions Mounting TG201338 XCITE IO Installation Instructions Mounting TG200627 cable interconnection XCITE CC c...

Страница 11: ...ose Rotating Covers 17 Close Panel Enclosure 18 Configure IQ4E Controller and I O Modules 1 Remove from DIN rail 3 INsTAllATIoN continued IQ4E Installation Instructions Configuring TG201339 IQ4 IO Ins...

Страница 12: ...end Control Systems Ltd s software suppliers HAS RELIED UPON Trend Control Systems Ltd TO CONDUCT SUFFICIENT TESTING TO DETERMINE THAT THE SOFTWARE IS SUITABLE FOR SUCH USE NO WARRANTIES FOR THE SOFTW...

Отзывы: